Page 4 of 13
MW38-BV Modular Fireplace
XG0310 Rev. 01 - 11/98
Installing The Gas Line
The gas line must be installed before finishing the MW38-BV Fire-
place.
Natural Gas
requires a minimum inlet gas supply pressure of
5.5" W.C. & a manifold pressure of 3.5" W.C.
Propane Gas
requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace
gas connection and the main operating gas valve is located behind
the removable brass trim at the bottom of the unit and need only be
attached to the gas line with an approved fitting, as required by the
applicable installation codes
.
Installation
Note:
After gas line is connected,
each
appliance connection
,
valve and valve train
must be checked while under
normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.
DO NOT use a flame of any kind to test for leaks.
Installing The Remote Switch
The
MW38-BV'
s gas valve, located behind the lower brass trim, may
be connected to a wall switch. The valve generates its own power on
a
millivolt circuit.
Use only low voltage wire, and
DO NOT
connect
any external power to it.
Refer to Figure 26 for wiring requirements.
Note:
The switch location must not exceed 30' from the fireplace.
Figure 5.
Gas line access.
2 1/2
Gasline access
6 x 2 1/2"
1
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
B-Vent Installation
The
MW38-BV
is certified for use with standard
4" B-Vent
and
requires no B-Vent appliance connector. Simply attach the B-Vent to
the fireplace flue collar, and secure it using 1/4" sheet metal screws.
Do not penetrate the inner sleave of the B-Vent when tightening the
screws.
Refer to the current
CAN/CGA B-149.1
and
.2
or
ANSI Z223.1-1988
Gas Installation Code
for specific vent sizing.
•
Test your B-Vent installation after completion to ensure that
no combustible by-products are spilling from the fireplace
opening. This draft test should be performed after a three(3)
minute warm up period. The manufacturer will not be
responsible for any installations with inadequate draw.
CAUTION: