Installation
RX 200
Control Module Installation
C. Control Module Installation
1. Position the new control module on the fireplace floor ( the red
switch "SW1" must be towards the front of the fireplace).
2. Connect the Power Plug to X1
2. Ensure the prefitted rubber gasket is properly positioned (Figure
11 - D). Otherwise, fit the gasket as shown.
3. Position the stepper motor on the gas control valve as shown in
Figure 12 - E.
4. Manually thread the two supplied mounting screws into the valve
body. Use a torque screw driver with Torx T20 bit, to tighten the two
screws to a torque setting of 25 lb-in +/- 5%.
5. Install the enclosed identification label to the valve body Figure 12
- G.
Figure 11
Stepper Motor Installations
Figure 12
Label Installation
Figure 13
Identification Label
- NG
Figure 14
Identification Label
- LP
Figure 15
New Control Module
Figure 16
X1 plug on control module
3. Connect the Spark and sensor wires to X2 and X3
4. Connect the Manual ON/OFF switch to X4
5. Connect the Valve Harness to X5
6. Connect the Stepper motor harness to X6
7. Attach the Control module to the bottom of the firebox using the
velcro strips supplied.
Figure 17
X2 > X6 plugs on control module