9 Operation
100
Rev. 06/2020
7.
Enter the value in the column
NOx inlet
of the Excel
®
file.
Example:
8.
Open the dosing valve manually via the menu item
Device -> Manual Valve Adjustment
until
the NO
X
value at the catalytic converter outlet corresponds to the desired final value (e.g.
30 ppm) in the window
Runtime Data – Sensors
. Refer to the section
Manual Valve
Adjustment
on page 54.
9.
Enter the value for the percentage opening in the column
Target Valve Opening
.
Example: