MW38-BV  Modular Fireplace

XG0310 Rev. 01 - 11/98

Installing The Gas Line

The gas line must be installed before finishing the MW38-BV Fire-
place. 

Natural Gas

 requires a minimum  inlet gas supply  pressure of

5.5" W.C. & a manifold pressure of 3.5" W.C. 

Propane Gas

 requires a

minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace
gas connection and the main operating gas valve is located behind
the removable brass trim at the bottom of the unit and need only be
attached to the gas line  with an approved fitting, as required by the

applicable installation codes

.

Installation

Note:

After gas line is connected, 

each 

appliance connection

,

valve and valve train

 must be checked while under

normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.

DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The 

MW38-BV'

s gas valve, located behind the lower brass trim, may

be connected to a wall switch. The valve generates its own power on

millivolt circuit.

 Use only low voltage wire, and 

DO NOT

 connect

any external power to it.

Refer to Figure 26 for wiring requirements.

Note:

  The switch location must not exceed 30' from the fireplace.

Figure 5.  

Gas line access.

2 1/2

Gasline access
6 x 2 1/2"

1

The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).

B-Vent  Installation

The 

MW38-BV 

is certified for use with standard 

4" B-Vent 

and

requires no B-Vent appliance connector. Simply attach the B-Vent to
the fireplace flue collar, and secure it using 1/4" sheet metal screws.
Do not penetrate the inner sleave of the B-Vent when tightening the
screws.

Refer to the current 

CAN/CGA B-149.1

 and

 .2

 or 

ANSI Z223.1-1988

Gas Installation Code

 for specific vent sizing.

Test your B-Vent installation after completion to ensure that
no combustible by-products are spilling from the fireplace
opening. This draft test should be performed after a three(3)
minute warm up period. The manufacturer will not be
responsible for any installations with inadequate draw.

CAUTION:

Содержание MW38-BV

Страница 1: ...in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper insta...

Страница 2: ...ons If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA must...

Страница 3: ...rd clearance as specified by the manufacturer of the B Vent 14 33 41 35 38 28 35 14 4 4 Figure 1 Fireplace dimensions Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framin...

Страница 4: ...may be connected to a wall switch The valve generates its own power on a millivolt circuit Use only low voltage wire and DO NOT connect any external power to it Refer to Figure 26 for wiring requireme...

Страница 5: ...he effects of elevated mantel temperatures which may be in excess of product design for example candles plastic or pictures This can cause melting deformation discoloration or premature failure of T V...

Страница 6: ...normal occurance Gas Control and Pilot Wiring MW38 BV I Honeywell Q3450 Pilot Assembly Pilot Electrical Harness Connector Honeywell Gas Control SV9501M Gas Control Connector Fuse Limit Switch Wall Swi...

Страница 7: ...ess you may remove the effiiciency baffles to gain access to the venting plate 3 Remove the insert by tipping the top of the insert outward and lifting the tabs past the slots in the bottom of the she...

Страница 8: ...Model MW38 BV 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower brass trim 1 Turn off remote switch 2 Flip down lower brass trim 1 STOP Read the safety inform...

Страница 9: ...o light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn...

Страница 10: ...water Operation Lighting Instructions See pages 8 and 9 Burner Adjustment The Wildfire is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the...

Страница 11: ...ve open Replace SV9500 SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transfor...

Страница 12: ...other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability Limitations On Liability Limitations On Liability...

Страница 13: ...el MW38 BV I 6 Aluminum Tubing 1 4 dia 7 Locking Nuts 8 Spacer 9 Bulkhead Fitting 10 90 Elbow 11 Burner Orifice 12 Burner Tube Available Options and Accessories 13 Add on Bay Window 14 Hand Held Remot...

Страница 14: ...Page 14 of 13 MW38 BV Modular Fireplace XG0310 Rev 01 11 98 Canadian Heating Products Inc Surrey BC V3W 2V6 Montigo Del Ray Corp Ferndale WA 98248 XG0310 Rev 0 09 98...

Отзывы: