No. Parameters
Description
Unit
220 Automatic switching
between summer and
winter time
If the conversion is activated, time adaptation is
performed automatically according to CET guide-
lines
Deactivated=0
Activated=1
Standard: 1
230 Setback difference
temperature
In case of activation of the setback via the external
input
[K]
Standard: 2-0
MVHR control
240 MVHR installation connec-
ted to the system
Control of a mechanical ventilation with heat reco-
very (MVHR) via the Ethernet interface Operation via
the room control units Display.
Deactivated=0
Activated=1
Standard: 0
Dew point sensor
250 Control direction of dew
point sensor input
The control direction of the dew point sensor input
at the base is inverted via room control unit or
parameter file.
normal=0
inverted=1
Standard: 0
Attention!
All user settings will be lost.
¾
If present, remove the microSD Card from the base station and delete the parameter file
“params_usr.bin” at the PC.
¾
Press the rmBUS button of the base station Radio for three seconds in order to start the pair-
ing mode.
9
The LED “Heating zone1” flashes.
¾
Press the rmBUS pushbutton again for a duration of 15 seconds.
9
Now the base station is reset to factory settings and behaves as it did during the first com-
missioning (see section 4).
Note! Previously allocated room control units must be paired newly, see section 4.3.
4.7 Resetting the factory settings
4.8 KWL Smart Home Ready
The MVHR Smart Home Ready allows the control of the ventilation levels of the mechanical ventila-
tion with heat recovery (MVHR) LZG 200/400 via the room control units or via the web interface of
room control unit bases (EZR bases) in stand-alone or master/slave operation.
The following preconditions must be met:
9
The base paired to the MVHR must be operated in stand-alone operation or as master.
9
The base paired to the MVHR must be an Ethernet variant.
9
The EZR and the MVHR must be in the same network.
The steps for performing an implementation of the MVHR in the Alpha 2 EZR system can be taken
from the LZG 200/400 installation and operating instructions.
4.9 Operating lock (hotel function)
Switch-over of the room control unit operating lock between “Standard” and “Restricted opera-
tion” (hotel function). Restricted function is only possible with code-protected operation lock
(parameter 030 = 1) with password (parameter 031). The restricted operation only allows a setting
Содержание BSF 20 Series
Страница 3: ...DEU ENG NDL FRA ITA ESP 3 7 Außerbetriebnahme 24 7 1 Außerbetriebnahme 24 7 2 Entsorgung 24 ...
Страница 27: ...27 DEU ENG NDL FRA ITA ESP 7 Decommissioning 48 7 1 Decommissioning 48 7 2 Disposal 48 ...
Страница 51: ...DEU ENG NDL FRA ITA ESP 51 7 Mise hors service 73 7 1 Mise hors service 73 7 2 Elimination 73 ...
Страница 76: ...DEU ENG NDL FRA ITA ESP 76 7 Buitenbedrijfstelling 97 7 1 Buitenbedrijfstelling 97 7 2 Afvalverwerking 97 ...
Страница 123: ...DEU ENG NDL FRA ITA ESP 123 7 Puesta fuera de servicio 144 7 1 Puesta fuera de servicio 144 7 2 Eliminación 144 ...