Montigo B34DV Скачать руководство пользователя страница 31

B-Series DV-2 Gas Fireplace

Page 31

Part No. XG0160 - 151125

 

                   

                        

Amendment

   

  (Gas Fireplace / Equipment sold in the State of Massachusetts)

 

 

 

 

   5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually 

reset device that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential 

purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery 

back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that 

a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure 

served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified 

licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide 

detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 

thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monox

-

ide detector with an alarm shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height 

of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal

-

lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 

CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted 

by the Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, build

-

ing or structure used in whole or in part for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manu-

facturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the 

equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the 

manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but 

identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all 

parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the 

installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent 

installation shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix B - State of Massachusetts

Содержание B34DV

Страница 1: ...t use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Instal...

Страница 2: ...situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Used to address prac...

Страница 3: ...other than as instructed in this manual Consult your local Gas Inspection Branch on installation requirements for factory built gas fireplaces Installation repairs should be done by a qualified contr...

Страница 4: ...roduction Rating Plate Sample B34 Figure A Rating Plate for B34 Standing Pilot Figure B Rating Plate for B34 Electronic Ignition LBL1205 V6 1 Stand Pilot Screen DEC06 2014 Teklynx LabelView Demo LB122...

Страница 5: ...roduction Rating Plate Sample B38 Figure C Rating Plate for B38 Standing Pilot Figure D Rating Plate for B38 Electronic Ignition LBL1205 V6 1 Stand Pilot Screen DEC06 2014 Teklynx LabelView Demo LB122...

Страница 6: ...ls which are perpendicular to the fireplace opening must not project beyond the area shown in Figure 23 Forprotectionagainstfreezingtemperatures itisrecommendedthatouter walls of the chase be insulate...

Страница 7: ...nnection and the main operating gas valve is located behind the removable trim at the bottom of the unit and need only be attached to the gas line with an approved fitting as required by the applicabl...

Страница 8: ...thetopofthetermination wheretemperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws Installing Heat Guards over Terminations Installing The Remote On Off Wa...

Страница 9: ...is 144 this would NOT be an acceptable installation Figure 8 B34 DV 2 Top Vent Venting Graph B38DV 2 Example A Acceptable Installation If the vertical dimension from the hearth is 84 and the horizont...

Страница 10: ...the centre of the fireplace to outside wall and a minimum of 7 6 when retracted in opposite direction see Figure 11 C flex sections and D rigid sections See table on page 9 may be used in conjunction...

Страница 11: ...or supplied with the MVTK 1 termination Figure 16 Vertical venting with 2 offsets 1 offset two 90 bends 4 7 Venting A Termination MVTK 1 B Stucco Kits MSR Stucco Frame MOSR Stucco Can BSR Brick Can C...

Страница 12: ...th and a frame if appropriate Flex may be turned to obtain desired degree of angle required but must not exceed 45 Figure 17 Extended installation Rear Vent Venting Runs The B Series DV 2 Rear Vent ha...

Страница 13: ...er the venting run will be acceptable Unacceptable venting can affect the fireplace s combustion The Venting Graph Measure the vertical height from the fireplace hearth to the centre of the terminatio...

Страница 14: ...GasAssociationmanteltestrequirements are for fire hazard prevention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufa...

Страница 15: ...Electrical Code ANSI NFPA 70 1987 For more information see the Fan Kit Installation Guide included with the fan kit 115 1 60 Supply G L1 L2 G L2 WH L1 BLK Quick Connect plug to motor NOTE Ifanyoftheor...

Страница 16: ...of the door This condensation will quickly dry however the condensation tends to run down the glass and cause some streaking CPI mode helps to resolve this issue If CPI mode is used during the winter...

Страница 17: ...DV 2 I Honeywell Q3450 Pilot Assembly Pilot Electrical Harness Connector Honeywell Gas Control SV9501M Gas Control Connector Junction Box 115VAC 24VAC 40 VA Transformer Black White Green Gnd Screw Wa...

Страница 18: ...Y 1 8 DWG NO SHEET 1 OF 1 WEIGHT B34DV MAN1 Finish MATERIAL DIMENSIONS ARE IN INCHES TOLERANCES FRACTIONAL 1 32 TWO PLACE DECIMAL 015 THREE PLACE DECIMAL 005 ALL BENDS ARE ASSUMED TO BE 90 UNLESS NOTE...

Страница 19: ...wards the fireplace as far as it will go Close the latches by holding Part B onto the groove at the top of the door and pushing Part A down completely To reinstall screen push the screen back onto the...

Страница 20: ...ainst the back of the log rest Carefully push the log onto the metal spikes on the log rest 4 Place the top logs in position as shown in figure 30a place the centre log down first then the right and l...

Страница 21: ...to the front log rest as shown in figure 30c Center the log from side to side and push it against the back of the log rest Carefully push the log onto the metal spikes on the log rest 4 Placethetoplog...

Страница 22: ...51125 Installation Cautions Q Q If logs are not placed properly excessive sooting will result Q Q The surface of the logs will crack due to the heat of the flames This is a normal occurrence Figure 30...

Страница 23: ...rom PILOT to OFF unless knob is pushed in slightly Do not force Gas Control Knob Shown in Pilot position with American Flame Electronic Ignition For Your Safety READ BEFORE LIGHTING phone Follow the g...

Страница 24: ...you don t smell gas go to the next step 6 Turn fireplace ON using wall switch or remote control 7 If the Fireplace does not light the System will cycle through two trials one minute audible clicking...

Страница 25: ...Wait 5 minutes to clear out any gas If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 5 Turn switch on the gas control to ON NOTE...

Страница 26: ...ht of the gas control valve See Figure 31 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counter clockwise To lower the flame height t...

Страница 27: ...k the Pilot Flame Sensor Rod and clean with steel wool or similar 2 Check the Pilot hood and clean with steel wool if dirty 3 Adjust pilot flame using the pilot adjustment screw if the pilot flame is...

Страница 28: ...Pilot RPA021 RPA021 Burner NG Front Contact local dealer for burner information Burner NG Rear Burner LPG Front Burner LPG Rear Thermocouple RTC182 RTC182 Thermopile RPG001 RPG001 Pilot Tubing RPTA03...

Страница 29: ...use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive tempe...

Страница 30: ...ance 100 000 BTU H 30 KW 12 inches 12 inches M clearance to forced air supply inlet 6 feet 3 feet above air inlet N clearance above paved sidewalk or paved driveway located on public property 7 feet 7...

Страница 31: ...ly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECT...

Страница 32: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0160 150204...

Отзывы: