background image

61D0006 

23

18

1

/

2

36" 

Note:  SCL  chimney  cap  is  the  same 
as  SC  chimney  cap  except  that  the 
SCL cap is a longer telescoping pipe 
used in special installations (i.e. chase 
installations) 

CHIIMNEY INSTALLATION 

1.  Extend the regular chimney sections until the top of the chimney is 4" 

below the total flue height desired. Do not snap the last section of inlet 

air duct or largest diameter pipe in place until Step 3 is completed.

2.  Remove the shingles from around the chimney so that the flashing 

may be installed. Install the upper part of the flashing under the 

shingles.

3.  Set the flashing on the roof. Scribe a line around the flashing. Cut 

1

/

4

" below the scribed line. This should increase the diameter of the 

flashing outlet enough to allow the flashing to be placed over the 

chimney. 

See Figure 25.

4.  Snap the last section of inlet air duct in place. Slide flashing over the 

chimney. Check for minimum clearances. Adjust chimney if neces-

sary to make minimum clearances. 

5.  Nail the flashing securely in place with eight (8) nails.
6.  Seal crack between top of flashing and chimney with mastic. Leave 

some extra mastic at this area to be used in step 8. 

Be  careful  to  avoid  electrical  shock 
hazard  when  contacting  wires  to  the 
metal chimney components.

CAUTION 

Use  pliers  and  wear  gloves  when 
handling the storm color The edge of 
the storm color is sharp. If you are not 
careful, you could cut your hands.

CAUTION 

CHIMNEY CAP INSTALLATION 

(CONTINUED)

Cut Off 

1

/

4

below Scribed 

Line

Figure 25 - Cutting Off Top of the 

Flashing 

Flashing 

Figure 26 - Installing Storm Collar 

and Chimney Cap 

Model SC 

Chimney Cap 

Apply Mastic 
Here
 

Storm Collar

 

  Flashing 

9.  Place chimney cap into matching parts of the last chimney section. Push chimney cap down until the brackets on the 

bottom of the chimney cap sits on the chimney pipe. Punch or drill 

1

/

8

" diameter holes in the inlet air duct (chimney pipe) 

where specified on the brackets. Fasten chimney pipe down with the No. 8 screws provided. 

Note: Do not penetrate 

the inner stainless steel pipe while installing the screws.

10. Check all the parts of the fireplace, chimney and chimney termination cap. Make sure none have been damaged or bent 

during installation. Check to see that all parts have been properly installed. 

Note: The metal used for chimney cap has a rust-protective coating but the cut edges of the parts are not 

protected. Detergent-wash and paint exposed parts of chimney cap with galvanized primer paint. 
This will prevent rusting and rust staining of nearby structures. 

7.  Place the storm collar around the chimney and put collar 

together like a belt in belt loops. With the loops facing 

up, slide the end of collar under the two loops on the 

other end. Overlap the ends of the collar until it is tight 

against the chimney. Bend the free end of the collar back 

over the loops to hold the storm collar securely together. 

Trim off the excess ends of the storm collar. 

8.  Slide storm collar down snugly against the flashing until 

the excess mastic left in step six is forced up into crack 

between the storm collar and chimney. This will make the 

joint between the flashing and the chimney watertight. 

See Figure 26. 

Содержание 36" and 42" Wood Burning Fireplaces BWB400A

Страница 1: ...INSTALLING SAVE THESE INSTRUCTIONS Only Unvented Gas Log Sets which have been found to comply with the Standard For Unvented Room Heaters ANSI Z21 11 2 are to be installed in this replace A hood must...

Страница 2: ...or years of heating and viewing enjoyment Please take time to read this entire manual before installing or operating your replace LISTING AND CODE APPROVALS The instructions contained in this manual p...

Страница 3: ...rheating Hazardous temperatures to develop on combustible materials adjacent to the replace or chimney The emission of smoke sparks or hazardous gases into the dwelling Leakage of rain water into the...

Страница 4: ...from outside to enter the replace rebox When the replace is not in use the outside combustion air damper should be closed to prevent cold air from entering the rebox An outside combustion air damper i...

Страница 5: ...tions of air leakage in the home Because cold air coming in may be unavoidable in some structures Monessen Hearth Systems is not responsible for heat loss or air in ltration through or around the repl...

Страница 6: ...lid fuel re logs or a certi ed decorative gas appliance may be installed in the replace as described later by this instruction manual The appliance must be properly connected to a venting system PRODU...

Страница 7: ...e replace in a large and open room that is centrally located in the house This will optimize heat circulation and comfort Locate replace away from frequently opened doors central heat outlets or retur...

Страница 8: ...pacers 133 4 Electrical 213 4 Framing Dimension 403 4 Framing Dimension C Framing Dimension B TOP VIEW FRONT VIEW SIDE VIEW BWB400A BWB400CA BWB400IA BWBC400IA BWB500A BWBC500A BWB500IA BWBC500IA Outs...

Страница 9: ...ate poor chimney draft and smoke spillage from the replace open ing into the home Use elbows to offset the chimney to avoid obstructions or to locate the chimney cap in a better location See Chimney O...

Страница 10: ...estopping be used at the ceiling level for chase installation even if local codes do not require restopping Do not insulate chase with blown or ll type insulation Only allow insulation to come into co...

Страница 11: ...If Necessary Metal Safety Strip Must Be Use if Unit Is Placed on Combustible Floor Metal Safety Strip Must Be Use if Unit Is Placed on Combustible Floor Figure 6 Installing Floor Protection Circulatin...

Страница 12: ...xtension materials in place Screw wall ties to the face of the replace Imbed the wall ties in the mortar joints of brick stone or other non combustible materials Place metal safety strip packed with t...

Страница 13: ...mney air space clearance to com bustibles 2 Place replace in the desired location Securely support and level replace Check face of the replace with a carpenter s level If replace is not plumb correct...

Страница 14: ...let Height Roof Flashing Model 612 Firestop Model SF Requires 15 x15 Opening 2 min Air Space to Combustibles Top Spacer Flexible Duct Type FP 4 U Combustion Air Assembly Model AK4 Front to Back Framin...

Страница 15: ...ontact with and possible damage to the chimney Install restop spacers at each ceiling level Install the proper chimney cap or chimney housing on the chimney to prevent the entry of rain and debris int...

Страница 16: ...Combustibles 15 Square Opening in Joist 2 Min Clearance to Combustibles 3 Min and 2 Above Any Point Within 10 Figure 15 Residential Installation Do not install combustible materials below top spacer N...

Страница 17: ...he roof and be seen on the rooftop If the chimney is to penetrate a pitched roof the hole in the roof must be rectangular instead of square and should be sized according to Table 1 INSTALLING FIRESTOP...

Страница 18: ...ress down until the snap locks engage Continue to add chimney sections on top of each other until chimney is at least 6 above roof opening on all sides See Figure 19 Note As the chimney sections are i...

Страница 19: ...y nails per strap Figure 20 Installing Chimney Supports Outer Pipe Flue Support Straps Fasten Securely Firestop Snap Lock Chimney Support Securely to Lower Pipes before Fastening Support Straps Chimne...

Страница 20: ...ustibles SF Firestop Spacer 2 min Air Space Clearance to Combustibles Vertical Chimney Enclosure Support Straps Support Straps Note Two 2 elbows may be used when total installation height is more than...

Страница 21: ...2 151 2 22 36 411 4 471 4 1 1 1 2 0 20 1 0 1 0 0 1 0 1 0 24 28 301 2 503 4 573 4 62 1 1 1 1 0 0 0 1 0 0 0 2 1 1 0 331 2 361 2 391 2 673 4 721 2 771 2 1 1 1 1 0 0 1 0 1 0 1 2 1 1 0 42 451 2 48 82 88 92...

Страница 22: ...23 Chimney Center Line Figure 23 SF30 Firestop Spacer Note If the inclined portion of the chimney passes through a oor or ceiling an SF30 restop spacer should be installed to provide the restop and s...

Страница 23: ...Cutting Off Top of the Flashing Flashing Figure 26 Installing Storm Collar and Chimney Cap Model SC Chimney Cap Apply Mastic Here Storm Collar Flashing 9 Place chimney cap into matching parts of the...

Страница 24: ...nside the hole in the chase cover Lower inlet air telescope down into the mating pipe of the chimney until ange on the telescope section rest on ange of the chase cover overhang Note All telescoping s...

Страница 25: ...when an adequate supply of air is provided by open ventilation 4 Do not take combustion air from attic space or garage space 5 Avoid extremely long runs and numerous turns in the duct leading from th...

Страница 26: ...NUED Figure 31 45 Corner Installation on Slab Floor Figure 30 Installation Above Basement or Crawl Space Do not take combustion air from attic space or garage CAUTION One Wall Inside Room Inside Wall...

Страница 27: ...duct clamp or screws See Figure 33 DO NOT remove the cover if the outside air will not be connected WARNING Figure 32 Attaching Outside Air Starting Collar and Insulation Ring to Left Side of Fireplac...

Страница 28: ...to each duct 3 Place duck clamp over the end of each duct Tighten duct clamp down snuggly 4 Push insulation back into place and over duct clamp Figure 35 Installing Duct Connector 403 Approximately 2...

Страница 29: ...of the replace and appliance to the people who will be operating them and leave all instruction manuals with the operator of the appliance If an unvented gas appliance is installed in the replace the...

Страница 30: ...the gas appliance to the gas pipe according to the appli ance makers instructions 6 Pack insulation around the pipe to prevent air owing through the tube either into or out of the rebox for proper se...

Страница 31: ...See Figure 38 2 Combustible mantel and or trim may be installed within shaded area in Figure 39 Use only non combustible materials below top of spacers and behind front face Note These instructions a...

Страница 32: ...To nd front clearances extend a line from back corner of unit to 4 in front of replace face and 1 outside screened opening Combustible materials may be placed within shaded areas Note Do not let combu...

Страница 33: ...s must be removed to gain access to the side of the replace to install junction box later Note A rectangular switch knockout is provided on the lower right hand face of the replace This replace has be...

Страница 34: ...ur yard Fireplace damper must be fully opened when using a gas appliance WARNING See Gas Appliance Installation for more guidelines HOW TO BUILD A BETTER FIRE The rst three res should be of moderate s...

Страница 35: ...extreme irritation for some people Use hemlock spruce juniper and other resinous woods with caution They contain moisture pockets which upon heating pop with considerable vigor Always use a re screen...

Страница 36: ...utside environmental conditions such as temperature and humidity or changes in the operation of the replace can lead to rapid buildup of soot and or creosote Have a a quali ed and reputable chimney sw...

Страница 37: ...heck the replace for proper adjustment and opera tion before leaving it unattended for long periods of time 13 Do inspect and clean the replace chimney regularly 14 Do keep the re screens closed when...

Страница 38: ...e chim ney 14 Don t neglect to apply caulking or mastic to the required joints of the ashing and between the ashing roof 15 Don t dry clothing or other articles near the replace 16 Don t store or plac...

Страница 39: ...CEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER Item Description QTY 400 Unit 500 Unit 1 Weldment Air Door Rod 1 031867 031867 2 Firescreen Panels 2 61D0001 61D0003 3 Back Firebrick Assembly 1 61D010...

Страница 40: ...for protecting oor against sparks and radiant heat 7 H2066 20 x66 hearth extension for protecting oor against sparks and radiant heat 8 AK4 4 diameter outside combustion air kit allows air from outsi...

Страница 41: ...p LFSQT Square shroud termination chimney cap for chase installation use with S8 telescope pipe and VFK ashing kit Minimum chase top dimensions 26 x26 SPC Pyramid shroud termination chimney cap for ch...

Страница 42: ...42 61D0006 NOTES...

Страница 43: ...61D0006 43 ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE CONSUMER...

Страница 44: ...ct safe operation We do not warrant this replace to be in compliance with your local building code Building codes vary greatly throughout the coun try and you should determine whether your local build...

Отзывы: