CPT

16 

The Interface Solution Experts

PC-Programmable Signal
Isolater/Converter

Figure 10. PC Confi guration Software Custom Table Tab

The Custom Table  feature allows you to setup your 
own custom curve table (Figure 10).  This allows you 
to tell the CPA what it should output when it receives 
a certain input.  This feature also allows you the ability 
to write a table in Microsoft

®

 Excel, save it in a .csv 

format.  The fi les are saved to/read to/read from the 
“Moore Industries\Custom Curves” folder. This makes 
it simple to save the custom table for downloading to 
multiple units or for backup purposes.  

The linearization will be in the form of X, Y 
coordinates.  You may choose up to 128 points.

To access this function click the Custom Table tab.  

1.  Select the number of points you are to set and 
insert this value into the “Number Of Points” line, hit 
“Enter”.  This will highlight the number of points you 
have selected.

Note:

To clear the table and start over at any time, click  

“Clear Table”.

2.  Type your individual values in the X and Y columns.  
Source variables are inserted into the X Column while 
the corresponding data is inserted into the Y Column.

3.  To save the displayed custom table  to your hard 
drive click the “Save Table” button.

To open or use this saved table at a later time, click 
the “Open Table” button and select the folder in which 
it  has been saved.

Use the “Table EGU” box to enter any alphanumeric 
engineering unit (up to 6 digits).

To use the Custom Table feature in your operation 
check the “Custom Table ON” box.

Note:

Once you have confi gured all parameters, 

download to the unit by either selecting “Download 

Confi guration” in the Confi guration dropdown menu 

located in the Communications bar or by clicking the        

button.

Custom Table

Содержание CPT HLPRG

Страница 1: ...CPTMay 2016 225 708 00 D PC Programmable Signal Isolater Converter All product names are registered trademarks of their respective companies CPT HLPRG PC Programmable Signal Isolater Converter...

Страница 2: ...s 6 Configuring the CPT 7 Installing the Configuration Software 8 Connecting the CPT to the PC 8 PC Configuration Software Summary 9 Configuration 10 Output Level if Failure 10 Broken Wire Test Overri...

Страница 3: ...Custom Table 16 Installation 17 Mounting the CPT 17 Making the Electrical Connections 17 Recommended Ground Wiring Practices 17 CE Conformity 17 Operation 17 Maintenance 17...

Страница 4: ...figuration The output may also be configured to narrower spans from the PC Configuration Program TX Power A transmitter excitation power supply is standard on the CPT HLPRG You may access this at the...

Страница 5: ...cal 3W max Power Supply Effect 0 002 of span per 1 of line change Input Impedance 20ohms for current inputs 1 1Mohm for voltage inputs Input Over Range Protection 100mA for current inputs 30Vdc for vo...

Страница 6: ...KEY AC DC Power Input ACC DCC Power Input CM Relay Common COM Analog Common GND Ground NOTES 1 Terminal blocks can accomodate 14 22 AWG solid wiring 2 NO CM NC labeling is present only when the unit i...

Страница 7: ...igent PC Configuration software The software settings are downloaded to the transmit ter in the form of a Configuration File and stored in the instruments memory You can save a backup copy of the file...

Страница 8: ...mitter and most parameters can be set without benefit of input from a CPT This makes it easy to create a set of operating parameters save them to disk and download them to one or more transmitters at...

Страница 9: ...ou may enable Start Measurements and Stop Measurements upload your configuration to PC or download your configuration to the unit save your configuration to a file and print out your configuration set...

Страница 10: ...3 6mA upscale for voltage outputs limits are 0 5V downscale and 11 0V upscale When a failure is detected the Fail Last feature if enabled holds the last measured value before the failure occurred If t...

Страница 11: ...re energized whenever the process input is in an alarm condition These relays de energize when the process input returns to the reset point including any deadband Band Alarm The Band Alarm incorporate...

Страница 12: ...verifies that the input from the sensor to the alarm is being interpreted correctly The CPT can trim any point along the scale Note that one point trimming applies an offset to the sensor reading whi...

Страница 13: ...grammable Signal Isolater Converter Figure 7 Trimming the CPT HLPRG MULTIMETER OR DCS NO INPUT READY ALARM COM COMPUTER PROGRAMMABLE TRANSMITTER VOLTAGE SOURCE _ CURRENT SOURCE _ _ AC OR DC POWER SUPP...

Страница 14: ...es stored click the Output Trim ON 5 Set Status back to Measurements On If selected the User trim values will be used and the manufacturer settings will be nullified Loop Test A Loop Test may be perfo...

Страница 15: ...he software 3 Insert a value between 5 and 120sec in the Damping Sec field This is the amount of time it will take for the output to reach 63 of the step output change once the input exceeds the value...

Страница 16: ...nts you are to set and insert this value into the Number Of Points line hit Enter This will highlight the number of points you have selected Note To clear the table and start over at any time click Cl...

Страница 17: ...ons Please refer to Figure 3 for electrical connections Recommended Ground Wiring Practices Moore Industries recommends the following ground wiring practices Any Moore Industries product in a metal ca...

Страница 18: ...nt packing material and carefully pack the equipment in a sturdy shipping contain er 5 Ship the equipment to the Customer Service Department nearest you The returned equipment will be inspected and te...

Отзывы: