SECTION 3
OPERATION
38
b) Automatic
rotation
(*)
after complete blowdown [Rotation
(*)
flag=8]
This function is activated when the rotation
(*)
flag is set to 8 with each MI Terminal MT1-200. Pressing
the “B.BLOW” switch on any MI Terminal MT1-200 under such setting resets the complete blowdown
notification timer. The rotation
(*)
is performed at the same time.
If setting of any priority combustion time after complete blowdown is made, the priority
(*)
is changed
temporarily.
c) Fixing the priority
(*)
of particular boiler [Rotation
(*)
flag=9]
This function is activated when the rotation
(*)
flag is set to 9 with each MI Terminal MT1-200. Under
this setting, the priority
(*)
set with the MI Terminal MT1-200 remains unchanged at automatic rotation
(*)
timing.
Precluding the priority
(*)
that is fixed with this setting, the other MT1-200 units under automatic
rotation
(*)
determine the priority
(*)
.
d) Automatic
rotation
(*)
at intervals of 1 to 12 hours [Rotation
(*)
flag = A to F]
(Option: Only when pressure sensor is installed)
If an optional pressure sensor is installed, the automatic rotation
(*)
can be performed at intervals of 1
to 12 hours by setting the rotation
(*)
flag to an alphabetical character rom A to F with the MI Terminal
MT1-200 of the boiler No.
(*)
1.
If the rotation
(*)
flag is set from A to F without installing an optional pressure sensor, the automatic
rotation
(*)
is performed every day at a specified time.
The following shows operation when an alphabetical character from A to F is set to the rotation
(*)
flag.
Rotation
(*)
flag
setting
Rotation
(*)
Every 1
hour
Rotation
(*)
is performed on the hour.
Every 2
hours
Rotation
(*)
is performed every two hours from 00:00.
(0 o'clock, 2 o'clock, 4 o'clock ..., 20 o'clock, 22 o'clock)
Every 4
hours
Rotation
(*)
is performed every four hours from 00:00.
(0 o'clock, 4 o'clock, 8 o'clock, 12 o'clock, 16 o'clock, 20
o'clock)
Every 6
hours
Rotation
(*)
is performed every six hours from 00:00.
(0 o'clock, 6 o'clock, 12 o'clock, 18 o'clock)
Every 8
hours
Rotation
(*)
is performed every eight hours from 00:00.
(0 o'clock, 8 o'clock, 16 o'clock)
Every 12
hours
Rotation
(*)
is performed every twelve hours from 00:00.
(0 o'clock, 12 o'clock)