background image

Page 11 of 13

MW38-BV  Modular Fireplace

XG0310 Rev. 01 - 11/98

Maintenance

Troubleshooting

If your fireplace still does not operate correctly, consult your dealer or
the manufacturer.

All service and repairs should be performed by a qualified
agency.

All spare parts, optional fans (see optional fan instruction guide), and
optional trim finishes are available from Canadian Heating Products
Inc. or your local dealer.

HONEYWELL SV 9500 /SV9600

Troubleshooting Sequence

NOTE:

Before Troubleshooting, Familiarize Yourself With

The Startup And Checkout Procedure.

· Turn Gas Supply off
· Set thermostat to

call for heat

SV9500/SV9600

is powered
(24 VAC nominal)

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

START

Igniter warms up
and glows red.

Pilot Valve opens.

Turn gas on.
Pilot Burner lights?

Main Valve opens?

SYSTEM OK

Unplug Pilot Burner Cable,

Measure Voltage at

SV9500/SV9600 HSI

Terminals (24 VAC

Nominal, See INSET)

Replace Igniter/

Flame Rod Assembly.

Replace Igniter/
Flame Rod Assembly.

Replace SV9500/SV9600

Measure Voltage to SV9500
/SV9600. Voltage must
be at least 19.5 VAC

Discard old Igniter/
Flame Rod Assembly.

Replace Igniter/Flame
Rod Assembly and retain.
Restart Troubleshooting

Sequence. Does main
valve open?

Replace
SV9500/

SV9600

Check
Transformer

Line Volt
Supply

Replace
SV9500/
SV9600.
Save old
Igniter/Flame

Rod Assembly
for service.

INSET

HSI

Terminals

CHECK:

· Line voltage power

· Low voltage transformer

· Limit Controller

· Thermostat

· Wiring

· Air proving switch on

combustion air blower system

· Vent damper (if used) is open

and end switch made

Gas Control Valve

Figure 13. 

Sit Nova 820 gas valve

.

Pilot  Burner Adjustment

1.

Locate Pilot Adjustment Screw. 

(See figure 13.)

2.

Adjust pilot screw to provide properly sized flame as shown in

figure 14).

3.

After installing or servicing, leak test with a soap solution with
main burner on. Coat pipe and tubing joints, gasket etc. with soap
solution. Bubbles indicate leaks. Tighten any areas where the
bubbles appear until the bubbling stops completely.

MW38-BV-I

Figure 14. 

Pilot Burner

Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy Pilot Flame

Locate pilot adjustement screw on gas
control valve. Flame is decreased by
turning adjustment screw clockwise.

Pilot won’t ignite

Disconnect remote wires and try to
light pilot. If pilot now works, remote
connections are faulty. Check wiring
diagram 

figure 

13

.

Main burner will

1. Check wiring (

see figure 13

).

not light

2. Check wall switch for proper
connection.

MW38-BV

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Содержание MW38-BV

Страница 1: ...in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper insta...

Страница 2: ...ons If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA must...

Страница 3: ...rd clearance as specified by the manufacturer of the B Vent 14 33 41 35 38 28 35 14 4 4 Figure 1 Fireplace dimensions Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framin...

Страница 4: ...may be connected to a wall switch The valve generates its own power on a millivolt circuit Use only low voltage wire and DO NOT connect any external power to it Refer to Figure 26 for wiring requireme...

Страница 5: ...he effects of elevated mantel temperatures which may be in excess of product design for example candles plastic or pictures This can cause melting deformation discoloration or premature failure of T V...

Страница 6: ...normal occurance Gas Control and Pilot Wiring MW38 BV I Honeywell Q3450 Pilot Assembly Pilot Electrical Harness Connector Honeywell Gas Control SV9501M Gas Control Connector Fuse Limit Switch Wall Swi...

Страница 7: ...ess you may remove the effiiciency baffles to gain access to the venting plate 3 Remove the insert by tipping the top of the insert outward and lifting the tabs past the slots in the bottom of the she...

Страница 8: ...Model MW38 BV 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower brass trim 1 Turn off remote switch 2 Flip down lower brass trim 1 STOP Read the safety inform...

Страница 9: ...o light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn...

Страница 10: ...water Operation Lighting Instructions See pages 8 and 9 Burner Adjustment The Wildfire is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the...

Страница 11: ...ve open Replace SV9500 SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transfor...

Страница 12: ...other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability Limitations On Liability Limitations On Liability...

Страница 13: ...el MW38 BV I 6 Aluminum Tubing 1 4 dia 7 Locking Nuts 8 Spacer 9 Bulkhead Fitting 10 90 Elbow 11 Burner Orifice 12 Burner Tube Available Options and Accessories 13 Add on Bay Window 14 Hand Held Remot...

Страница 14: ...Page 14 of 13 MW38 BV Modular Fireplace XG0310 Rev 01 11 98 Canadian Heating Products Inc Surrey BC V3W 2V6 Montigo Del Ray Corp Ferndale WA 98248 XG0310 Rev 0 09 98...

Отзывы: