Warranty and Claim Procedure
WARRANTY CLAIM PROCEDURE
1. Before proceeding, please refer to product manual, including troubleshooting section.
2. Contacting your authorized Morningstar distributor or dealer from whom you purchased the unit is
the first step in the warranty process. Local dealers can often address warranty issues quickly.
3. If supplier is unable to address the issue, please contact Morningstar by e-mail
([email protected]) with:
(A) purchase date and location -- business or company name
(B) full model and serial numbers (SN is 8-digits on unit bar label)
(C) failure behavior, including LED indications
(D) array configuration, panel Pmax, Voc, Vmp, Isc, and nominal battery voltage; these
specifications are needed to receive assistance.
(E) multi-meter available (for field troubleshooting)
4. After warranty replacement has been approved and new unit(s) received, please return failed
unit(s) using the pre-paid shipping label, and follow any product specific instructions if requested by
Morningstar Warranty Dept.
5. If instructed by Morningstar, after warranty replacement shipment has been received, return of
failed unit(s) is required before further warranty replacements can be considered for the original or
future cases.
NOTE: An RMA number must be issued by Morningstar prior to return of any unit(s)
under this warranty. Please do not return units without an RMA or case number. Doing so will
increase the time required to resolve your claim.
9.0
Technical Specifications
Electrical
TS-MPPT-60-600V-48 TS-MPPT-60-600V-48-DB
Nominal System Voltage
48 Volts
48 Volts
Maximum Battery Current
60 Amps
60 Amps
(63A breaker included)
Maximum Solar Input Voltage
Maximum Operating Input Current
600 Volts dc 600 Volts dc
15 Amps 15 Amps
Battery Operating Voltage Range
16 - 72 Volts dc
16 - 72 Volts dc
Nominal Maximum Input Power*
3200 Watts
3200 Watts
Voltage Accuracy
≤ 0.1 % ± 100 mV
≤ 0.1 % ± 100 mV
Self consumption (tare loss)
2-3.5 Watts 2-3.5 Watts
Transient Surge Protection
4500 Watts / port 4500 Watts / port
*These power levels refer to the maximum wattage the TS-MPPT-60-600V-48 can process. Higher power arrays
can be used without damaging the controller, but array cost-benefit will be reduced at power levels much beyond
the nominal rating.
Battery Charging
Charging algorithm:
4 - stage
Charging stages: Bulk, Absorption, Float, Equalize
Temperature compensation coefficient:
-5 mV / °C / cell (25 °C ref.)
Temperature compensation range (RTS connected) -30 °C to +80 °C
Temperature compensated set-points:
Absorption, Float, Equalize, HVD
Battery high voltage disconnect:
Charge stage regulation v0.5V
Battery low voltage disconnect / reconnect: 14.0 / 16.0 Volts
Charging Set-points (48 Volt systems):
Settings
Switches
Battery
Type
Absorp.
Stage
Float
Stage
Equalize
Stage
Absorp.
Time
Equalize
Time
Equalize
Timeout
Equalize
Interval
sw: 4-5-6
Volts
Volts
Volts
Minutes Minutes Minutes
Days
off-off-off
1 - Sealed*
56.00
54.80
150
off-off-on
2 - Sealed*
56.60
54.80
57.60
150
60
120
28
off-on-off
3 - Sealed*
57.20
54.80
58.40
150
60
120
28
off-on-on 4 - AGM/Flooded
57.60
54.80
60.40
180
120
180
28
on-off-off
5 - Flooded
58.40
54.00
61.20
180
120
180
28
on-off-on
6 - Flooded
58.80
54.00
61.60
180
180
240
28
on-on-off
7 - L-16
61.60
53.60
64.00
180
180
240
14
on-on-on
8 - Custom
Custom
Custom
Custom
Custom
Custom
Custom
Custom
* “Sealed” battery type includes gel and AGM batteries
See section 4.2 for more information