Page 10
H34D Gas Fireplace
Part No. XG0130
Installation
Figure 20.
Extended installation.
Figure 21a.
Corner installation.
Figure 21b.
Flex installation.
Rear Vent Venting Runs
The H34DL Rear Vent has three possible installations which do not
require vertical lift, all of these installations require that you install the
RHS101 heat sheild.
1. Straight Installation.
The height from the hearth to the center of the termination is 27
3/8". H34DL Rear Vent versions are supplied with a 18" extension
pipe (EXT18) with female/female connections. For shorter installa-
tions, cut the EXT18 to the desired length. Refer to figure 20.
For extended installations, use the EXT18 section as supplied for a
18" vent run. Ensure that the RHS101 heat sheild is installed
before attaching the pipe to the termination.
Note:
For Rear Vent models, maximum horizontal run with no
vertical lift must never exceed 18".
2. 45° Corner Installation.
Attach an EEL-45 (45° elbow) directly onto the flue collar. Cut the
EXT-18 to suit, and attach it to the EEL-45. Slide the fireplace into
position and attach to the termination. Ensure that the RHS101
heat sheild is installed before attaching the pipe to the
termination.
3. Corner Installation — 45° or less.
Use an MTO-3 termination and an MFL-1 or MFL-2 (12" or 24"
compressed length) and a frame, if appropriate. Flex may be turned
to obtain desired degree of angle required but must not exceed 45°.
Ensure that the RHS101 heat sheild is installed before
attaching the pipe to the termination.
Figure 19.
Heat Shield. Install by sliding over the vent pipe where it
passes through combustible construction.
Heat Shield
The heat shield (RHS101) must be used on all installations straight
through the wall, at the point where the vent pipe connects to the
termination. With the heat shield, proper vent clearances can be
maintained. The heat shield is not included with the fireplace.
To install the heat shield, slide one section over the vent pipe on the
inside of the wall opening, with the circular portion inside the wall cavity.
Screw the shield in place over the wall opening. Install the second
section on the outside of the wall opening sliding the circular portion into
the wall opening. Refer to Figure 19.