background image

37

Operation

XG0146 - 180405

Section 10: Cleaning and Maintenance 

General

• 

Have the fireplace and installation inspected yearly. The inspection 

must include, but is not limited to, the following: 

•  A visual check of the entire vent system and termination, where 

accessible.

• 

An inspection of   the explosion relief  flappers and the door 

gaskets to ensure a proper seal.  

•  An inspection of the burner, vent run, and primary air openings.
• 

An inspection of the gas valve, gas components, and pilot flame.  

For your convenience a 1/8" manifold pressure tap is supplied 

on the gas valve for a test gauge connection.

•  Inspection of all optional equipment; fans, thermostats, remote 

control lights, etc. 

•  For Natural Gas this appliance requires a minimum inlet pressure 

of 5.5" W.C. and a manifold pressure of 3.5" W.C.

•  For Propane Gas this appliance requires a minimum inlet pressure 

of 11" W.C. and a manifold pressure of 10" W.C.

• 

Always keep the fireplace area clear and free of combustible materials, 

as well as gasoline and other flammable vapors and liquids. 

•  Do not use this appliance if any part has been under water. 

Immediately call a qualified service technician to inspect the appliance 

and to replace any part of the control system and any gas control 

which has been under water.

•  Inspection of glass doors and screen for damage and proper 

installation.

Cleaning

When the fireplace is first activated, there may be some smoke and a 

visible film may be left on the glass. This is a normal condition, and is 

the result of burning of protective coatings on new metal.
•  Glass must be cleaned periodically to remove any film (which is 

a normal by-product of combustion) which may be visible. Film 

can easily be removed by removing the door. Handle the door 

carefully, and clean it with non-abrasive, non-ammonia based 

glass cleaners. One of the most effective products is Kel-Kem.

•  During the initial firing, Silicone seals will "off gas", leaving a 

visual deposit of a white substance on combustion chamber 

walls. This can easily be removed using normal household 

products.

•  Use a vacuum cleaner or whisk broom to keep the control 

compartment, burner, and firebox free from dust and lint.

Figure 28.

 

Hi-Lo' Adjustment on the SIT Nova 820  gas valve

Figure 28.b

 

'Hi-Lo' Adjustment on the SIT Proflame 2 gas valve.

Hi-Lo Burner Adjustment: (SIT Nova 

820).

The H*34DF* is equipped with an adjustable burner, allowing you to 

raise or lower the flames. To adjust the flames, locate the black knob 

marked 'Hi-Lo', in the centre of the gas control valve (See Figure 33). 
• 

To raise the flame height, turn the black knob (located behind the 

lower control compartment) counter-clockwise.

• 

To lower the flame height, turn clockwise.

Hi-Lo Burner Adjustment: (SIT Proflame 

2).

The H*34DF*I is equipped with an adjustable burner, allowing you to 

raise or lower the flames. To adjust the flames, locate the black knob 

marked 'Hi-Lo', in the centre of the gas control valve (See Figure 34). 
• 

To raise the flame height, turn the black knob (located behind the 

lower control compartment) counter-clockwise.

• 

To lower the flame height, turn clockwise.

Pilot Burner Adjustment.

1. 

Locate Pilot Adjustment Screw. (See figure 33 or 34.)

2. 

Adjust pilot screw to provide properly sized flame as shown.

3. After installing or servicing, leak test with a soap solution with main 

burner on. Coat pipe and tubing joints, gasket etc. with soap solution. 

Bubbles indicate leaks. Tighten any areas where the bubbles appear 

until the bubbling stops completely.

Do not use ammonia or abrasive cleaners on the glass, they will 

permanently etch the surface. Use an approved gas fireplace cleaner 

such as Kel-Kem or White off.

NOTICE

Manifold Pressure

Test Connection

Wall Switch

Power 

Generator

Pilot Adjustment Screw

Inlet Pressure

'Hi-Lo' Adjustment Knob

Gas Control Knob (Shown in “Pilot” position)

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Hi Lo Adjustment

Inlet Pressure
Test Connection

Содержание H34DF

Страница 1: ...tural Gas or Propane Gas HLB34 18 000 BTU hr Natural Gas or Propane Gas HLB34 2 18 000 BTU hr Natural Gas or Propane Gas Read and understand this manual Improper installation adjustment alteration ser...

