Using the generator

12/06/03 

 M37GB_1500G_GE

I

GB

F

WARNING

!

Access  forbidden  to  area  adjacent  to 

electricity-generating  group  for  all  non-

authorized personnel.

It is absolutely forbidden to connect the unit 

to the public mains and/or another electrical 

power source .

37

REV.3-11/11

The electricity-generating groups are to be considered 

electrical energy producing stations.

The  dangers  of  electrical  energy  must  be  considered 

together with those related to the presence of chemical 

substances (fuels, oils, etc.), rotating parts and waste 

products (fumes, discharge gases, heat, etc.).

GENERATION IN AC (ALTERNATING CURRENT)

Before  each  work  session  check  the  efficiency  of  the 

ground connection for the electricity-generating group if 

the distribution system adopted requires it, such as, for 

example, the TT and TN systems.

Check that the electrical specifications for the units to be 

powered - voltage, power, frequency - are compatible 

with those of the generator. Values that are too high or 

too low for voltage and frequency can damage electrical 

equipment irreparably.

In some cases, for the powering of three-phase loads, 

it is necessary to ensure that the cyclic direction of the 

phases corresponds to the installation’s requirements.

Connect  the  electric  devices  to  be  powered  to  the 

AC sockets, using suitable plugs and cables in prime 

condition.

Before starting up the group, make certain no dangerous 

situations exist on the installation to be powered.

Check that the thermal-magnetic switch (Z2) is in the OFF 

position (input lever in downward position).

Start up the electricity-generating group, positioning the 

thermal-magnetic switch (Z2) and differential switch (D) 

to ON (input lever in upward position). 

Before powering on the utilities, check that the voltmeter 

(N) and frequency meter (E2) indicate nominal values; 

in addition, check on the voltmeter change-over switch 

(H2) (where it is assembled) that the three line voltages 

are the same.

+

 

In the absence of a load, the values for voltage and 

frequency can be greater than their nominal values. See 

sections on VOLTAGE and FREQUENCY.

OPERATING CONDITIONS

POWER

The electrical power expressed in kVA on an electricity-

generating  group  is  the  available  output  power  to  the 

reference environmental conditions and nominal values 

for: voltage, frequency, power factors (cos 

ϕ

).

There  are  various  types  of  power:  PRIME  POWER 

(PRP), STAND-BY POWER established by ISO 8528-1 

and 3046/1 Norms, and their definitions are listed in the 

manual’s TECHNICAL SPECIFICATIONS page.

+

 

During the use of the electricity-generating group 

NE-

VER EXCEED 

the power indications, paying careful at-

tention when several loads are powered simultaneously.

VOLTAGE

GENERATORS WITH COMPOUND SETTING 

(THREEPHASE)

GENERATORS WITH CONDENSER SETTING 

(SINGLEPHASE)

In  these  types  of  generators,  the  no-load  voltage  is 

generally greater than 3–5% with respect to its nominal 

value;  f.e.  for  nominal  voltage,  threephase  400Vac 

or  singlephase  230Vac,  the  no-load  voltage  can  be 

comprised  between  410-420V  (threephase)  and  235-

245V (singlephase). The precision of the load voltage is 

maintained within ±5% with balanced loads and with a 

rotation speed variation of 4%. Particularly, with resistive 

loads (cos 

ϕ

 = 1), a voltage over-elevation occurs which, 

with the machine cold and at full load, can even attain 

+10 %, a value which in any case is halved after the first 

10-15 minutes of operation.  

The insertion and release of the full load, under constant 

rotation speed, provokes a transitory voltage variation 

that is less than 10%; the voltage returns to its nominal 

value within 0.1 seconds.

GENERATORS WITH ELECTRONIC SETTING (A.V.R.)

In  these  types  of  generators,  the  voltage  precision  is 

maintained within ±1,5%, with speed variations comprised 

from -10% to +30%, and with balanced loads. The voltage 

is the same both with no-load and with load; the insertion 

and release of the full load provokes a transitory voltage 

variation that is less than 15%; the voltage returns to its 

nominal value within 0.2–0.3 seconds.

FREQUENCY  

The frequency is a parameter that is directly dependent 

on the motor’s rotation speed. Depending on the type of 

alternator, 2 or 4 pole, we will have a frequency of 50/60 

Hz  with  a  rotation  speed  of  3000/3600  or  1500/1800 

revolutions per minute.

WARNING

!

For the canopy generator sets provided with doors, 

the following instruction shall be observed. During 

the  normal  operation,  the  doors  of  the  engine 

compartment  and/or  the  electrical  box  shall  be 

kept closed, locked up if possible, as they must be 

considered in all respects as protection barriers. 

The  access  to  the  internal  parts  shall  occur  for 

maintenance purposes only, by qualified personnel 

and, in any case, when the engine is stopped. 

Содержание GE 7000 KDes-gs

Страница 1: ...USE AND MAINTENANCE MANUAL M A D E I N I T A L Y GE 7500 HBSL AVR GE 7500 HBSLE AVR Codice Code Codigo Kodezahl 257759003 Edizione Edition Edici n Ausgabe 05 2014...

Страница 2: ......

Страница 3: ...rovided elastic support which must damp the vibrations and also eliminate sounds which would produce noise The unit has a protective closed frame which protects it against unintentional impacts during...

Страница 4: ...continue to satisfy the needs of its clients aswell as to improve the transparency and thecom munications regarding all the company s activesin accordance with the official procedures and inhar mony w...

