Page 4

H34D Gas Fireplace

Part No. XG0130

Vent  Installation

This section covers the installation of direct venting and terminations.

Installation Requirements

H34D fireplaces are certified for use with Montigo Standard Series

(4" / 7")

 venting components.

Minimum 

2" clearance to combustibles 

required for vent pipes

Use only 

certified Montigo vent components.

 (Use of other parts will void the

Montigo warranty, and may impede the operation of the fireplace.)

All joints must be secured with a minimum of two screws per joint

Vent terminations must not be recessed in walls or siding

Horizontal runs must be supported by a minimum of two supports
per horizontal run. A minimum of one screw on each side of
support is also required

Flex vent sections may be stretched up to 50% of their total length
(eg. a 24" section may be stretched to 36").

Maximum horizontal run with no vertical rise is 6 feet.

Solid vent sections may be cut less than half way from the female end

Venting components can be used in any combination of solid/rigid
pipe or flex pipe and in any orientation (Male connectors can face
in any direction)

Vent Terminations

Selecting A Termination Location
Choosing your vent termination location will help to determine whether
you need to use a top vent or rear vent fireplace. Figure 6a, below,
shows typical fireplace locations and the venting options they provide.
For a more detailed diagram of allowed termination locations, see
Appendix A.

Cautions:

Cautions:

Cautions:

Cautions:

Cautions:

Installing The Gas Line

The gas line must be installed before finishing the H34D Fireplace.
Natural Gas requires a minimum  inlet gas supply  pressure of 5.5"
W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure of
10" W.C. Provision must also be made for a 1/8" N.P.T. plugged tapping
and be accessible for test gauge connection immediately upstream of the
gas supply controls to the appliance. The fireplace gas connection and
the main operating gas valve is located behind the removable trim at the
bottom of the unit and need only be attached to the gas line  with an
approved fitting, as required by the applicable installation codes.
• Only use gas shut-off valves approved for use by the state, province,
region, or governing body, in which the appliance is being installed, or
as required by the applicable installation codes.
• Flexible gas connectors must not exceed 3 feet in length, unless it is
allowable  within applicable installation codes.

Installation

Figure 6a.

  

Fireplace locations and vent terminations.

Note:

After gas line is connected, 

each 

appliance connection

,

valve and valve train

 must be checked while under

normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.

DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The H34D's gas valve, located behind the lower trim, may be connected
to a wall switch. The valve generates its own power on a millivolt
circuit. Use only low voltage wire, and DO NOT
 connect any
external power to it.
Refer to Figure 30 for wiring requirements.
Note:  The switch location must not exceed 30' from the fireplace.

Figure 5.  

Gas line access.

The appliance and its individual shutoff valve must be disconnected from
the gas supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).

Vent terminations can be very hot. If the termination

is less than 7 feet above a public walkway, it should

be fitted with a certified Montigo Heat Guard. (Part no.

MTKOG)
Do not obstruct, or attempt to conceal, the vent

termination. These actions will affect the operation

of the fireplace, and may be hazardous.
In heavy snow areas, take extra care to prevent snow

buildup from obstructing the vent termination.

Содержание H34D

Страница 1: ...ur gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do n...

Страница 2: ...ConsultyourlocalGasInspectionBranchoninstallationrequirementsfor factory builtgasfireplaces Installation repairsshouldbedonebya qualifiedcontractor Installations in Canada must conform to the current CAN CGA B 149 1and 2GasInstallationCodeandlocalregulations Iftheoptional air circulatingfankitisinstalled itmustbeelectricallygroundedin accordance with CSA C22 1 Canadian Electrical Code Part 1 and o...

Страница 3: ...m Corner framing dimensions using a 45 elbow Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framing depth may be reduced to 16 Framing WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Top View Front Vi...

Страница 4: ...cegasconnectionand themainoperatinggasvalveislocatedbehindtheremovabletrimatthe bottomoftheunitandneedonlybeattachedtothegasline withan approved fitting as required by the applicable installation codes Only use gas shut off valves approved for use by the state province region or governing body in which the appliance is being installed or asrequiredbytheapplicableinstallationcodes Flexiblegasconnec...

Страница 5: ...SRframeasshownhere and attachbyscrewingthroughthefourpilotholesinthetermination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensurethatthetwolongmountingbracketsarefacingthebottomof thetermination Seeinset Thiswillprovidemoreheatprotection atthetopofthetermination wheretemperaturesarehighest 2 Attachtothefaceplateoftheterminationusingfoursheetmetalscrews Installing Heat Guards over Terminations Installation Ins...

Страница 6: ...let using5screws asillustratedbelow Figure 7a Flue cap installation for Top Vented fireplace Figure 7b Flue collar installation for Top Vented fireplace Figure 8a Flue cap installation for Rear Vented fireplace Figure 8b Flue collar installation for Rear Vented fireplace H34DL Rear Vent UsethefollowinginstructionstoconvertanH34DLforTopVentuse 1 Installthe4 innerfluecaponthetopflueoutletandsecureth...

Страница 7: ...gcanaffectthefireplace s combustion themaximumverticalventrunforaTopVentedunitis32feet The Venting Graph Measuretheverticalheightfromthefireplacehearthtothecentreofthe terminationandthehorizontalrunfromthefromthefireplacefluecollarto thewallflangeofthetermination PlotontheVentingGraph Fig 9 with an X If the X falls on or above the top boundary of the shaded area the installationisacceptable Exampl...

Страница 8: ... D rigidsectionsmaybeusedinconjunctionwith oneanothertoobtaindifferentpossiblehorizontallengthinstallations Figure 13 ExtendedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select appropriate components Figure 14 RetractedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select ap...

Страница 9: ...h MEXT 2 24 length MEXT 3 36 length MEXT 4 48 length D Support Ring Plate MSPXT 7 E Firestop FS 7 F Roof Flashing MRF 7 1 12 7 12 pt MRF 12 7 12 12 12 pt Figure 16 Straight vertical venting showing required MXT 10 adaptor supplied with the MVTK 1 termination A maximum of two offsets each offset has two 90 bends may be madeandshallnotexceedtotallengthof25 oftheverticalventheight when measured cente...

Страница 10: ...andattachittotheEEL 45 Slidethefireplaceinto positionandattachtothetermination EnsurethattheRHS101 heat sheild is installed before attaching the pipe to the termination 3 Corner Installation 45 or less Use an MTO 3 termination and an MFL 1 or MFL 2 12 or 24 compressedlength andaframe ifappropriate Flexmaybeturned toobtaindesireddegreeofanglerequiredbutmustnotexceed45 Ensure that the RHS101 heat sh...

Страница 11: ...ceptable Installation Iftheverticaldimensionfromthehearthis94 andthehorizontal runtothewallflangeoftheventterminationis126 thiswouldbe anacceptableinstallation Example C Unacceptable Installation Iftheverticaldimensionfromthefloorofthefireplaceis78 andthe horizontalruntothewallflangeoftheventterminationis108 this would NOT be an acceptable installation Figure 22 H34D Rear Vent Venting Graph Instal...

Страница 12: ...tocombustiblematerials Newtechnology tomeetconsumerandgovernmentdemandsforthe wiseuseofenergy haspromptedustomanufacturemanymodelsof fireplaceswhicharehot fuelandenergyefficient Pleasebeaware temperaturesoverthemantelwillriseabovenormal roomtemperatureandwallsabovefireplacemaybehottotouch Werecommendcarefulconsiderationbegiventotheeffectsofelevated manteltemperatureswhichmaybeinexcessofproductdesi...

Страница 13: ...NOTE If any of the original wire supplied with the appliance is replaced it must be replaced with the same type or its equivalent Figure 26b Wiring schematic for optional fans Figure 26a Wiring for optional fans Removing and Installing the Door Removing the door The door is held in place by a lip on the top of the metal frame and two bucklesatthebottom Releasethebucklesandliftthedoorcarefullyup an...

Страница 14: ...Base log placement Figure 28d Bottom left and right log placement Figure 28e Top left and right log placement Base Log Bottom Left Log Bottom Right Log Top Left Log Top Right Log Base Log Bottom Right Log Bottom Left Log Top Left Log Top Right Log 5 Start the fireplace If the flame appears satisfactory replace the glass door If the flame does not appear satisfactory double check the air inlet and ...

Страница 15: ...odel H34D 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell ga...

Страница 16: ... light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trim 3 Turn the switch on the gas control to Off 4 Flip up the trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Turn sw...

Страница 17: ...ped with an adjustable burner allowing you to raise orlowertheflames Toadjusttheflames locatetheblackknobmarked Hi Lo in the centre of the gas control valve See Figure 29 The front burnersarenotadjustable Toraisetheflameheight turntheblackknob locatedbehindthe lower trim counterclockwise Tolowertheflameheight turnclockwise Figure 29 Hi Lo Adjustment on the H34D s gas valve Cleaning Whenthefireplac...

Страница 18: ... yourlocaldealerorthemanufacturer HONEYWELL SV 9500 SV9600 Troubleshooting Sequence NOTE Before Troubleshooting Familiarize Yourself With The Startup And Checkout Procedure Turn Gas Supply off Set thermostat to call for heat SV9500 SV9600 is powered 24 VAC nominal NO NO NO NO NO YES YES YES YES YES YES YES NO NO NO START Igniter warms up and glows red Pilot Valve opens Turn gas on Pilot Burner lig...

Страница 19: ...ltinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove InnoeventshallThe...

Страница 20: ...ted States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda po...

Страница 21: ...he H34D I equipped with Hot Surface Ignition HSI are not approved for use in mobile or manufac tured homes The H34D MH is rated for NaturalGasat18 000BTU H 5 28Kilowatts max input and 14 000BTU H 4 10Kilowatts min input Propane at 18 000 BTU H 5 28 Kilowatts max input and 14 000 BTU H 4 10Kilowatts min input Conversion Kits TheH34D MHmobilehomeapplianceisfieldconvertiblebetween Natural Gas NG and ...

Страница 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0130 Rev 0 11 2003 ...

Отзывы: