Morningstar TRISTAR TS-MPPT-60-600V-48 Скачать руководство пользователя страница 21

41

TriStar MPPT 600V Operator’s Manual

40

Installation

AVERTISSEMENT :  
L’appareil n’est pas fourni avec un dispositif GFDI. Ce contrôleur de charge doit être 
utilisé avec un dispositif GFDI externe tel que requis par l’Article 690 du Code électrique 
national de la région de l’installation.

NOTE:  

Conductors identified by the color combination green/yellow shall only be used for earthing 

conductors.

Use a copper wire to connect the grounding terminal in the wiring box - and any other dead           

metallic components - to earth ground.  

Per NEC 690.45 and NEC Table 250.122, minimum size 

for  copper grounding wire are: 

TriStar MPPT 600V unit  -  60A:   10 AWG  ( 8 mm

2

)

        OR, of the same, or greater, cross-sectional area as the PV wires.

e ro n in ter ina is i entifie

t e ro n s

o a acent to t e ter ina an s o n

below:

Do not connect the system negative conductor to this terminal.  NEC requires the use of an 

external ground fault protection device (GFPD). The TriStar MPPT 600V does not have internal 

ground fault protection, but Morningstar Corporation offers an accessory GFPD-600V.  The 

system electrical negative should be bonded through a GFPD to earth ground at one (and only 

one) location. The grounding point may be located in the solar circuit or the battery circuit.

WARNING:  Risk of Fire
DO NOT bond system electrical negative to earth ground at the controller. Per NEC 
requirements, system negative must be bonded to earth ground through a GFPD at only 
one point.

AVERTISSEMENT :  Risque d’incendie
NE LIEZ PAS le côté négatif du système à la mise à la terre au niveau du contrôleur. 
Selon les exigences du CNE, le côté négatif du système doit être mis à la terre par un 
GFPD à un seul point.

3.9 Power-up and Commissioning

Step 11 - Power Up (TS-MPPT-60-600V-48 and TS-MPPT-60-600V-48-DB)

WARNING:  Risk of Damage
Connecting the solar power source  to the battery terminal will permanently damage the 
TriStar MPPT 600V.

WARNING:  Risk of Damage
Connecting the solar power source  or battery connection with reverse polarity will permanently 
damage the TriStar MPPT 600V.

AVERTISSEMENT:  Risque d’endommagement
La connexion du réseau solaire sur la borne de la batterie endommagera le TriStar MPPT 600V 
600Vde façon permanente.

AVERTISSEMENT:  Risque d’endommagement
La connexion du réseau solaire ou la connexion de la batterie avec une polarité inversée 
endommagera le TriStar MPPT 600V 600Vde façon permanente.

• 

Confir t at t e so ar an

atter

o arities are correct

•  Note that a battery must be connected to the TriStar MPPT 600V to start and operate the 

controller. The controller will not operate only from solar input.

• 

C ose t e atter

isconnect rea er

or e terna first

ser e t at t e

s in icate

a successful start-up. (LEDs blink Green - Yellow - Red in one cycle)

•  Close the solar disconnect switch (DB or external).  If the power source is active, the 

TriStar MPPT 600V will begin charging. If an optional TriStar Meter is installed, charging 

current will be reported along with charging state.

Power-Down

WARNING: Risk of Damage 

  ONLY disconnect the battery from the TriStar MPPT 600V AFTER the solar input has been disconnected.  
   Damage to the controller may result if the battery is removed while the TriStar MPPT 600V is charging.

 

AVERTISSEMENT:  Risque d’endommagement

 Le TriStar MPPT 600V SEULEMENT déconnecter la batterie APRÈS l’entrée solaire a été             
  déconnectée.  Le contrôleur pourrait endommager si la batterie est retirée quand le TriStar MPPT 600V  
est en charge.

•   To prevent damage, power-down must be done in the reverse order as power-up.

Содержание TRISTAR TS-MPPT-60-600V-48

Страница 1: ...www morningstarcorp com Solar Battery Charger with TrakStarTM Maximum Power Point Tracking Technology MODELS TS MPPT 60 600V 48 TS MPPT 60 600V 48 DB MAXIMUM POWER POINT TRACKING TRISTAR MPPT 600V TM...

Страница 2: ...Conduit Knock outs and Wiring Routing 21 3 4 Controller Preparation 23 3 5 Mounting 26 3 6 Network Connections 28 3 7 Wiring Connections 30 Confi ration 3 9 Power Up Commissioning 41 4 0 Operation 42...

Страница 3: ...tion of the controller AVERTISSEMENT Indique une condition potentiellement dangereuse Faites preuve d une prudence extr me lors de la r alisation de cette t che PRUDENCE Indique une proc dure critique...

