Function Blocks
40
02/02 AWB27-1300-GB
Description of the outputs
Table 6:
Outputs for dialling the modem
Outputs
Data type
Description
dial_active/
dial_result
BOOL
The outputs indicate the communication between the module
and the modem (initialisation, dialling). A call from the
communication partner is not indicated. This event can be
detected on the “message” output (RING code = 2) and on the
“busy” output (= 1).
dial_dcd
BOOL
Connection is established.
dial_busy
BOOL
1. On dialling:
After signal “1“ has been set on the “dial” input, “dial_busy”
shows “1“ until the connection has been cleared. The reset to
“0“ after the connection has been cleared can be delayed via
“dial_wait_repeat”.
In this way a dial attempt can be prevented or delayed if:
– the communication partner is calling or
– a subsequent station is dialled locally and the country wait
time in the modem has not yet elapsed in the modem
(possible error “DELAYED CALL“ or “BLACK LISTED“).
2. Incoming call
dial_alarm
BOOL
The output is set if a connection cannot be established after the
specified number of attempts. If the “dial_repeat” input is set
to “0”, the “alarm” function block output is only triggered on
error code H2F.
It is reset on “reset”, “dial” = 0, or when a connection has
been established.
dial_message
STRING
Status messages in plain text
a
dial_wait_time
TIME
Remaining time till the next connection attempt.
dial_modem_
code
USINT
a