11
Installation
xg0226 - 042220
Co-linear venting into existing masonry chimney
Figure 99.a
Co-linear top vented configuration.
hearth
10'
Min.
30'
Max.
dual 3"
liners
•
Maximum 30 feet vertical pipe
•
Minimum 10 feet vertical
•
restrictor usage recommended for longer vertical runs
• Keep the flexible liner as straight as possible, avoid unnecessary
bending
• A maximum of two certified couplers may be used per length of 3" liner
• DelRay co-linear installation requires reducing from Montigo 4/7
to Duravent 4x6⅝
the appliance can be adapted to co-linear applications using an existing
chimney. The appliance must not be connected to a chimney flue serving
a separate solidfuel burning appliance such as a wood burning fireplace.
the unit must be fully enclosed while maintaining clearances to
combustibles detailed elsewhere in this manual
notice
46dVA-Ad-M1
(Part converts Montigo 4/7 to Duravent 4/6⅝)
46dVA-clAA
(converts duravent direct vent to co-linear)
46DVA-CL33K
(high wind termination)
co-linear
portion of
vent system
may only be
installed within
the fireplace
cavity and
chimney.