6.5.4
Relay Control
A single, no voltage auxiliary relay can be controlled with the above three user settings. Please see
section 2 for more details on how to use this relay settings.
Since there is only one relay, setting more than one option will perform action for all three states. The
typical use for the setting all three is to start a generator when the battery goes low or the load is higher
than is economical to run purely of batteries
The relay will open again once a bulk charge is completed.
6.5.4.1
Warnings
When a battery critical flag is set, the auxiliary relay will be engaged. The battery critical value is
triggered at 1.97 VPC.
6.5.4.2
Solar Sleep
When a high load flag is set, the auxiliary relay will be engaged.
6.5.4.3
Battery Float
When an overload flag is set, the auxiliary relay will be engaged.
6.5.4.4
Battery Critical
The relay closes when the battery reaches a critical voltage level.
NOMAD USER MANUAL
PAGE
25