41
DEU
ENG
NDL
FRA
ITA
ESP
No. Parameters
Description
Unit
040 External sensor connected
to the RBG
Logging on an additional sensor for the registration
of the floor temperature (Floor sensor), the room
temperature or the dew point
no sensor=0
Dew point sen.=1
Floor sensor=2
Room sensor=3
Standard: 0
060 Correction of actual value
registration
Registration of the actual temperature with a correc-
tion factor
-2.0...+2.0 K
in 0.1 increments
110 Control direction
switching outputs
Switchover of NC and NO actuators (only globally)
NC=0 / NO=1
Standard: 0
115 Use as setback input
Change-over between use of the ECO input for
setback or holiday function of the room control unit.
The holiday function cannot be activated any longer
via the room control unit if this parameter has been
set to 1.
ECO=0
Holiday=1
Standard: 0
120 Unit of temperature
display
Toggle function of the display between degree
Celsius and degree Fahrenheit
°C=0
°F=1
Standard: 0
Pump configuration
130 Pump output
Use the control of a local recirculation pump (in the
heating circuit distributor) or a global recirculation
pump (heating installation).
local=0
global=1
Standard: 0
131 Pump type
Selection of the used pump: Conventional Pump
(KP) / High efficiency Pump (HP)
CP=0
HP=1
Standard: 0
132 Pump turn-on delay
Time elapsing from the moment of the command
from a switching output until the pump is actually
switched on.
[min]
Standard: 2
133 Pump follow-up time
Time elapsing from the moment of switching off
the switching outputs until the pump is actually
switched off.
[min]
Standard: 2
134 Control direction switch-
ing output
The control direction can be inverted if the pump
relay is used as control output
normal=0
inverted=1
Standard: 0
135 Minimum running time
The minimum running time indicates how long the
HP must run until it may be switched off again.
[min]
Standard: 30
136 Minimum standstill time
High efficiency pump: The pump may only be
switched off if a minimum standstill time can be
ensured.
[min]
Standard: 20
Configuration of change-over functionality / boiler relay
140 Function of relay boiler /
CO output
Selection whether the switching output shall serve
for controlling a pump relay, or as CO pilot
Boiler=0
CO pilot=1
Standard: 0
141 Line-up time
Time elapsing from the moment of the command
from a switching output until the boiler relay is actu-
ally switched on.
[min]
Standard: 0
Содержание BSF 20 Series
Страница 3: ...DEU ENG NDL FRA ITA ESP 3 7 Außerbetriebnahme 24 7 1 Außerbetriebnahme 24 7 2 Entsorgung 24 ...
Страница 27: ...27 DEU ENG NDL FRA ITA ESP 7 Decommissioning 48 7 1 Decommissioning 48 7 2 Disposal 48 ...
Страница 51: ...DEU ENG NDL FRA ITA ESP 51 7 Mise hors service 73 7 1 Mise hors service 73 7 2 Elimination 73 ...
Страница 76: ...DEU ENG NDL FRA ITA ESP 76 7 Buitenbedrijfstelling 97 7 1 Buitenbedrijfstelling 97 7 2 Afvalverwerking 97 ...
Страница 123: ...DEU ENG NDL FRA ITA ESP 123 7 Puesta fuera de servicio 144 7 1 Puesta fuera de servicio 144 7 2 Eliminación 144 ...