33

TriStar MPPT 600V Operator’s Manual

32

Installation

Minimum Wire Size (Field Wiring Connections Only)

The NEC requires that the wires carrying the system current never exceed 80% of the 

conductor's current rating.  Table 3.2 below provides the minimum size of copper wire for battery 

output connections allowed by NEC for both TriStar MPPT 600V models when the output current 

equals the full nameplate rating. Wire types rated for 75°C and 90°C are included.

*   The TS-MPPT-60-600V-48-DB comes pre-wired with #6 AWG copper wire.  If replacement is  

     required, use #6 AWG or larger wire.    

**  The TS-MPPT-60-600V-48-DB comes pre-wired with #6 AWG copper wire.  If replacement is  

     required, use only copper conductors.

Wire Type

75°C Wire

90°C Wire

Copper

4 AWG (21 mm

2

)

6 AWG (13 mm

2

)

Aluminum

2 AWG (34 mm

2

)

4 AWG (21 mm

2

)

 Table 3-2 Minimum Output Wire Sizes

Disconnects

WARNING:  Shock Hazard
Fuses, circuit breakers, and disconnect switches should never open grounded system conductors. Only 
GFDI devices are permitted to disconnect grounded conductors.

AVERTISSEMENT :  Risque de décharge électrique
Les fusibles, coupe-circuits et interrupteurs ne doivent jamais ouvrir les conducteurs du système mis à la 
terre. Seuls les dispositifs GFDI sont autorisés à déconnecter les conducteurs reliés mis à la terre.

Circuit breakers or fuses must be installed in both the battery and solar circuits. 

The protection 

device ratings and installation methods must conform to NEC requirements.

WARNING:

The TriStar MPPT 600V is not protected against PV short circuit faults.  A breaker  

                or fuse, close to the controller, in the (+) PV input wire will also protect the PV wiring  
                against a short that may draw battery current backwards through the product.

             

AVERTISSEMENT :

  

Le TS-MPPT-600V-TR n’est pas protégé contre les défauts de court-circuit de PV.  

                Un disjoncteur fusible, ou près du programmateur, dans le signe (+) PV d’entrée fil protégera également le  

                câblage PV  contre un court-circuit qui peut tirer une batterie courant en arrière à travers le produit.

Connect the Power Wires - TS-MPPT-60-600V-48 

WARNING:  Shock Hazard
The solar PV power source  can produce open-circuit voltages in excess of 500 Vdc 
when in sunlight. Verify that the solar input breaker or disconnect has been opened 
(disconnected) before installing the system wires.

AVERTISSEMENT :  Risque de décharge électrique
Le réseau PV solaire peut produire des tensions de circuit ouvert supérieures à 500 V cc  

à la lumière du soleil. Vérifiez que le coupe-circuit ou l’interrupteur d’entrée solaire a été 

ouvert (déconnexion) avant d’installer les câbles du système.

SOLAR NEG. (-)

SOLAR POS. (+)

BATTERY NEG. (-)

BATTERY POS. (+)

Figure 3-14. Power Terminal Locations

Connect the four (4) power conductors shown in Figure 3-14 as described in the following 

steps

:

1.

Confirm that the system input and output disconnect switches are both turned off before    

connecting the power wires to the controller. 

2. Pull PV and battery wires into the standard wiring box. The Remote Temperature Sensor 

(RTS) and Battery Sense wires can be routed inside conduit along with the battery power 

conductors if required. The RTS and Battery Sense wires CANNOT be routed in the same 

conduit with the high voltage solar conductors. It is easier to pull the RTS and Sense wires 

before the power cables.

3. Only route high voltage solar circuit conductors in the high voltage wiring zone and low volt-

age battery and network conductors within the low voltage zone. Refer to section 3.2 for more 

information.

4. Replace the yellow Solar Terminal Bridge if removed as shown in Figure 3-9 on page 25. The 

bridge should fit over the solar power terminals. The bridge isolates the high voltage solar 

wiring from the low voltage wiring area. The bridge MUST be installed before proceeding. 

Connect the solar (+) wire to the solar (+) terminal on the TriStar MPPT 600V. 

WARNING:  Risk of Damage
Be very certain that the solar connection is made with correct polarity. Turn on the solar 
power source  breaker/disconnect and measure the voltage on the open wires BEFORE 
connecting to the TriStar MPPT 600V. Disconnect the solar breaker/disconnect before 
wiring to the controller.

AVERTISSEMENT :  Risque d’endommagement

Assurez-vous que la connexion solaire est effectuée avec la polarité correcte. Activez le coupe-

circuit/interrupteur de réseau solaire et mesure la tension sur les câbles ouverts AVANT la 
connexion au TriStar MPPT 600V. Déconnectez le coupe-circuit/interrupteur solaire avant le 
câblage sur le contrôleur.