Страница 5: ...2 7 INSTALLATION AND DIMENSIONS M 3 UNPACKING M 4 1 TRANSPORT AND DISPLACEMENTS M 6 ASSEMBLY CTM TR M 25 SET UP FOR OPERATION M 26 STARTING AND STOPPING M 31 CONTROLS M 37 USE AS A GENERATOR M 43 MAI...

Страница 6: ...matter In no case MOSA division of B C S S p A will be held responsible for any damaga direct or indirect in relation with the use of the given information MOSA division of B C S S p A does not take...

Страница 7: ...ke parts away do not tear pages and keep it in places protected from dampness and heat You must take into account that some figures contained in it want only to identify the described parts and theref...

Страница 8: ...cluded in any machine standard equipment Here below the adopted symbol CE marking is clearly readable and unerasable and it can be either part of the data plate Furthermore on each model it is shown t...

Страница 9: ...Marchio Brand Modello Model Matricola Serial number conforme con quanto previsto dalle Direttive Comunitarie e relative modifiche est en conformit avec ce qui est pr vu par les Directives Communautair...

Страница 10: ...urs limited at 500 h No overload is admitted Prime power PRP maximum available power for use at variable loads for a yearly illimited number of hours The average power to be taken during a period of 2...

Страница 11: ...r whatever event which may cause serious injuries or death predispose the first aid in accordance with the ruling labour accident standards or of local instructions FIRE PREVENTION In case the working...

Страница 12: ...ersons Use only with safety clothing It is compulsory to use the personal protection means given in equip ment Use only with safety clothing It is compulsory to use the personal protection means given...

Страница 13: ...a dangerous increase of the temperature Make sure that the machine does not move during the work block it possibly with tools and or devices made to this purpose Maximum leaning of the machine in cas...

Страница 14: ...GE 7000 HBSL HBSLE AVR GE 7500 HBSL HBSLE AVR M 2 7 REV 0 05 14 Installazione Installation Installation I GB F Luftzirkulation Instalaci n...

Страница 15: ...Dimensioni Dimensions Dimensions I GB F Abmessungen Dimensiones GE 7000 HBSL HBSLE AVR GE 7500 HBSL HBSLE AVR M 2 7 1 REV 0 05 14 STANDARD STD CTM7 1 STD CTM7 2...

Страница 16: ...rough handling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately...

Страница 17: ...th it s packaging and conform to local rules and regulations Only authorized persons involved in the transport of the machine should be in the area of movement DO NOT LOAD OTHER PARTS WHICH CAN MODIFY...

Страница 18: ...Lift the machine and assemble the parts as shown in the drawing ATTENTION The CTM accessory cannot be removed from the machine and used separately actioned manually or following vehicles for the tran...

Страница 19: ...correctly installed and that there are no leaks around the filter which couldlead to infiltrationsof non filteredair to the inside ofthe motor Gasoline is highly fammable Refuel with motor shut off in...

Страница 20: ...slowly RUNNING IN During the first 50 hours of operation do not use more than 60 of the maximum output power of the unit and check the oil level frequently CAUTION CLOSED OPEN CHOKE ROD 7 pull the rop...

Страница 21: ...encieux d chappement Silenciador de descarga 28 Interruttore motore Engine switch lnterrupteur moteur Interruptor motor 31 Tappo scarico olio motore Oil drain tap Bouchon d charge huile moteur Tap n v...

Страница 22: ...nditions and nominal values for voltage frequency power factors cos There are various types of power PRIME POWER PRP STAND BY POWER established by ISO 8528 1 and 3046 1 Norms and their definitions are...

Страница 23: ...o the motor allows it see to a start up with reduced voltage star point triangle start up or with autotransformer or use a soft start system In all cases when the user circuit requires the start up of...

Страница 24: ...protection forcefully pressed to prevent its intervention ATTENTION USAGE WITH EAS AUTOMATIC START UP PANEL The electricity generating group in combination with the EAS automatic start up panel forms...

Страница 25: ...O NOT USE COMPRESSED AIR DECALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable STRENUOUS OPERATING CONDITIONS Under extreme operating conditions...

Страница 26: ...d replace them when the maintenance requiring their removal is complete Please wear the appropriate clothing and make use of the PPE Personal Protective Equipment according to the type of intervention...

Страница 27: ...n the covers and all the other parts of the machine carefully Protect the machine with a plastic hood and store it in o dry place DIESEL ENGINE For short periods of time it is advisable about every 10...

Страница 28: ...he various components of the machine must be made accordingly to rules in force of law a o local rules Particular attention must be paid when getting rid of lubricating oils battery electrolyte and in...

Страница 29: ...4 Polarity inverter switch Z4 Transformer 230 48V W4 Diode bridge polarity change X4 Base current diode bridge Y4 PCB control unit polarity inverter A5 Base current switch B5 Auxiliary push button ON...

Страница 30: ...25460 II LEGENDA LEGEND LEGENDE REFERENZLISTE S2 Trasmettitore livello olio Oil level transmitter Tran smetteur niveau huile lstandssensor F3 Interruttore motore Engine switch Contacteur d arret moteu...

Страница 31: ...Schema elettrico Electric diagram Schemas electriques GE 7000 7500 HBSLE AVR M 61 2 REV 0 05 14 Stromlaufplan Esquema el ctrico...

Страница 32: ...Schema elettrico Electric diagram Schemas electriques GE 7500 HBSL HBSLE AVR M 61 3 REV 0 05 14 Stromlaufplan Esquema el ctrico...

Страница 33: ......

Страница 34: ...MOSA div della BCS S p A Stabilimento di Viale Europa 59 20090 Cusago MI Italia Tel 39 0290352 1 Fax 39 0290390466 WWW MOSA IT...

Отзывы: