Using the generator

I

GB

F

The  frequency,  and  therefore  the  number  of  motor 

revolutions, is maintained constant by the motor’s speed 

regulation system.

Generally,  this  regulator  is  of  a  mechanical  type  and 

presents a droop from no-load to nominal load  which 

is  less  than  5  %  (static  or  droop),  while  under  static 

conditions precision is maintained within ±1%.Therefore, 

for  generators  at  50Hz  the  no-load  frequency  can  be 

52–52.5 Hz, while for generators at 60Hz the no-load 

frequency can be 62.5-63Hz.

In some motors or for special requirements the speed 

regulator is electronic; in these cases, precision under 

static    operating  conditions  attains  ±0.25%,  and  the 

frequency is maintained constant in operation from no-

load to load (isochronal operation).

POWER FACTOR - COS 

ϕ

The power factor is a value which depends on the load’s 

electrical  specifications;  it  indicates  the  ratio  between 

the Active Power (kW) and Apparent Power (kVA). The 

apparent power is the total power necessary for the load, 

achieved  from  the  sum  of  the  active  power  supplied 

by the motor (after the alternator has transformed the 

mechanical power into electrical power), and the Reactive 

Power (kVAR) supplied by the alternator. The nominal 

value for the power factor is cos

 ϕ

 = 0,8; for different 

values comprised between 0.8 and 1 it is important during 

usage not to exceed the declared active power (kW), so 

as to not overload the electricity-generating group motor; 

the apparent power (kVA) will diminish proportionally to 

the increase of cos 

ϕ

.

For cos 

ϕ

 values of less than 0.8 the alternator must 

be  downgraded,  since  at  equal  apparent  power  the 

alternator should supply a greater reactive power. For 

reduction  coefficients,  contact  the  Technical  Service 

Department.

START-UP OF ASYNCHRONOUS MOTORS

The start-up of asynchronous motors from an electricity-

generating group can prove critical because of high start-

up currents the asynchronous motor requires (I start-up 

= up to 8 times the nominal current In.). The start-up 

current  must  not  exceed  the  alternator’s  admissible 

overload current for brief periods, generally in the order 

of 250–300% for 10–15 seconds.

To avoid a group oversize, we recommend following these 

precautionary measures:

-  in the case of a start-up of several motors, subdivide the 

motors into groups and set up their start-up at intervals 

of 30–60 seconds.

-  when  the  operating  machine  coupled  to  the  motor 

allows it, see to a start-up with reduced voltage, star 

point/triangle start-up or with autotransformer, or use 

a soft-start system.

In all cases, when the user circuit requires the start-up 

of an asynchronous motor, it is necessary to check that 

there are no utilities inserted into the installation, which 

in the case of a voltage droop can cause more or less 

serious disservices (opening of contact points, temporary 

lack of power to control and command systems, etc.).

12/06/03 

 M37GB_1500G_GE

SINGLE-PHASE LOADS 

Power to monophase utilities by means of three-phase 

generators requires some operating limitations.

-  In  single-phase  operation,  the  declared  voltage 

tolerance can no longer be maintained by the regulator 

(compound or electronic regulator), since the system 

becomes highly unbalanced.

 The voltage variation 

on the phases not affected by the power can prove 

dangerous;  we  recommend  sectioning  the  other 

loads eventually connected

.            

-  The  maximum  power  which  can  be  drawn  between 

Neutral and Phase (start connection) is generally 1/3 

of  the  nominal  three-phase  power;  some  types  of 

alternators even allow for 40%. Between two Phases 

(triangle  connection)  the  maximum  power  cannot 

exceed 2/3 of the declared three-phase power.

-  In  electricity-generating  groups  equipped  with 

monophase sockets, use these sockets for connecting 

the loads. In other cases, always use the "R" phase 

and Neutral.

ELECTRIC PROTECTIONS

THERMAL-MAGNETIC SWITCH

The  electricity-generating  group  is  protected  against 

short-circuits  and  against  overloads  by  a  thermal-

magnetic  switch  (Z2)  situated  upstream  from  the 

installation.  Operating  currents,  both  thermic  and 

magnetic, can be fixed or adjustable in relation to the 

switch model.

+

 

In models with adjustable ope-

rating  current 

do  not  modify

  the 

settings, since doing so can com-

promise the installation’s protection 

or the electricity-generating group’s 

output characteristics. For eventual 

variations,  contact  our  Technical 

Service Department.

The  intervention  of  the  protection  feature  against 

overloads  is  not  instantaneous,  but  follows  a  current 

overload/time  outline;  the  greater  the  overload 

the  less  the  intervention. 

Furthermore,  keep  in  mind 

that  the  nominal  operating 

current refers to an operating 

temperature  of  30°C,  so 

that each variation of 10°C 

roughly corresponds to a variation of 5% on the value of 

nominal current.

In  case  of  an  intervention  on  the  part  of  the  thermal 

magnetic  protection  device,  check  that  the  total 

absorption  does  not  exceed  the  electricity-generating 

group’s nominal current.

M

37.

1

REV.1-09/05

Содержание GE 7000 KDes-gs

Страница 1: ...USE AND MAINTENANCE MANUAL M A D E I N I T A L Y GE 7500 HBSL AVR GE 7500 HBSLE AVR Codice Code Codigo Kodezahl 257759003 Edizione Edition Edici n Ausgabe 05 2014...

Страница 2: ......

Страница 3: ...rovided elastic support which must damp the vibrations and also eliminate sounds which would produce noise The unit has a protective closed frame which protects it against unintentional impacts during...

Страница 4: ...continue to satisfy the needs of its clients aswell as to improve the transparency and thecom munications regarding all the company s activesin accordance with the official procedures and inhar mony w...

Страница 5: ...2 7 INSTALLATION AND DIMENSIONS M 3 UNPACKING M 4 1 TRANSPORT AND DISPLACEMENTS M 6 ASSEMBLY CTM TR M 25 SET UP FOR OPERATION M 26 STARTING AND STOPPING M 31 CONTROLS M 37 USE AS A GENERATOR M 43 MAI...

Страница 6: ...matter In no case MOSA division of B C S S p A will be held responsible for any damaga direct or indirect in relation with the use of the given information MOSA division of B C S S p A does not take...

Страница 7: ...ke parts away do not tear pages and keep it in places protected from dampness and heat You must take into account that some figures contained in it want only to identify the described parts and theref...

Страница 8: ...cluded in any machine standard equipment Here below the adopted symbol CE marking is clearly readable and unerasable and it can be either part of the data plate Furthermore on each model it is shown t...

Страница 9: ...Marchio Brand Modello Model Matricola Serial number conforme con quanto previsto dalle Direttive Comunitarie e relative modifiche est en conformit avec ce qui est pr vu par les Directives Communautair...

Страница 10: ...urs limited at 500 h No overload is admitted Prime power PRP maximum available power for use at variable loads for a yearly illimited number of hours The average power to be taken during a period of 2...

Страница 11: ...r whatever event which may cause serious injuries or death predispose the first aid in accordance with the ruling labour accident standards or of local instructions FIRE PREVENTION In case the working...

Страница 12: ...ersons Use only with safety clothing It is compulsory to use the personal protection means given in equip ment Use only with safety clothing It is compulsory to use the personal protection means given...

Страница 13: ...a dangerous increase of the temperature Make sure that the machine does not move during the work block it possibly with tools and or devices made to this purpose Maximum leaning of the machine in cas...

Страница 14: ...GE 7000 HBSL HBSLE AVR GE 7500 HBSL HBSLE AVR M 2 7 REV 0 05 14 Installazione Installation Installation I GB F Luftzirkulation Instalaci n...

Страница 15: ...Dimensioni Dimensions Dimensions I GB F Abmessungen Dimensiones GE 7000 HBSL HBSLE AVR GE 7500 HBSL HBSLE AVR M 2 7 1 REV 0 05 14 STANDARD STD CTM7 1 STD CTM7 2...

Страница 16: ...rough handling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately...

Страница 17: ...th it s packaging and conform to local rules and regulations Only authorized persons involved in the transport of the machine should be in the area of movement DO NOT LOAD OTHER PARTS WHICH CAN MODIFY...

Страница 18: ...Lift the machine and assemble the parts as shown in the drawing ATTENTION The CTM accessory cannot be removed from the machine and used separately actioned manually or following vehicles for the tran...

Страница 19: ...correctly installed and that there are no leaks around the filter which couldlead to infiltrationsof non filteredair to the inside ofthe motor Gasoline is highly fammable Refuel with motor shut off in...

Страница 20: ...slowly RUNNING IN During the first 50 hours of operation do not use more than 60 of the maximum output power of the unit and check the oil level frequently CAUTION CLOSED OPEN CHOKE ROD 7 pull the rop...

Страница 21: ...encieux d chappement Silenciador de descarga 28 Interruttore motore Engine switch lnterrupteur moteur Interruptor motor 31 Tappo scarico olio motore Oil drain tap Bouchon d charge huile moteur Tap n v...

Страница 22: ...nditions and nominal values for voltage frequency power factors cos There are various types of power PRIME POWER PRP STAND BY POWER established by ISO 8528 1 and 3046 1 Norms and their definitions are...

Страница 23: ...o the motor allows it see to a start up with reduced voltage star point triangle start up or with autotransformer or use a soft start system In all cases when the user circuit requires the start up of...

Страница 24: ...protection forcefully pressed to prevent its intervention ATTENTION USAGE WITH EAS AUTOMATIC START UP PANEL The electricity generating group in combination with the EAS automatic start up panel forms...

Страница 25: ...O NOT USE COMPRESSED AIR DECALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable STRENUOUS OPERATING CONDITIONS Under extreme operating conditions...

Страница 26: ...d replace them when the maintenance requiring their removal is complete Please wear the appropriate clothing and make use of the PPE Personal Protective Equipment according to the type of intervention...

Страница 27: ...n the covers and all the other parts of the machine carefully Protect the machine with a plastic hood and store it in o dry place DIESEL ENGINE For short periods of time it is advisable about every 10...

Страница 28: ...he various components of the machine must be made accordingly to rules in force of law a o local rules Particular attention must be paid when getting rid of lubricating oils battery electrolyte and in...

Страница 29: ...4 Polarity inverter switch Z4 Transformer 230 48V W4 Diode bridge polarity change X4 Base current diode bridge Y4 PCB control unit polarity inverter A5 Base current switch B5 Auxiliary push button ON...

Страница 30: ...25460 II LEGENDA LEGEND LEGENDE REFERENZLISTE S2 Trasmettitore livello olio Oil level transmitter Tran smetteur niveau huile lstandssensor F3 Interruttore motore Engine switch Contacteur d arret moteu...

Страница 31: ...Schema elettrico Electric diagram Schemas electriques GE 7000 7500 HBSLE AVR M 61 2 REV 0 05 14 Stromlaufplan Esquema el ctrico...

Страница 32: ...Schema elettrico Electric diagram Schemas electriques GE 7500 HBSL HBSLE AVR M 61 3 REV 0 05 14 Stromlaufplan Esquema el ctrico...

Страница 33: ......

Страница 34: ...MOSA div della BCS S p A Stabilimento di Viale Europa 59 20090 Cusago MI Italia Tel 39 0290352 1 Fax 39 0290390466 WWW MOSA IT...