Function Blocks
34
02/02 AWB27-1300-GB
Parameter function block
Description of the inputs
Table 2:
Inputs for dialling the modem
Dial-up prefix (dial_praefix)
The dial-up procedure is defined by the “dial_praefix”
function block input. Check the general specification for the
telephone exchange or network. Also, read about this aspect
in your modem manual.
Inputs
Data
type
Value
range
Description
reset
BOOL
0/1
Sets the dial-up function block and corresponding
telecontrol function block to the basic setting and
initialises the modem.
lock_station
BOOL
0/1
“lock_station” = 1 is used to lock the station from
the services coming from all other stations (except
for service 33). If the station is locked, error code
4B will be displayed.
dial
BOOL
0/1
Setting the “dial” input from 0
r
1 will establish
a connection to the set partner station.
Deactivating the input from 1
r
0 clears the
connection.
sim_pin
STRING
(4)
The PIN number of the (SIM) telephone card must
be entered here as a string. This four-digit number
is loaded into the adapter on power on or module
reset. If the PIN number is loaded retentively, it is
recognised during initialisation.
dial_praefix
STRING
max. 10
characters
Dial-up prefix for the modem,
a
telegramformat
BOOL
0/1
Selection of the telecontrol frame format
0: FT1.2
1: FT3
modem_type
USINT
0 to 6
The initialisation string is sent according to the
modem type (
a