1.3 Specifications
1.3.1 Common
Specifications
Applicable boiler
:
Three position step burner HIGH-LOW-OFF
Quantity of boiler under control :
15 units at the maximum
Control pressure
:
Employed
Sensor
(Type)
Working
Pressure Range
MPa
{PSI}
Control Range
MPa
{PSI}
YSK-AC10M-333
0.098 - 0.93
{14 - 136}
0.050 - 0.39
{8 - 56}
YSK-AC20M-334
0.195 - 1.86
{28 – 270}
0.098 - 0.78
{14 – 114}
Control communication
:
Mutual information transmission by two-core (pair)
twisted pair cable
(*)
.
Total interconnection length
:
Maximum 300 m (wiring for MI control
(*)
communication
line)
Control method
:
Combustion unit distribution system by steam header
pressure
Low fire unit ensuring type starting system (for the units
specified)
Low fire priority stop system
Functions :
Automatic
rotation
(*)
function
Complete blowdown immediate prioritized combustion
functions
Abnormal boiler backup functions
Pre-purge backup function
Pressure holding function of each boiler (optional)