MorrHeat - Most Heat In The Industry - Rev 3/18/2019
Troubleshooting Continued...
1. Boiler shuts off
2. Loss of prime
overnight
▲ Manual reset
▲ Vacuum air leak in air line
▶ Plugged filter or tank empty
▼ Plugged pump screen
▲ Required manual reset
▲ Tighten all fuel connections
▶ Check pump screen
▼ Clean filter (use vent port), reprime pump
3.Fails to Start
▲ Vacuum leak
▲ Inadequate fuel supply
▶ No pressure
▶ No pre-heat
▶ Auto start circuit not
functioning
▶ No arc
▶ No air pressure
▲ Open bleeder port if air is present.
▲ Clean filter. Check all fuel connections . Tighten fittings.
▶ Check, may need cleaning - to access, remove, pump cover.
▶ Use vent port, and reprime pump.
▶ Be sure all wiring to pre-boiler is tight.
▶ Bad heat rod - replace.
▶ Check circuit control board and replace if necessary.
▶ Check continulty at terminals of heat rod limit snap switch.
▶ Check springs to electrode rod adjustment (under transformer) -
make sure they have good contanct. Open burner door and make sure
electrode tips aren't touching flame cone.
▶Check pressure regulator and adjust. Check air supply line for
restrictions or leaks. Pull compressor cover and inspect carbon vanes.
May need to replace. Check filter, clean if needed.
4. Reduced air pressure
and can’t increase
▲ Gauge may be bad.
▲ Intake filter muffler is plugged
with dust or dirt.
▶ Exposed to winter
▼ Compressor vanes may be
worn
▲ Replace gauge
▲ Remove & clean with carburetor cleaner, dry thoroughly. Do not use.
▶ Remove cover, clean rust with emery cloth
▼ Replace carbon vanes
5. Hard starting
(Diminished flame)
▲ Pariially plugged filter.
▶ Restriction in nozzle usually
only when initially installed. New
lines may have foreign material
in them.
▶ Air band open too far
▼ Out of fuel
▼ No oil to burner
▲ Clean filter.Using vent port-reprime pump
▶ Remove nozzle and check for foreign objects
▶ Aluminium block pre-boiler inside burner should not build up carbon.
If carbon present, pre-heat circuit is malfunctioning. Thermocouple
heat sensor wire could have open circuit. Heat control board may have
blown circuit and circuit board fuse. Inspect both and replace either if
needed.
▶ Close air band - while viewing flame; open air band slowly unitl
combustion chamber a clear, not orange
▼ Refill storage
▼ Clean pump screen - remove pump cover. Using vent port, re-prime
pump.
Problem
Cause
Suggestion
▲
Most likely ||
▶
Less likely ||
▼
Least Likely