SECTION 3
OPERATION
15
1.3 Setting Operation (Control Pressure, Alarm Pressure)
This section offers explanation on setting methods related to header steam pressure.
Perform setting by operating the internal potentiometers with the front panel of the main unit open.
a) Setting of control pressure
Press the “DISPLAY CHANGE” switch to display the “Control
pressure setting”.
Turn the internal potentiometer VR1 to set the maximum steam
pressure value.
b) Setting of control range
Press the “DISPLAY CHANGE” switch to display the “Control range
setting”.
Turn the internal potentiometer VR4 to set a control steam pressure
range.
c) Setting of pressure alarm L
Press the “DISPLAY CHANGE” switch to display the “Pressure
alarm L setting”.
Turn the internal potentiometer VR3 to set a pressure at which low
steam pressure alarm is set off.
d) Setting of pressure alarm H
Press the “DISPLAY CHANGE” switch to display the “Pressure
alarm H setting”.
Turn the internal potentiometer VR2 to set a pressure at which high
steam pressure alarm is set off.