10
2.6 PROGRAM THRESHOLD VALUES FOR THE INPUTS
A separate high and/or low temperature limit can be set for each temperature sensor.
All limits can be set between -35 and +70 ºC. Negative values are set
by placing a “-”
in front of the value.
To enter a temperature limit, be sure the Mobeye CML2275 is in program mode. Send
an SMS text message to the unit with following content for the first sensor:
SMS command lower limit:
1111 LTL1:
example:
1111 LTL1:-5
SMS command upper limit:
1111 HTL1:
example:
1111 HTL1:25
Similar for the second sensor:
SMS command lower limit:
1111 LTL2:
SMS command upper limit:
1111 HTL2:
Please mind the space behind 1111.
2.7 SWITCHING ON/OFF
After the previous steps, the Mobeye CML2275 is ready for use and switched on
automatically. It can be switched on and off by the user-defined time schemes or the
button on top. By default this button is ‘locked’, to prevent that the unit can be switched
off by mistake. This can be changed by choosing the value “OFF” for the setting
“BUTTONLOCK” (see 6.20). After unlocking the button, the system can be switched
on and off pressing it for one second.
When the unit is switched off, the green LED is off. When the unit is on, the green
LED blinks once every 3 seconds (battery-powered)
or stays ‘on’ continuously (in case
of an external power supply).
In the disarmed status the Mobeye CML2275 will not send alarm notifications. The
functions automatic arming and sending
a ‘low battery’ message, are still active.