FLOOR REQUIREMENTS FOR MODEL SL02
These notes are for your guidance prior to installation.
1.
It is the user
’
s responsibility to provide a satisfactory site area.
2.
The floor should be a single reinforced concrete slab.
Min concrete thickness = 100mm
Min plan dimensions of 3800mm x 2200mm
Prepared base 100mm thickness of quarry rubble compacted to 95%
SL81 reinforcement mesh
Min thickness of concrete above mesh = 65mm
25Mpa concrete
3.
For correct installation of the Scissor Lift Hoist, the floor must be flat and level
at the anchorage points. A level tolerance between bases of 8mm is allowable
and 10mm front to rear. Check with straight edge and spirit level.
4.
Recommended anchor bolts are expansion sleeve type anchors 20mm
diameter with a minimum length of 82mm.
Use the manufacturers recommended installation procedures.
NOTE: Some authorities do not approve expanding type anchorage devices.
5.
If there is any doubt about the quality of the floor, a replacement slab should
be installed. Use a qualified person to design the replacement slab.
6.
No liability for any damages will be accepted should you install the hoist on an
unsuitable floor.
Содержание SL02
Страница 1: ...Page 1 of 22 Rev B Dec 2009 MOLNAR SCISSOR LIFT HOIST SL02 INSTALLATION OPERATION MAINTENANCE MANUAL...
Страница 4: ...Page 4 of 22 Rev B Dec 2009 Model SL02 Complies fully with the Australian Standard 1418 9 1996...
Страница 13: ...Page 13 of 22 Rev B Dec 2009...
Страница 16: ...Page 16 of 22 Rev B Dec 2009 ELECTRICAL DIAGRAM WIRING TO THIS UNIT TO COMPLY WITH AS3000...
Страница 17: ...Page 17 of 22 Rev B Dec 2009 ELECTRONIC DIAGRAM...
Страница 18: ...Page 18 of 22 Rev B Dec 2009 HYDRAULIC DIAGRAM...
Страница 21: ...Page 21 of 22 Rev B Dec 2009...