Страница 2: ...ion See Appendix B The Montigo warranty will be voided by and Montigo disclaims any responsibility for the following actions Modification of the fireplace and or components including Direct Vent assem...

Страница 3: ...3 Fireplace Facing 23 Finishing around the fireplace 23 Flush Finishing the Fireplace 23 Section 7 Screen Installation and Removal 24 Removing the Screen 24 To Install Screens 24 Replacement Screens 2...

Страница 4: ...tricalinstallations mustconformtothelocalcodesor intheabsenceoflocalcodes to the current version of Canadian Electrical Code CSA C22 1 1 Installations in the USA must conform to the local codes or in...

Страница 5: ...tops installed Exteriorwall roofflashinginstalledandsealedincompliancewithlocalbuildingcode Terminations installed and sealed in compliance with local building code Direct vent termination is highest...

Страница 6: ...6 180405 Rating Plate Sample Figure 1 1 Rating Plate for standing pilot SIT Figure 1 2 Rating Plate for IPI electronic ignition LBL1205 V6 2 Stand Pilot Screen AUG 17 2015 LB1223 V5 2 SIT IPI with scr...

Страница 7: ...affic has adequate ventilation and offers an accessible path for Direct Vent installation 898 35 3 8 134 5 1 4 578 22 3 4 140 5 1 2 797 31 3 8 653 25 11 16 489 19 1 4 838 33 86 3 3 8 203 8 POWER SUPPL...

Страница 8: ...ons Shelves over the fireplace Alcove above the fireplace Shelves over the fireplace Top vent Figure 3 b Combustible Framing for shelves over the fireplace Rear vent Figure 3 d Combustible Framing for...

Страница 9: ...ions the minimum clearance is 2 from the rear of the fireplace to a wall or any combustible materials and 17 to the underside of any combustible shelf materials Figure 4 For Top or Rear Vent applicati...

Страница 10: ...nation location is acceptable Once the termination location has been established refer to the appropriate section below for installation details All fireplaces shipped from the factory are top vent Si...

Страница 11: ...led diagram of allowed termination locations see Appendix A A maximum of two offsets each offset is made up of 2 90 bends may be made for vertical vent runs Firestops must be installed as required by...

Страница 12: ...upport plate 32 max Termination 12 Max PVTK1 PEXT Sections Figure 6 d Rear vent roof mounted venting 1 90 bend Storm collar Support plate 32 max Roof flashing MVTK1 Termination Support ring MEXT Secti...

Страница 13: ...the interior side of the studs concrete or finished wall construction using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here from the inside and attach to the MOSR by i...

Страница 14: ...ed area the installation is acceptable Wall mounted Terminations ThefollowingdetailsaresomepossibleconfigurationsforWallmounted terminations See below Heat Shield Termination Hearth Exterior Wall 39 M...

Страница 15: ...the Venting Graph with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable VENT RUN Figure 9 H 34DF Rear Vent Venting Graph for wall mounted terminations...

Страница 16: ...onandanMFL 1orMFL 2 12 or24 compressed length andaframe ifappropriate Flexmaybeturnedtoobtaindesired degree of angle required but must not exceed 45 NOTE Through the wall venting kits are also availab...

Страница 17: ...of rigid pipe to maintain integrity of internal supports For flex venting place the springs supplied with the pipe kit between the outer and inner pipes to keep the pipes separate and avoid any possib...

Страница 18: ...f m Section MEXT 3 36 f m Section MEXT 4 48 f m Section MEXT 6 72 f m Section 46DVA 06 6 Section 46DVA 09 9 Section 46DVA 12 12 Section 46DVA 18 18 Section 46DVA 24 24 Section 46DVA 36 36 Section 46D...

Страница 19: ...e structure To complete the installation fasten the Heat Shield Outer Section Termination frame to the structure Figure 15 e RHS100 Installation Figure 15 c RHS100 Installation Install by sliding Oute...

Страница 20: ...ights ON OFF CONTROL MAIN Power 120VAC 60 Hz 6 Amps SPARK SENSOR RED BLACK BATTERY PACK MAIN ON OFF SWITCH YELLOW GREEN 5 PROFLAME PILOT B RNER ORANGE GREEN BLACK BROWN YELLOW ORANGE 6 10 6 B B Wht Wh...

Страница 21: ...cold start condensationwillnormallyformontheinnerglass surface of the door This condensation will quickly dry however the condensation tends to run down the glass and cause some streaking CPI mode he...

