IPB-5000A
8. External Interface
8-7
Pin No.
Description
27
COUNT-UP Output Terminal.
The Pin is closed when COUNT-UP reaches the set pre-set count
value. Input Count Reset Signal for releasing the output of COUNT-UP.
The rated capacity of a contact is 24VDC 20mA (Semi-conductor
switch used).
28
READY Output Terminal.
The output manner can be selected at the setting of
READY OUTPUT
in
6.(9)
②
STATUS (2/2)
Screen.
WELD ON
Closed at the time when weld current is ready for being supplied.
Open at WELD OFF or in the occurrence of NG.
POWER ON
Closed in the occasion when the power supply of
IPB-5000A
is
turned on.
The rated capacity of a contact is 24VDC 20mA (Semi-conductor
switch used).
29
COMMON Terminal for Output.
Shared commonly for GOOD, NG, END, CAUTION, COUNT UP and
READY.
30
COMMON Terminal for Output.
Shared commonly for GOOD, NG, END, CAUTION, COUNT UP and
READY.
31
POWER Input Terminal for activating a solenoid valve.
Input the power of 120VAC, 24VAC/ DC.
Note: When an external power supply is used, prepare the power
supply protected by a fuse.
32
Solenoid Valve 1 Output Terminal.
Closed at inputting of 1ST STAGE. The rated capacity of a contact is
120VAC, 24VAC/DC 0.5A (Semi-conductor switch used). Prepare a
solenoid valve with the current capacity of 0.5A or less.
33
Solenoid Valve 2 Output Terminal.
Closed when the sequence works. The rated capacity of a contact is
120VAC, 24VAC/DC 0.5A (Semi-conductor switch used). Prepare a
solenoid valve with the current capacity of 0.5A or less.
34
COM Terminal for Solenoid Valve.
Used for activating a solenoid valve by the use of an internal power
supply.
Internally connected to GND Chassis.
35
Preparatory Input Terminal. (Do not connect here. If it is connected
without the instruction, It may be damaged.)
36
Preparatory Input Terminal. (Do not connect here. If it is connected
without the instruction, It may be damaged.)
37
Preparatory Output Terminal. (Do not connect here. If it is connected
without the instruction, It may be damaged.)
38
Preparatory Output Terminal. (Do not connect here. If it is connected
without the instruction, It may be damaged.)
39
Preparatory Output Terminal. (Do not connect here. If it is connected
without the instruction, It may be damaged.)