             

NOTE: 

Tighten all new screw terminal connections to specified torque values

               

REMARQUE :

Serrer toutes les nouvelles connexions terminal vis au couple spécifié de valeurs

Содержание TRAKSTAR TS-MPPT-60-600V-48

Страница 1: ...www morningstarcorp com Solar Battery Charger with TrakStarTM Maximum Power Point Tracking Technology MODELS TS MPPT 60 600V 48 TS MPPT 60 600V 48 DB MAXIMUM POWER POINT TRACKING TRISTAR MPPT 600V TM...

Страница 2: ...s 20 3 3 Conduit Knock outs and Wiring Routing 22 3 4 Controller Preparation 24 3 5 Mounting 27 3 6 Network Connections 29 3 7 Wiring Connections 31 3 8 Configuration 38 3 9 Grounding Power up and Pow...

Страница 3: ...of the controller AVERTISSEMENT Indique une condition potentiellement dangereuse Faites preuve d une prudence extr me lors de la r alisation de cette t che PRUDENCE Indique une proc dure critique pou...

Страница 4: ...trouve dans le compartiment de c blage et est identifi e par le symbole ci dessous estampill dans le boit Informations de S curit Lisez toutes les instructions et les avertissements figurant dans le m...

Страница 5: ...batterie repose par inadvertance Dans l affirmative supprimer la source du contact avec le sol Contact avec n importe quelle partie d une batterie mise la terre peut entra ner un choc lectrique La pr...

Страница 6: ...ovided to ensure all pole disconnection from the power supply This disconnection shall be incorporated in the fixed wiring Using the TriStar MPPT 600V grounding terminal in the wiring compartment a pe...

Страница 7: ...se the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio...

Страница 8: ...female 8 EIA 485 Port Four 4 position screw terminal for EIA 485 bus connections 9 Knock out Seals typ of eight 8 Steel seals to protect internals when knock outs not in use 10 Ground Terminals 2 tot...

Страница 9: ...ts 1 Heatsink Aluminum heatsink to dissipate controller heat the TriStar MPPT 600V is 100 passively cooled for reliability 2 Battery Negative Power Terminal Power connection for battery cable terminat...

Страница 10: ...PC or to other serial devices using the EIA 485 adapter The adapter converts an RS 232 serial interface to EIA 485 compliant bus signals An LED shows network activity and errors DIN rail compatible 3...

Страница 11: ...he yellow Solar Terminal Bridge must be properly fitted in place before making the solar power terminal connections The battery wiring and all communication cables must only be routed within the low v...

Страница 12: ...of the high voltage and low voltage wiring paths 2 3 4 1 5 6 Figure 3 2 Knock outs left view 2 1 4 5 6 Figure 3 3 Knock outs right view 7 8 9 10 Figure 3 4 Knock outs bottom view Figure 3 5 Knock outs...

Страница 13: ...irez jamais le couvercle en pr sence de tension sur une des connexions d alimentation du TriStar MPPT 600V 600V600V Use a 2 Phillips screw driver to remove the four 4 screws that secure the wiring box...

Страница 14: ...necteurs des raccordements collets ou des fouloirs dans les ouvertures afin de prot ger le c blage des bords coupants WARNING Shock Hazard Never route network cables in the same conduit as the power c...

Страница 15: ...ks 9 Carefully align the keyhole on the TriStar MPPT 600V with the screw head Slide the TriStar MPPT 600V down over the keyhole The pre drilled pilot holes should align with the mounting holes in the...

Страница 16: ...pre assembled cables take care not to damage the plugs when the cables are pulled through conduit MeterBusTM Connection MeterBusTM networks use standard 4 wire or 6 wire RJ 11 telephone cables If poss...

Страница 17: ...nnect has been opened disconnected before installing the system wires AVERTISSEMENT Risque de d charge lectrique Le r seau PV solaire peut produire des tensions de circuit ouvert sup rieures 500 V cc...

Страница 18: ...NING Risk of Damage Be very certain that the battery connection is made with correct polarity Turn on the battery breaker disconnect and measure the voltage on the open battery wires BEFORE connecting...

Страница 19: ...Connect the solar wire to an available terminal on the solar block as in S and connect the solar wire to an available terminal on the solar block as in S 8 Replace the Wiring Divider removed in Step...

Страница 20: ...MPPT 600V Mode Switch 1 Solar Charging OFF Future Use ON Switch 2 Not Used OFF Switch 3 Charging Mode Charging Mode Switch 3 Normal 48V OFF Custom Multiplier ON Allows for nominal charging voltages o...

Страница 21: ...ith an external GFDI device as required by the Article 690 of the U S National Electrical Code for the installation location AVERTISSEMENT L appareil n est pas fourni avec un dispositif GFDI Ce contr...

Страница 22: ...y The TriStar MPPT 600V utilizes Morningstar s TrakStarTM Maximum Power Point Tracking MPPT technology to extract maximum power from high voltage power sources commonly used in grid tie applications T...