Страница 4: ...terre se tro e ans e co arti ent e c a e et est i entifi e ar e symbole ci dessous estampill dans le boit Informations de S curit ise to tes es instr ctions et es a ertisse ents fi rant ans e an e a a...

Страница 5: ...a zone de travail ter iner si atterie re ose ar ina ertance ans a fir ati e s ri er a so rce contact avec le sol Contact avec n importe quelle partie d une batterie mise la terre peut entra ner un cho...

Страница 6: ...provided to ensure all pole disconnection from the power supply This isconnection s a e incor orate in t e fi e irin Using the TriStar MPPT 600V grounding terminal in the wiring compartment a permanen...

Страница 7: ...nt or re locate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connecte...

Страница 8: ...RS 232 Port 9 pin serial connector female 8 EIA 485 Port Four 4 position screw terminal for EIA 485 bus connections 9 Ground Terminals 2 total A chassis ground terminal for equipment grounding 10 Bla...

Страница 9: ...site at www morningstarcorp com or inquire with your local Morningstar dealer EIA 485 RS 232 Communications Adapter RSC 1 Connect one or more TriStar MPPT 600V controllers to a PC or to other serial d...

Страница 10: ...in the system These protection devices are external to the TriStar MPPT 600V controller and must be a maximum of 90 amps for the TriStar MPPT 600V Maximum battery short circuit current rating must be...

Страница 11: ...PPT 600V wiring box Knockout place ment dimensions are on the inside front cover Figures 3 2 to 3 5 show knock out types The TriStar MPPT 600V wiring box provides continuous and separate paths for hig...

Страница 12: ...1 2 or M20 0 88 22 2 mm Battery low voltage NO 11 2 3 4 1 09 27 8 mm Solar high voltage NO 12 2 1 1 36 34 5 mm Battery low voltage NO Solar connector mounting hole diameters vary Wieland Solar DC con...

Страница 13: ...ider is secured with only one screw 1 Use a 2 Philips screw driver to remove the screw 2 Lift and tilt the divider towards the bottom of the unit as shown in Figure 3 8 3 Lift the divider out of the w...

Страница 14: ...oller may be insta e in a enti ate enc os re it s ficient air o e er insta t e ri tar in a sealed enclosure The controller may be mounted in an enclosure with sealed batteries but never it ente oo e a...

Страница 15: ...section 5 0 for more information about networking and the connection s required for your system WARNING Shock Hazard Only route network cables in the same conduit as the photovoltaic power conductors...

Страница 16: ...ss of 500 Vdc when in sunlight Verify that the solar input breaker or disconnect has been opened disconnected before installing the system wires AVERTISSEMENT Risque de d charge lectrique Le r seau PV...

Страница 17: ...hat the battery connection is made with correct polarity Turn on the battery breaker disconnect and measure the voltage on the open battery wires BEFORE connecting to the TriStar MPPT 600V Disconnect...

Страница 18: ...recte dans le cas contraire subira des dommages Activez le coupe circuit interrupteur de la batterie et mesure la tension sur les c bles ouverts AVANT la connexion au TriStar MPPT 600V D connectez le...

Страница 19: ...ferrite sur l extr mit du RTS si une longueur de c ble est enlev e Cette bobine assure la conformit avec les normes d missions lectromagn tiques Step 8 Battery Voltage Sense The voltage at the batter...

Страница 20: ...ation will only occur when manually started with the push button or when requested from the equalize menu on the TriStar meter Automatic equalization will occur accor in to t e atter ro ra s ecifie se...

Страница 21: ...seul point 3 9 Power up and Commissioning Step 11 Power Up TS MPPT 60 600V 48 and TS MPPT 60 600V 48 DB WARNING Risk of Damage Connecting the solar power source to the battery terminal will permanent...

Страница 22: ...the ability to charge batteries with power sources of higher nominal voltages The TriStar MPPT 600V charges a 48 Volt battery bank with a high voltage power source The power source open circuit volta...

Страница 23: ...e syst me Certain atter t es enefit ro a erio ic oost c ar e to stir t e e ectro te e e t e ce o t ages and complete the chemical reactions Equalize charging raises the battery voltage above the stand...

Страница 24: ...inal 48 Volt battery banks Settings Switches 4 5 6 Battery Type Absorp Stage Volts Float Stage Volts Equalize Stage Volts Absorp Time Minutes Equalize Time Minutes Equalize Interval Days off off off 1...

Страница 25: ...sly for 60 min However because the Float exit timer is cumulative multiple momentary load events that pull the battery voltage below Float voltage for a combined 60 minutes duration will also force an...

