background image

Page 10

H34D Gas Fireplace

Part No. XG0130

Installation

Figure 20.

 

Extended installation.

Figure 21a.

 

Corner installation.

Figure 21b.

 

Flex installation.

Rear Vent Venting Runs

The H34DL Rear Vent has three possible installations which do not
require vertical lift, all of these installations require that you install the
RHS101 heat sheild.

1. Straight Installation.

The height from the hearth to the center of the termination is 27
3/8". H34DL Rear Vent versions are supplied with a 18" extension
pipe (EXT18) with female/female connections. For shorter installa-
tions, cut the EXT18 to the desired length. Refer to figure 20.
For extended installations, use the EXT18 section as supplied for a
18" vent run. Ensure that the RHS101 heat sheild is installed
before attaching the pipe to the termination.
Note:

For Rear Vent models, maximum horizontal run with no
vertical lift must never exceed 18".

2. 45° Corner Installation.

Attach an EEL-45 (45° elbow) directly onto the flue collar. Cut the
EXT-18 to suit, and attach it to the EEL-45. Slide the fireplace into
position and attach to the termination. Ensure that the RHS101
heat sheild is installed before attaching the pipe to the
termination.

3. Corner Installation — 45° or less.

Use an MTO-3 termination and an MFL-1 or MFL-2 (12" or 24"
compressed length) and a frame, if appropriate. Flex may be turned
to obtain desired degree of angle required but must not exceed 45°.
Ensure that the RHS101 heat sheild is installed before
attaching the pipe to the termination.

Figure 19.

Heat Shield. Install by sliding over the vent pipe where it
passes through combustible construction.

Heat Shield

 The heat shield (RHS101) must be used on all installations straight
through the wall
, at the point where the vent pipe connects to the
termination. With the heat shield, proper vent clearances can be
maintained. The heat shield is not included with the fireplace.
To install the heat shield, slide one section over the vent pipe on the
inside of the wall opening, with the circular portion inside the wall cavity.
Screw the shield in place over the wall opening. Install the second
section on the outside of the wall opening sliding the circular portion into
the wall opening. Refer to Figure 19.

Содержание H34D

Страница 1: ...ur gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do n...

Страница 2: ...ConsultyourlocalGasInspectionBranchoninstallationrequirementsfor factory builtgasfireplaces Installation repairsshouldbedonebya qualifiedcontractor Installations in Canada must conform to the current CAN CGA B 149 1and 2GasInstallationCodeandlocalregulations Iftheoptional air circulatingfankitisinstalled itmustbeelectricallygroundedin accordance with CSA C22 1 Canadian Electrical Code Part 1 and o...

Страница 3: ...m Corner framing dimensions using a 45 elbow Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framing depth may be reduced to 16 Framing WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Top View Front Vi...

Страница 4: ...cegasconnectionand themainoperatinggasvalveislocatedbehindtheremovabletrimatthe bottomoftheunitandneedonlybeattachedtothegasline withan approved fitting as required by the applicable installation codes Only use gas shut off valves approved for use by the state province region or governing body in which the appliance is being installed or asrequiredbytheapplicableinstallationcodes Flexiblegasconnec...

Страница 5: ...SRframeasshownhere and attachbyscrewingthroughthefourpilotholesinthetermination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensurethatthetwolongmountingbracketsarefacingthebottomof thetermination Seeinset Thiswillprovidemoreheatprotection atthetopofthetermination wheretemperaturesarehighest 2 Attachtothefaceplateoftheterminationusingfoursheetmetalscrews Installing Heat Guards over Terminations Installation Ins...

Страница 6: ...let using5screws asillustratedbelow Figure 7a Flue cap installation for Top Vented fireplace Figure 7b Flue collar installation for Top Vented fireplace Figure 8a Flue cap installation for Rear Vented fireplace Figure 8b Flue collar installation for Rear Vented fireplace H34DL Rear Vent UsethefollowinginstructionstoconvertanH34DLforTopVentuse 1 Installthe4 innerfluecaponthetopflueoutletandsecureth...

Страница 7: ...gcanaffectthefireplace s combustion themaximumverticalventrunforaTopVentedunitis32feet The Venting Graph Measuretheverticalheightfromthefireplacehearthtothecentreofthe terminationandthehorizontalrunfromthefromthefireplacefluecollarto thewallflangeofthetermination PlotontheVentingGraph Fig 9 with an X If the X falls on or above the top boundary of the shaded area the installationisacceptable Exampl...

Страница 8: ... D rigidsectionsmaybeusedinconjunctionwith oneanothertoobtaindifferentpossiblehorizontallengthinstallations Figure 13 ExtendedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select appropriate components Figure 14 RetractedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select ap...

Страница 9: ...h MEXT 2 24 length MEXT 3 36 length MEXT 4 48 length D Support Ring Plate MSPXT 7 E Firestop FS 7 F Roof Flashing MRF 7 1 12 7 12 pt MRF 12 7 12 12 12 pt Figure 16 Straight vertical venting showing required MXT 10 adaptor supplied with the MVTK 1 termination A maximum of two offsets each offset has two 90 bends may be madeandshallnotexceedtotallengthof25 oftheverticalventheight when measured cente...

Страница 10: ...andattachittotheEEL 45 Slidethefireplaceinto positionandattachtothetermination EnsurethattheRHS101 heat sheild is installed before attaching the pipe to the termination 3 Corner Installation 45 or less Use an MTO 3 termination and an MFL 1 or MFL 2 12 or 24 compressedlength andaframe ifappropriate Flexmaybeturned toobtaindesireddegreeofanglerequiredbutmustnotexceed45 Ensure that the RHS101 heat sh...

Страница 11: ...ceptable Installation Iftheverticaldimensionfromthehearthis94 andthehorizontal runtothewallflangeoftheventterminationis126 thiswouldbe anacceptableinstallation Example C Unacceptable Installation Iftheverticaldimensionfromthefloorofthefireplaceis78 andthe horizontalruntothewallflangeoftheventterminationis108 this would NOT be an acceptable installation Figure 22 H34D Rear Vent Venting Graph Instal...

Страница 12: ...tocombustiblematerials Newtechnology tomeetconsumerandgovernmentdemandsforthe wiseuseofenergy haspromptedustomanufacturemanymodelsof fireplaceswhicharehot fuelandenergyefficient Pleasebeaware temperaturesoverthemantelwillriseabovenormal roomtemperatureandwallsabovefireplacemaybehottotouch Werecommendcarefulconsiderationbegiventotheeffectsofelevated manteltemperatureswhichmaybeinexcessofproductdesi...

Страница 13: ...NOTE If any of the original wire supplied with the appliance is replaced it must be replaced with the same type or its equivalent Figure 26b Wiring schematic for optional fans Figure 26a Wiring for optional fans Removing and Installing the Door Removing the door The door is held in place by a lip on the top of the metal frame and two bucklesatthebottom Releasethebucklesandliftthedoorcarefullyup an...

Страница 14: ...Base log placement Figure 28d Bottom left and right log placement Figure 28e Top left and right log placement Base Log Bottom Left Log Bottom Right Log Top Left Log Top Right Log Base Log Bottom Right Log Bottom Left Log Top Left Log Top Right Log 5 Start the fireplace If the flame appears satisfactory replace the glass door If the flame does not appear satisfactory double check the air inlet and ...

Страница 15: ...odel H34D 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell ga...

Страница 16: ... light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trim 3 Turn the switch on the gas control to Off 4 Flip up the trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Turn sw...

Страница 17: ...ped with an adjustable burner allowing you to raise orlowertheflames Toadjusttheflames locatetheblackknobmarked Hi Lo in the centre of the gas control valve See Figure 29 The front burnersarenotadjustable Toraisetheflameheight turntheblackknob locatedbehindthe lower trim counterclockwise Tolowertheflameheight turnclockwise Figure 29 Hi Lo Adjustment on the H34D s gas valve Cleaning Whenthefireplac...

Страница 18: ... yourlocaldealerorthemanufacturer HONEYWELL SV 9500 SV9600 Troubleshooting Sequence NOTE Before Troubleshooting Familiarize Yourself With The Startup And Checkout Procedure Turn Gas Supply off Set thermostat to call for heat SV9500 SV9600 is powered 24 VAC nominal NO NO NO NO NO YES YES YES YES YES YES YES NO NO NO START Igniter warms up and glows red Pilot Valve opens Turn gas on Pilot Burner lig...

Страница 19: ...ltinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove InnoeventshallThe...

Страница 20: ...ted States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda po...

Страница 21: ...he H34D I equipped with Hot Surface Ignition HSI are not approved for use in mobile or manufac tured homes The H34D MH is rated for NaturalGasat18 000BTU H 5 28Kilowatts max input and 14 000BTU H 4 10Kilowatts min input Propane at 18 000 BTU H 5 28 Kilowatts max input and 14 000 BTU H 4 10Kilowatts min input Conversion Kits TheH34D MHmobilehomeapplianceisfieldconvertiblebetween Natural Gas NG and ...

Страница 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0130 Rev 0 11 2003 ...

Отзывы: