OPTIONAL 240 VOLT SINGLE PHASE
MINIMUM REQUIREMENTS FOR ELECTRICAL CONNECTION
OF MOLNAR HOISTS
Important: All installations should be carried out by suitably
qualified persons. Failure to comply may void warranty.
The following information is a guide only based on the
latest standards as set out in AS/NZS 3000, for installations
outside of Australia & New Zealand refer to local
standards regulations.
Circuit Breakers should be of "D" curve type (motor start,
high inrush current) - Ratings given as a maximum for
circuit & motor protection based on DOL selection guide.
Voltage operating range: -6% to + 10% of motor
nameplate Voltage.
Motor Voltage 240V Operation range 225V to 264V.
Cable sizes are given as a guide only for a maximum
cable length to 30m. Longest cable runs and in area
where supply voltage is below motor voltage,
Calculation should be made to ensure Voltage Drop will
not fall below minimum operating voltage.
When installed motors must be tested under Full Load checking
Voltage at motor terminals
.
Motor 2.2kW 240V Single-phase model CWC3640F
Full Load Current
12.4 Amps
Min Cable Size
2.5mm 2 core
+
earth
Circuit Breaker
1 phase 32 Amp 10kA
Recommended Clipsal4CB132/10 or equivalent
Содержание SL02
Страница 1: ...Page 1 of 22 Rev B Dec 2009 MOLNAR SCISSOR LIFT HOIST SL02 INSTALLATION OPERATION MAINTENANCE MANUAL...
Страница 4: ...Page 4 of 22 Rev B Dec 2009 Model SL02 Complies fully with the Australian Standard 1418 9 1996...
Страница 13: ...Page 13 of 22 Rev B Dec 2009...
Страница 16: ...Page 16 of 22 Rev B Dec 2009 ELECTRICAL DIAGRAM WIRING TO THIS UNIT TO COMPLY WITH AS3000...
Страница 17: ...Page 17 of 22 Rev B Dec 2009 ELECTRONIC DIAGRAM...
Страница 18: ...Page 18 of 22 Rev B Dec 2009 HYDRAULIC DIAGRAM...
Страница 21: ...Page 21 of 22 Rev B Dec 2009...