![Moeller S40-AM-TD Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/moeller/s40-am-td/s40-am-td_manual_1819281046.webp)
Parameter function block
43
02/02 AWB27-1300-GB
1) Reset on incoming or outgoing call with DCD = 1.
2) Filled with an empty string on clearing connection.
3) Updated after execution of services 20 and 21.
4) Updated on connection establishment and after execution of
service 31 Read Status.
“dial_modem_code”
,
“dial_message”
During communication between the telecontrol module and
the modem, the modem generates status messages. These
messages are indicated at the “dial_message” function
block output in plain text and at the function block output
“dial_modem_code” as a numerical value.
Table 8:
Messages on the function block outputs
“dial_modem_code” and “dial_message”
dial_modem
Meaning
_code
_message
00
OK, RESET OK
Correct input
01
CONNECT
Data connection xxxxBaud
02
RING
Incoming call
03
NO CARRIER
No or excessively low signal reception level
04
ERROR
Error (Code
a
fail_code)
05
TRANSFER DATA
Data channel ready to send/receive
06
NO DIALTON
No dial tone present
07
BUSY
Busy tone received
08
NO ANSWER
Station not reporting (e.g. no modem)
10
ABORT
No loop current