![Mosa DSP 2x400 PS-PL Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/mosa/dsp-2x400-ps-pl/dsp-2x400-ps-pl_use-and-maintenance-manual_1836905022.webp)
DSP 2x400 PSX
DSP 600 PS/PSX
REV.0-11/05
M
21
ENGINE STARTING AND USE
28/1
1/05 88412-GB
NOTE
!
Do not alter the factory adjustment of the
engine and do not touch the sealed parts.
Check daily
CAUTION
!
1500 / 1800 RPM ENGINES
These engines start their normal operating speed.
IGNITION KEY
The ingnition key is a part of the EP5
engine protection device and has
three positions.
STARTING THE ENGINE
Introduce the key (Q1), turn it clockwise completely,
leaving it as soon as the engine starts.
NB.: for safety reason the key must be kept by
qualified personel.
Let the engine run for some minutes before drawing
the load.
ENGINE PROTECTION (EP5)
The EP5 device monitors the engine oil pressure,
the engine water temperature and the rpm of the
engine. If the oil pressure is too low, the water tem-
perature too high or the speed too high, the device
shuts-down the engine. For a few seconds after the
engine is started the shut-down function is inhibited
to allow the engine to start.
M5.1
(yellow) Fuel
reserve
M5.2
(yellow) Battery
charge
M5.3
(red) Overspe-
ed
M5.4
(red) High tem-
perature
M5.5
(red) Low oil
pressure
M5.6
(green) Protec-
tion unit on
M5.5
M5.6
M5.4
M5.3
M5.2
M5.1
M
STOP
OFF
b
a
c
LOW OIL PRESSURE (M5.5
)
In the event of low oil pressure the LED lights and
the engine is shut-down.
HIGH TEMPERATURE (M5.4)
If the water temperature is too high the LED lights
and the engine is shut-down.
OVERSPEED (M5.3)
If the engine speed goes over the preset value the
LED lights and the engine is shutdown. The nominal
frequency (50 or 60 Hz) is monitored .
FUEL RESERVE (M5.1)
If the fuel level reaches the reserve level the LED
lights and the sirene sounds and the engine is shut-
down.
BATTERY CHARGE (M5.2)
It the battery is not being charged the LED light but
the engine does not stop.The visual signal will stay
on until until the charging system is repaired.
STOP BUTTON
The stop button can be used to stop the engine at
any time. Push and hold the button until the engine
stops.
OFF
ON
START
RUNNING-IN
During the first 50 hours of operation, do not use
more than 60% of the maximum output power of
the unit and check the oil level frequently, in any
case please stick to the rules given in the engine
use manual.
Содержание DSP 2x400 PS-PL
Страница 38: ...DSP 2x400 PSX REV 0 11 05 M 53 Dimensioni Abmessungen Dimension 18 11 05 88412 I...
Страница 42: ...DSP 2x400 PS PL REV 0 11 05 M 61 2 Stromlaufplan 28 11 05 78413 D...
Страница 43: ...DSP 2x400 PS PL REV 1 02 11 M 61 3 Stromlaufplan 28 11 05 78413 D...
Страница 44: ...DSP 2x400 PS PL REV 1 02 11 M 61 4 Stromlaufplan 28 11 05 78413 D...
Страница 45: ...DSP 2x400 PS PL REV 1 02 11 M 61 5 Stromlaufplan 28 11 05 78413 D...
Страница 46: ...DSP 2x400 PS PL REV 1 02 11 M 61 6 Stromlaufplan 28 11 05 78413 D...