2.3 Basic Data Display and Setting Operation
This section describes how to perform setting operation on the basic data display mode.
Press the “SELECT” and “B.BLOW” switches simultaneously to display the basic data display mode.
To go back to the normal display mode, press the “SELECT” and “S.BLOW” switches simultaneously.
Setting can be performed as in same way as normal setting in the following procedures.
1) Press the “SELECT” switch as many times as needed to display the desired setting information.
2) Press the “UP” and “DOWN” switches simultaneously.
(The area that allows setting starts blinking.)
3) Press the “UP” or “DOWN” switch to set the desired value.
4) Press the “SELECT” switch as many times as needed to display the digit to be changed.
Repeat 3). When all the digits are set, the setting is finished with nothing blinking on the display.
The following thirteen items can be set or changed;
Steam pressure setting (high) ................................................. Refer to
P.25.
Differential setting (high) ......................................................... Refer to
P.25.
Steam pressure setting (low) .................................................. Refer to
P.26.
Differential setting (low)........................................................... Refer to
P.26.
Holding-pressure setting ......................................................... Refer to
P.27.
Differential setting (holding) .................................................... Refer to
P.27.
Timer (Sun. through Sat.) ........................................................ Refer to P.28.
Post-fire time ........................................................................... Refer to P.31.
Rotation
(*)
time (only for the boiler No.
(*)
1) .............................. Refer to
P.31.
Rotation
(*)
flag ......................................................................... Refer to
P.32.
Priority combustion time after complete blowdown ................. Refer to
P.32.
Notification time for complete blowdown timing ...................... Refer to
P.32.
Notification time for soot blow timing ....................................... Refer to P.33.
NOTE
The information in the shaded box can be displayed and set only when an optional
pressure sensor is installed on the MI Terminal MT1-200.