Страница 22: ...ction valve and valve train under normal operatingpressurewithacommerciallyavailableleakchecksolution DO NOT USE A FLAME OF ANY KIND TO TEST FOR LEAKS PRESSURE REQUIREMENTS Gas Pressure Natural Gas Pr...

Страница 23: ...D INTO A WALL Side wall clearances are 3 Combustible surrounds may be installed with 3 clearance to the side of the fireplace as shown Combustible Header Drywall Sheetrock 3 45 6 When covering the upp...

Страница 24: ...fireplace has been turned off Safety screens are mandatory while glass is hot and can reduce the risks of severe burns Please keep children away from the fireplace at all times CAUTION NOTICE Screen B...

Страница 25: ...or on either side usually midway and lift upward lift the door carefully up and away from the front of the fireplace Place the door aside in a safe place while maintenance and or cleaning is being per...

Страница 26: ...ontigo burners and accessories Never install or add any additional or alternative media rock wool or other material in this appliance The use of additional or alternative materials may pose potential...

Страница 27: ...satisfactory replace the glass door If the flame does not appear satisfactory double check the air inlet and exhaust outlet pipe to ensure that they are unobstructed STEP 7 Place the Embers as shown A...

Страница 28: ...P 3 Slide the rock guard locator tabs behind the Burner The rocks on the Rock Guard should line up between the air inlets of the burner STEP 4 Slide the rock guard locator tabs behind the Burner The r...

Страница 29: ...hree faux D ceramic Rocks between burner and front of firebox frame flat surfaces of rock against the front of door opening and bottom pan of the fireplace Note similar size of rock diameters Figure 2...

Страница 30: ...ux Rock on top behind the pilot burner faux Rocks Figure 23 t Place the seventh Top faux Rock in the front Figure 23 u Place the eight Top faux Rock in the front to the Right of the last Rock Figure 2...

Страница 31: ...unless knob is pushed in slightly Do not force Standing Continuous Pilot Ignition SIT NOVA 820 with American Flame Electronic Ignition For Your Safety READ BEFORE LIGHTING C Use only your hand to pus...

Страница 32: ...the Troubleshooting section Repeat step 5 9 If the system will not function correctly follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier 1 STOP Read...

Страница 33: ...flame 2 Control Module 4 Wiring Harness 5 Variable Speed fans If applicable 7 Proflame 2 remote control 8 Battery Pack 9 Manual override switch NOTE Can not be used with home automation systems SW1 Pr...

Страница 34: ...r 4 times to indicate transmitter s command is accepted The System is now initialized Temperature Indication Display With the system in the Off position press the Thermostat Key and the Mode Key at th...

Страница 35: ...show that the room thermostat is On and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD sc...

Страница 36: ...to turn on off or adjust the fan speed A single beep will confirm reception of the command Disabling Thermostat Some jurisdictions and bedroom installations require the thermostat to be disabled 1 Pa...

Страница 37: ...ring the initial firing Silicone seals will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed using normal household products Use a vacuum cl...

Страница 38: ...Pressure are within acceptable limits Pilot lights but Main burner will not Light and igniter continues to spark 1 Check the Pilot Flame Sensor Rod and clean with steel wool or similar 2 Check the Pi...

Страница 39: ...Pilot Tubing RPTA03 Door RDTH34 Replacement Screen RSCH34 Replacement Parts List SIT IPI Proflame 2 Part H34DF I HLB34DF I HLB34DF I 2 Log Set RLGSH34 N A N A NG Gas Valve hi low RGC3044 Propane Gas V...

Страница 40: ...bustion air inlet to other appliance for appliance 100 000 BTU H 30 KW 12 inches 12 inches M clearance to forced air supply inlet 6 feet 3 feet above air inlet N clearance above paved sidewalk or pave...

Страница 41: ...gas NG or liquefied petroleum LP only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the appliance produce excessive temperatures will result in a...

Страница 42: ...of The Companies The Companies shall in no event be responsible for any warranty work done without first obtaining the Companies written consent The Companies employees and dealers have no authority t...

Страница 43: ...he sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Appendix C Amendment Gas Fireplace Equipment sold in the State of Massach...

Страница 44: ...XG0146 180405 Installation Maintenance Manual H34DF HLB34DF HLB34DF 2 Single Sided Gas Fireplace...

Отзывы: