MKS Device Dependent Messages
Chapter Seven: IEEE-488 Communications Option
122
Trip Point Messages (Continued)
Function
Message
Trip Point Channel
Command
Shortcut command
Query:
Shortcut query:
:control:relay A or B:trip (@ tp chan)
:cont:rela A or B:trip (@ tp chan)
:control:relay A or B:trip?
:cont:rela A or B:trip?
where tp chan equals:
1 for Channel 1
2 for Channel 2
3 for Channel 3
Latch Mode
Command
Shortcut command
Query:
Shortcut query:
:control:relay A or B:latch state
:cont:rela A or B:latch state
:control:relay A or B:latch?
:cont:rela A or B:latch?
where state equals:
enab for enabled
disa for disabled
Table 34: IEEE-488 Trip Point Messages
Example 1: How To Configure the Trip Point A Value
To set the TP A high value to 900, issue the following command:
:control:relay a:high 900
ENTER
Example 2: How To Set the Trip Point Hysteresis
The trip point hysteresis value is defined as a ± percent of the trip point value and can range from
0 to 10%. Refer to How To Adjust the Hysteresis, page 78, for more information.
To change the hysteresis value to 2% for TP B, enter:
:control:relay b:hyst 2
ENTER
Note
The 670 instrument will accept fractional entries with or without the
leading zero. For example, you may enter either “0.1” or “.1” to set the
hysteresis value.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com