Страница 23: ...loat is to protect the battery from long term overcharge The green SOC LED will blink once every two 2 seconds during Float charging Once in Float stage loads can continue to draw power from the batte...

Страница 24: ...discharged condition the soft crystals will turn into hard crystals over time This process called lead sulfation causes the crystals to become harder over time and more difficult to convert back to so...

Страница 25: ...ranging from sealed gel AGM maintenance free to Flooded and L 16 cells In addition an 8th charging setting provides for custom set points us ing MSViewTM PC software Table 4 1 above summarizes the ma...

Страница 26: ...ure The need for temperature compensation depends on the temperature variations battery type how the system is used and other factors If the battery appears to be gassing too much or not charging enou...

Страница 27: ...d Table 4 3 Manual Equalization LED Indcations NOTE For multiple TriStar MPPT 600V controllers on a MeterBusTM network initialize a battery equalization using the TriStar meter so that all equalizatio...

Страница 28: ...ts or conditions that may require the TriStar MPPT 600V to modify operation Alarms are commonly used to alert the user that the controller is nearing a specific voltage current or temperature limit Al...

Страница 29: ...ue to be lit and the control ler will not complete start up or begin charging Retry the firmware update The firmware must be successfully loaded before the controller will start up Note The second ind...

Страница 30: ...le TSMPPT HV controllers on a network View and log data with MSViewTM PC Software View logged data stored in the TriStar MPPT 600V internal memory Update TriStar MPPT 600V firmware Program custom sett...

Страница 31: ...ble can be purchased at your local electronics retailer Tripp Lite brand compatibility has been verified The serial connection is ideal for configuring custom settings or monitoring a single TriStar M...

Страница 32: ...alimentation au r seau EIA 485 si la tension nominale du syst me est sup rieure 12 V For more information on EIA 485 networking refer to the Morningstar Communications Document on our website at http...

Страница 33: ...erts Text Messages The email and SMS alerts feature sends notification to an email address or mobile phone if one of the following occurs TriStar MPPT 600V self diagnostics fault condition TriStar MPP...

Страница 34: ...g a large segment of the MIB hierarchy to be queried by the SNMP manager from a managed device RESPONSE Used by the SNMP Agent to deliver requested information Also acts as an acknowledgment WARNING R...

Страница 35: ...pter The default MODBUS ID of the TriStar MPPT 600V is 1 Verify that the PC software is configured to communicate using the correct ID Problem Cannot connect to the controller via EIA 485 Solution Che...

Страница 36: ...ller before installing or adjusting the TriStar MPPT 600V There are no fuses or disconnects inside the TriStar MPPT 600V Do not attempt to repair Informations de S curit Lisez toutes les instructions...

Страница 37: ...onstitu de batteries du m me type fabricant et ge Ne fumez pas proximit du groupe de batteries Les connexions d alimentation doivent rester serr es pour viter une surchauffe excessive d une connexion...

Страница 38: ...un personnel bien inform sur les piles et les pr cautions de s curit appropri es Soyez tr s prudent quand vous travaillez avec des grandes batteries au plomb Portez des lunettes de protection et ayez...

Страница 39: ...xcept the SureSineTM inverter are warrantied to be free from defects in materials and workmanship for a period of FIVE 5 years from the date of shipment to the original end user Warranty on replaced u...

Страница 40: ...Volts Maximum Battery Current 60 Amps 60 Amps 63A breaker included Maximum Solar Input Voltage Maximum Operating Input Current 600 Volts dc 600 Volts dc 15 Amps 15 Amps Battery Operating Voltage Range...

Страница 41: ...33 6 mm2 Terminal block wire size DB model Solar 14 AWG 2 5 mm2 to 4 AWG 21 1 mm2 Battery 14 AWG 2 5 mm2 to 2 AWG 33 6 mm2 Grounding 14 AWG 2 5 mm2 to 4 AWG 21 1 mm2 Recommended Torques 5 16 in power...

Страница 42: ...ray Voltage Volts Battery Current Amps Battery Current vs Array Voltage OVER VOL TAGE Figure 10 1 Battery Current vs Array Voltage 10 0 Appendix 0 10 20 30 40 50 60 70 60 65 70 75 80 85 90 95 Heatsink...

Страница 43: ...Array Voltage 84 86 88 90 92 94 96 98 100 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 E ciency E cien...

Страница 44: ...0 C ambient temperature Exceeds wire ampacity at 40 C ambient temperature Exceeds wire ampacity at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway c...

Страница 45: ...C ambient temperature Exceeds wire ampacity at 40 C ambient temperature Exceeds wire ampacity at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway ca...

Страница 46: ...TO PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES LOSS OF USE DATA OR PROFITS OR BUSINESS INTERRUPTION HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING...

Отзывы: