971 UniMag
™
Operation manual
9
The 971 is as standard supplied with RS232 or RS485 user interface. The user interface allows change of
transducer parameters such as set point settings and calibration.
The serial interface uses the following data format: 8 data bits, 1 stop bit and no parity bit.
RS232 user interface
The 971 is DCE (Data Communication Equipment) and can
be connected to DTE (Data Terminal Equipment), typically a
PC
.
The serial communication does not use hardware handshake.
The RS232 standard does not specify the maximum cable
length, but length depends on environment, cable quality and
communication speed
.
In general cable spans shorter than
15m (50ft.) do not require any extra precautions.
The RS232 connection on transducers delivered with 6 pin Hirschmann and 8 pin RJ45/FCC68 connector is
available at a separate connector. Refer to Accessories and Replacement part number page 35 for RS232
programming cable. The connector is located under the label on the top of the transducer.
RS485 user interface
RS485 is a network communication system that enables the
user to communicate with several units on the same
communication line.
RS485 is a balanced communication system, because signal
on one wire is ideally the exact opposite of the signal on the
second wire. Compared to RS232 communication RS485
allows significantly longer cable span. The maximum length of
cable span depends on the environment, cable quality and communication speed, but relative long cable
spans up to 1,200m (4,000 ft.) is possible.
There are 2 wires other than ground that are used to transmit the digital RS485 signal. The 971 uses half
duplex communication.
Always use high quality shielded data cables for serial communication. For long cable
runs use twisted pairs. See also Accessory and Replacement part number page 35.
The EIA-485 and NMEA standards specification states that signal A is the inverting “-“and signal B is the non
inverting or “+”. This is in conflict with the A/B naming used by a number of differential transceiver
manufacturers which is incorrect, but their practice is used throughout the industry. Therefore care must be
taken when using A/B naming. In addition to the A and B connections, the EIA standard also specifies a third
interconnection point called C, which is the common ground.
At high communication baud rates and when using long cable runs, a termination resistor of typical 120 Ohm
should be connected between pin 1 and 2 at the 971 DSUB connector and between pin A and B at the data
communication equipment. The termination resistors provides low impedance that reduces the sensitivity to
electrical noise and prevents data reflection that can cause data communication corruption.
RS485 twisted pair cable run with 120 Ω terminator resistors (971 with 15 pin connector)
When connecting multiple devices in a RS485 network make sure that proper guidelines and
specifications are followed to ensure optimal communication performance of the 971.
Improper network design can cause data communication interruption and data collision.
Содержание UniMag 971
Страница 1: ...P N 100017131 971 UniMag Transducer Operation and Installation Manual Revision C January 2010...
Страница 36: ...971 UniMag Operation manual 33 mm Inch mm Inch...
Страница 37: ...971 UniMag Operation manual 34 mm Inch...
Страница 40: ...971 UniMag Operation manual 37...
Страница 41: ...971 UniMag Operation manual 38...
Страница 42: ...971 UniMag Operation manual 39...
Страница 44: ...P N 100017133 971 UniMag Transducer Operation and Installation Manual Revision C January 2010...