31
5. Installation
W: Generating set width
L: Generating set length
H: Generating set height
A: >1000 mm
B: >500 mm
C= H+1500 mm (Min. 2500 mm)
5.
Installation
WARNING
•
Before proceeding with the installation, carefully read section
Safety - “2.6 Installation precau-
tions” and “2.7 Precautions during operation”.
•
The installation and the electrical connection described in this chapter are indicative.
For these operations, it is necessary to contact Specialized Technicians who must issue the
necessary certifications.
5.1 Fastening
•
Fix the generating set on rigid pitches, isolated against vibrations coming from other structures and with
a mass equal to at least three times the mass of the generating set.
This guarantees an adequate absorption of the vibrations produced by the machine.
•
Do not place the generating set on terraces or raised floors that have not been adequately sized and
verified beforehand.
5.2 Installation outdoors
WARNING
•
If the outdoor installation is temporary, correctly place the generating set on the ground.
This prevents vibrations on the frame during operation from causing the generating set to
move, in particular when the electrical load is on.
Example of installation with shelter
A
B
B
A
W
L
H
C
D5260260
Fig. 1