Страница 26: ...improve the accuracy of the battery charging See Section 3 4 Step 8 for instructions on how to connect the battery sense wires 4 3 Push button The following functions can be enabled with the pushbutt...

Страница 27: ...Absorption G blinking once per second Equalization state G fast blink two times per second Float state G slow blink once per two seconds Faults Alarms Over temperature Y R sequencing High voltage disc...

Страница 28: ...ndicate a failure If the control ler is restarted with the failure still present the controller may not detect that the battery sense is connected and the LEDs will not indicate a fault A TriStar mete...

Страница 29: ...not factory calibrated Return the controller to an authorized Morningstar dealer for service 5 0 Networking and Communication 5 1 Introduction The TriStar MPPT 600V provides several communication opti...

Страница 30: ...ollers Figure 5 1 An example MeterBus network to fi e contro ers can e net or e to et er it a sin e ti e s can e daisy chained together to allow networks of up to 15 controllers and 2 meters Refer to...

Страница 31: ...twork with custom charge settings using MSViewTM PC software connect the TriStar MPPT 600V to other Morningstar controllers with the RSC 1 Serial to EIA 485 Adapter sold separately bridge an Ethernet...

Страница 32: ...tion about Ethernet connectivity and networking refer to the Morningstar Communications Document on our web site at HTTP www morningstarcorp com Network Information Connect to the TriStar MPPT 600V vi...

Страница 33: ...contro er can e confi re to o a itiona o tion al values each day The maximum number of days that can be stored decreases as the number of logged values increases Standard Values Minimum Battery Volta...

Страница 34: ...ence see Section 4 4 Faults Alarms of this manual to determine the cause If a TriStar Meter 2 600V is connected the diagnostics menu will display reported faults and alarms Troubleshooting 6 0 If the...

Страница 35: ...n of the controller AVERTISSEMENT Indique une condition potentiellement dangereuse Faites preuve d une prudence extr me lors de la r alisation de cette t che PRUDENCE Indique une proc dure critique po...

Страница 36: ...nts casual contact The TriStar MPPT 600V heatsink can become very hot during operation Use insulated tools when working with batteries Avoid wearing jewelry during installation The battery bank must b...

Страница 37: ...vrir ou mutiler les piles L lectrolyte est nocif pour la peau et peut tre toxique Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the proper saf...

Страница 38: ...k Hazard Disconnect all power sources to the controller before removing the wiring box cover Never remove the cover when voltage exists on the TriStar MPPT 600V power connections AVERTISSEMENT Risque...

Страница 39: ...MAGES OF ANY KIND INCLUDING BUT NOT LIMITED TO LOST PROFITS DOWN TIME GOODWILL OR DAMAGE TO EQUIPMENT OR PROPERTY R15 8 18 Warranty and Claim Procedure 8 0 WARRANTY CLAIM PROCEDURE 1 Before proceeding...

Страница 40: ...aled 56 60 54 80 57 60 150 60 120 28 off on off 3 Sealed 57 20 54 80 58 40 150 60 120 28 off on on 4 AGM Flooded 57 60 54 80 60 40 180 120 180 28 on off off 5 Flooded 58 40 54 00 61 20 180 120 180 28...

Страница 41: ...ndoor vented Protections Solar High Voltage Disconnect Solar High Voltage Reconnect Battery High Voltage Disconnect Battery High Voltage Reconnect High Temperature Disconnect High Temperature Reconnec...

Страница 42: ...60 Amp Battery Current Limit 60 Amp Battery Current Limit Vb 60 V 0 100 200 300 400 500 600 500 1000 1500 2000 2500 3000 3500 INPUT VOLTAGE Volts POWER Watts Output Power vs Array Input Voltage Figur...

Страница 43: ...6 8 8 1 10 2 13 6 6 2 1 2 3 2 6 2 8 3 2 3 7 4 3 5 1 6 4 8 5 4 1 3 1 5 1 6 1 8 2 0 2 3 2 7 3 2 4 0 5 3 2 5 0 8 0 9 1 0 1 1 1 3 1 4 1 7 2 0 2 5 3 4 Table 9 2 Maximum 1 way wire distance for 48V systems...

Страница 44: ...ty at 50 C ambient temperature Exceeds wire ampacity at 40 C ambient temperature Exceeds wire ampacity at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a ra...

Страница 45: ...o con ctors ro t e so ar or atter so rce to t e controller 1 way distance Shaded cells in the table indicate that the current exceeds the ampacity of the wire for a i en a ient te erat re as efine in...

Отзывы: