
5. Installation
32
5.3 Indoor installation
*
Important
•
The room where the generating set will be installed must comply with the legislation in force at the
place of installation.
Installation of the generating set indoor must be carried out in accordance with the instructions described.
8
10
9
1
4
3
5
7
2
6
B
A
E
D
C
H
D5260270
Fig. 2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Generating set
Auxiliary extractor
Exhaust pipes
Exhaust pipe protection and insulation
Rain cap and anti-intrusion hood
Air ejection duct
Platform with insulated foundation
Air inlet with anti-intrusion mesh
Entrance door
Containment step
Recommended minimum size
(A)
(B)
(C)
(D)
(E)
(H)
Generating set 1000 mm
Generating set width + 2000 mm
Generating set width + 200 mm
Generating set 400 mm
Generating set width + 400 mm
Generating set 1500 mm (Min. 2500
mm)
Содержание RENTAL GE 50 KR-5
Страница 2: ......
Страница 10: ...2 Safety 6 2 2 Positioning of safety decal and information 1 2 2 3 4 5 5 5 5 6 6 7 7 8 9 10 11 6 D5260040...
Страница 58: ...7 Maintenance 54 NOTES...
Страница 66: ...8 Alarms 62 NOTES...
Страница 67: ......