Telecontrol function
block services
59
02/02 AWB27-1300-GB
Service 20: Read PLC clock – partner station
When performing this service, the clock data for station B,
increased by the “time_adjust” value, is relayed to station A
and output at the “rec_clock” function block output of
station A.
Use it in conjunction with the function block “lock_time”
input and you can define whether station A clock time is to
be synchronised.
“lock_time” = 1:Read PLC clock station B
The clock data of station B is increased by the “time_adjust”
value (of station A) and applied to the “rec_clock” function
block output of station A.
Figure 12: “lock_time” = 1: Read PLC clock station B
“lock_time” = 0:Synchronising to the PLC clock –
partner station
Station B time data is increased by the “time_adjust” value
(of station B). The new time value is output at the
“rec_clock” function block output and overwrites the PLC
clock data of station A.
lock_time:=1
rec_clock
Year
Month
Day
Weekday
Hour
Minute
Second
time_adjust
Station A
Date and time
Station A
Station B
RAM memory
RAM memory