H34D Gas Fireplace

Part No. XG0130

Maintenance

Gas Control Valve

Pilot  Burner Adjustment

1. Locate Pilot Adjustment Screw. (See figure 30.)
2. Adjust pilot screw to provide properly sized flame as shown in

 figure 31).

3. After installing or servicing, leak test with a soap solution with main

burner on. Coat pipe and tubing joints, gasket etc. with soap solution.
Bubbles indicate leaks. Tighten any areas where the bubbles
appear until the bubbling stops completely.

Figure 31. 

Pilot Burner.

Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy Pilot Flame

Locate pilot adjustement screw on

gas control valve. Flame is decreased by
turning adjustment screw clockwise.

Pilot won’t ignite

Disconnect remote wires and try to light
pilot. If pilot now works, remote
connections are faulty. Check wiring
diagram figure

 

30.

Main burner will

1. Check wiring (see figure 30).

not light

2. Check wall switch for proper
connection.

H34D

Troubleshooting

If your fireplace still does not operate correctly, consult your dealer or
the manufacturer.
All service and repairs should be performed by a qualified
agency.
All spare parts, optional fans, and optional trim finishes are available from
your local dealer or the manufacturer.

HONEYWELL SV 9500 /SV9600

Troubleshooting Sequence

NOTE:

Before Troubleshooting, Familiarize Yourself With

The Startup And Checkout Procedure.

· Turn Gas Supply off
· Set thermostat to

call for heat

SV9500/SV9600

is powered
(24 VAC nominal)

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

START

Igniter warms up
and glows red.

Pilot Valve opens.

Turn gas on.
Pilot Burner lights?

Main Valve opens?

SYSTEM OK

Unplug Pilot Burner Cable,

Measure Voltage at

SV9500/SV9600 HSI

Terminals (24 VAC

Nominal, See INSET)

Replace Igniter/

Flame Rod Assembly.

Replace Igniter/
Flame Rod Assembly.

Replace SV9500/SV9600

Measure Voltage to SV9500
/SV9600. Voltage must
be at least 19.5 VAC

Discard old Igniter/
Flame Rod Assembly.

Replace Igniter/Flame
Rod Assembly and retain.
Restart Troubleshooting

Sequence. Does main
valve open?

Replace
SV9500/

SV9600

Check
Transformer

Line Volt
Supply

Replace
SV9500/
SV9600.
Save old
Igniter/Flame

Rod Assembly
for service.

INSET

HSI

Terminals

CHECK:

· Line voltage power

· Low voltage transformer

· Limit Controller

· Thermostat

· Wiring

· Air proving switch on

combustion air blower system

· Vent damper (if used) is open

and end switch made

H34D-I

Figure 30. 

Sit Nova 820 

gas valve

.

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Spill Switch

Содержание H34D

Страница 1: ...ur gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do n...

Страница 2: ...ConsultyourlocalGasInspectionBranchoninstallationrequirementsfor factory builtgasfireplaces Installation repairsshouldbedonebya qualifiedcontractor Installations in Canada must conform to the current CAN CGA B 149 1and 2GasInstallationCodeandlocalregulations Iftheoptional air circulatingfankitisinstalled itmustbeelectricallygroundedin accordance with CSA C22 1 Canadian Electrical Code Part 1 and o...

Страница 3: ...m Corner framing dimensions using a 45 elbow Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framing depth may be reduced to 16 Framing WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Top View Front Vi...

Страница 4: ...cegasconnectionand themainoperatinggasvalveislocatedbehindtheremovabletrimatthe bottomoftheunitandneedonlybeattachedtothegasline withan approved fitting as required by the applicable installation codes Only use gas shut off valves approved for use by the state province region or governing body in which the appliance is being installed or asrequiredbytheapplicableinstallationcodes Flexiblegasconnec...

Страница 5: ...SRframeasshownhere and attachbyscrewingthroughthefourpilotholesinthetermination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensurethatthetwolongmountingbracketsarefacingthebottomof thetermination Seeinset Thiswillprovidemoreheatprotection atthetopofthetermination wheretemperaturesarehighest 2 Attachtothefaceplateoftheterminationusingfoursheetmetalscrews Installing Heat Guards over Terminations Installation Ins...

Страница 6: ...let using5screws asillustratedbelow Figure 7a Flue cap installation for Top Vented fireplace Figure 7b Flue collar installation for Top Vented fireplace Figure 8a Flue cap installation for Rear Vented fireplace Figure 8b Flue collar installation for Rear Vented fireplace H34DL Rear Vent UsethefollowinginstructionstoconvertanH34DLforTopVentuse 1 Installthe4 innerfluecaponthetopflueoutletandsecureth...

Страница 7: ...gcanaffectthefireplace s combustion themaximumverticalventrunforaTopVentedunitis32feet The Venting Graph Measuretheverticalheightfromthefireplacehearthtothecentreofthe terminationandthehorizontalrunfromthefromthefireplacefluecollarto thewallflangeofthetermination PlotontheVentingGraph Fig 9 with an X If the X falls on or above the top boundary of the shaded area the installationisacceptable Exampl...

Страница 8: ... D rigidsectionsmaybeusedinconjunctionwith oneanothertoobtaindifferentpossiblehorizontallengthinstallations Figure 13 ExtendedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select appropriate components Figure 14 RetractedInstallationusingacombinationofsolidandflex venting Use the vent graph to determine your allowable run then select ap...

Страница 9: ...h MEXT 2 24 length MEXT 3 36 length MEXT 4 48 length D Support Ring Plate MSPXT 7 E Firestop FS 7 F Roof Flashing MRF 7 1 12 7 12 pt MRF 12 7 12 12 12 pt Figure 16 Straight vertical venting showing required MXT 10 adaptor supplied with the MVTK 1 termination A maximum of two offsets each offset has two 90 bends may be madeandshallnotexceedtotallengthof25 oftheverticalventheight when measured cente...

Страница 10: ...andattachittotheEEL 45 Slidethefireplaceinto positionandattachtothetermination EnsurethattheRHS101 heat sheild is installed before attaching the pipe to the termination 3 Corner Installation 45 or less Use an MTO 3 termination and an MFL 1 or MFL 2 12 or 24 compressedlength andaframe ifappropriate Flexmaybeturned toobtaindesireddegreeofanglerequiredbutmustnotexceed45 Ensure that the RHS101 heat sh...

Страница 11: ...ceptable Installation Iftheverticaldimensionfromthehearthis94 andthehorizontal runtothewallflangeoftheventterminationis126 thiswouldbe anacceptableinstallation Example C Unacceptable Installation Iftheverticaldimensionfromthefloorofthefireplaceis78 andthe horizontalruntothewallflangeoftheventterminationis108 this would NOT be an acceptable installation Figure 22 H34D Rear Vent Venting Graph Instal...

Страница 12: ...tocombustiblematerials Newtechnology tomeetconsumerandgovernmentdemandsforthe wiseuseofenergy haspromptedustomanufacturemanymodelsof fireplaceswhicharehot fuelandenergyefficient Pleasebeaware temperaturesoverthemantelwillriseabovenormal roomtemperatureandwallsabovefireplacemaybehottotouch Werecommendcarefulconsiderationbegiventotheeffectsofelevated manteltemperatureswhichmaybeinexcessofproductdesi...

Страница 13: ...NOTE If any of the original wire supplied with the appliance is replaced it must be replaced with the same type or its equivalent Figure 26b Wiring schematic for optional fans Figure 26a Wiring for optional fans Removing and Installing the Door Removing the door The door is held in place by a lip on the top of the metal frame and two bucklesatthebottom Releasethebucklesandliftthedoorcarefullyup an...

Страница 14: ...Base log placement Figure 28d Bottom left and right log placement Figure 28e Top left and right log placement Base Log Bottom Left Log Bottom Right Log Top Left Log Top Right Log Base Log Bottom Right Log Bottom Left Log Top Left Log Top Right Log 5 Start the fireplace If the flame appears satisfactory replace the glass door If the flame does not appear satisfactory double check the air inlet and ...

Страница 15: ...odel H34D 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell ga...

Страница 16: ... light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trim 3 Turn the switch on the gas control to Off 4 Flip up the trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Turn sw...

Страница 17: ...ped with an adjustable burner allowing you to raise orlowertheflames Toadjusttheflames locatetheblackknobmarked Hi Lo in the centre of the gas control valve See Figure 29 The front burnersarenotadjustable Toraisetheflameheight turntheblackknob locatedbehindthe lower trim counterclockwise Tolowertheflameheight turnclockwise Figure 29 Hi Lo Adjustment on the H34D s gas valve Cleaning Whenthefireplac...

Страница 18: ... yourlocaldealerorthemanufacturer HONEYWELL SV 9500 SV9600 Troubleshooting Sequence NOTE Before Troubleshooting Familiarize Yourself With The Startup And Checkout Procedure Turn Gas Supply off Set thermostat to call for heat SV9500 SV9600 is powered 24 VAC nominal NO NO NO NO NO YES YES YES YES YES YES YES NO NO NO START Igniter warms up and glows red Pilot Valve opens Turn gas on Pilot Burner lig...

Страница 19: ...ltinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove InnoeventshallThe...

Страница 20: ...ted States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda po...

Страница 21: ...he H34D I equipped with Hot Surface Ignition HSI are not approved for use in mobile or manufac tured homes The H34D MH is rated for NaturalGasat18 000BTU H 5 28Kilowatts max input and 14 000BTU H 4 10Kilowatts min input Propane at 18 000 BTU H 5 28 Kilowatts max input and 14 000 BTU H 4 10Kilowatts min input Conversion Kits TheH34D MHmobilehomeapplianceisfieldconvertiblebetween Natural Gas NG and ...

Страница 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0130 Rev 0 11 2003 ...

Отзывы: