![Montigo B34DV Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/montigo/b34dv/b34dv_installation-operation-and-maintenance-manual_1830440010.webp)
B-Series DV-2 Gas Fireplace
Page 10
Part No. XG0160 -151125
Installation
PEL
Example 1:
For our shortest venting configuration use components A and E
(see table on
page 9
)
.
Figure 9.
Typical Top Vent installation. If the 90° elbow is
installed directly on the fireplace, for height to the
center of the termination see chart on
page 6
.
Horizontal Venting
Figure 10.
Typical Top Vent installation. The solid sections can
be used in various combinations to obtain the desired vent run.
The vent run
must
fall within the limits set by the venting graph.
90° Elbow
MEXT Section
Termination
Example 2:
Rigid sections and an elbow used in conjunction with 3 ft. flex
section (MFL-3) will, when extended in a five foot chase, allow for
a maximum horizontal run of twelve and one-half feet from the
centre of the fireplace to outside wall and a minimum of 7'6" when
retracted in opposite direction
(see
Figure 11
)
.
"C" flex sections and "D" rigid sections (See table on
page 9
)
may be used in conjunction with one another to obtain different
possible horizontal length installations, Figure 12.
NOTE:
Flex section with no vertical rise must not exceed maximum
horizontal length of 3 feet
(see
Figure 13
)
. Flex runs over 3 feet
must fall within the limits set by the venting graph, and must have
a minimum vertical rise of 3" per foot of flex.
Figure 11.
Extended Installation using a combination of
solid and flex venting. Use the vent graph to determine your
allowable run, then select appropriate components.
Figure 12.
Retracted Installation using a combination of
solid and flex venting. Use the vent graph to determine your
allowable run, then select appropriate components.
Figure 13.
Horizontal flex installation with no vertical rise.
36” max.
Flex Section
Hearth
Termination
Exterior
Wall