6.15 TEMPERATURE CALIBRATION
The high quality temperature sensor is digital and calibrated at the factory. For special
applications it is possible to calibrate the sensor and program a correction. The
adjusted temperature will be used in the measurement and reports. For each
temperature sensor a calibration can be entered.
Example: the Mobeye CML2275 measures 13 °C. Actual ambient temperature: 13,5
°C. To adjust this difference, +0,5 degrees shall be programmed.
SMS-command calibration sensor 1:
TOFFSET1:
SMS-command calibration sensor 2:
TOFFSET2:
example: 1111 TOFFSET1:0,5
6.16 ALARM INDICATION
The CML2275 has an internal piezo siren, which sounds at an alarm and keeps
sounding as long as the unit is in alarm status. The siren can be interrupted by briefly
pressing the button. The alarm i
ndication can be disabled, so it won’t sound at all
(OFF). As default this indication is set to ‘ON’.
SMS command alarm indication:
ALARMSOUND:
example:
1111 ALARMSOUND:OFF
6.17 PULSE TIME OUTPUT
The pulse time or switch time of the output is adjustable between 1 and 9999 seconds.
The pulse time indicates how long the output remains switched after a telephone
number sends CODE O1ON (e.g. 1111 O1ON), before it automatically switches back
again. If the pulse time is set to 0 seconds, the output will not automatically switch
back. It may be switched back by SMS command CODE O1OFF. By default, the pulse
time is set to "0" second.
SMS command pulse time output:
TO1:
example:
1111 TO1:45