6. Operation
38
3 - Turn the control panel power switch (2) ON.
2
D5260440
4 - Press the start button (3) to launch the generating set
start sequence.
Note:
The start button only works in MAN mode.
5 - Before supplying a load, let the engine run for the time
shown in the following table.
Ambient temperature
Time required
≤ -20°C
5 minutes
-19°C – -10°C
2 minutes
-9°C – -5°C
1 minute
≤ -4°C
20 seconds
Note:
For starting and use at temperatures below -10°C, refer
to the engine instruction manual or contact the Technical
Support Service.
3
D5260450
6 - Set the main machine residual current circuit breaker
with overcurrent protection (1) to ON (insertion lever
upwards).
7 - Turn all residual current circuit breaker with overcur-
rent protection (RCBO) and the residual current circuit
breakers that protect the utilities connected to the output
sockets to ON.
4
D5260660
1
Note:
•
It is advisable not to set the switches of unused output sockets to ON.
•
Before powering the utilities, check that the values of the voltages and the frequency correspond to the
rated values on the control unit.