 '12 • SRK-T-122

How to set upper and lower limit of temperature sting range

1.   Stop the air-conditioner, and press          (SET) and          (MODE) button at the same time for

      3 seconds or more.

      The indication changes to"FUNCTION SET    "

2.   Press      button once, and change to the "TEMP RANGE    " indication.

3.   Press         (SET) button, and enter the temperature range setting mode.

4.   Confirm that the "Upper limit      " is shown on the display.

5.   Press         (SET)button to fix.

6.

Indication: "            SET UP"    "UPPER 28

          "

Select the upper limit value 30

 with temperature setting button     ."UPPER30

    "

          (blinking)

Press         (SET) button to fix. "UPPER 30

" (Displayed for two seconds)

          After the fixed upper limit value displayed for two seconds, the indication will returm

          to"UPPER LIMIT     ".

7.   Press      button once,   "LOWER LIMIT      " is selected, press         (SET) button to fix.

Indication: "            SET UP"      "LOWER 20

       "

Select the lower limit value 18

 with temperature setting button     ."LOWER18

    "

          (blinking)

Press         (SET) button to fix. "LOWER 18

" (Displayed for two seconds)

          After the fixed lower limit value displayed for two seconds, the indication will returm

          to"LOWER LIMIT    "

8.  Press  ON/OFF  button to finish.

Connection of wired remote controller

Interface kit(1)

Interface kit(2)

Interface kit(16)

DIP suitch

(SW2-2)

Rotary

switch

Remote controller line (no polarity)

Remote controller line 

(no polarity)

Regarding the connection of wired remote controller, refer to the instruction manual of wired remote controller.

Switch ON the DIP switch SW2-2 (Factory setting : ON) on the interface PCB.

Caution:Wireless remote controller attached to the indoor unit can be used in parallel, after connecting the wired remote controller. However,

                      some of functions other than the basic functions such as RUN/STOP, Temperature Setting, etc. may not work properly and may have

                      a mismatch between the display and the actual behavior.

Wiring connection between the interface and the wired remote controller.

When using the wireless remote controller in parallel with the wired remote controller;

    Temperature setting range should be changed with the wired remote controller (The set temperature may not be displayed correctly on the

    wireless remote controller, unless change of temperature setting range is done.)

    Changing procedure of temperature setting range is as follows.

Clamp the connection cables with cable clamps.

Installation and wiring of wired remote controller

A

Install the wired remote controller with reference to the attached instruction manual of wired remote controller.

B

0.3mm

2

x

 2-core cable should be used for the wiring of wired remote controller.

C

Maximum length of wiring is 600m.

If the length of wiring exceeds 100m, change the size of cable as mentioned below.

100m-200m: 0.5mm

2

x

 2-core, 300m or less: 0.75mm

2

x

 2-core, 400m or less: 1.25mm

2

x

 2-core, 600m or less: 2.0mm

2

x

 2-core

However, cable size connecting to the terminal of wired remote controller should not exceed 0.5mm

2

. Accordingly if the size of connection

cable exceeds 0.5mm

2

, be sure to downsize it to 0.5mm

2

 at the nearest section of the wired remote controller and waterproof treatment should

be done at the connecting section in order to avoid contact failure.

D

Don't use the multi-core cable to avoid malfunction.

E

Keep the wiring of wired remote controller away from grounding (Don't touch it to any metal frame of building, etc.).

F

Connect the connection cables to the terminal blocks of the wired remote controller and the interface securely (no polarity).

Control of multiple units by a single wired remote controller

Multiple units (up to 16) can be controlled by a single wired remote controller.

In this case, all units connected with a single wired remote controller will operate

under the same mode and same setting temperature.

Connect all the interface with 2-core cables of wired remote controller line.

Set the address of indoor unit for remote controller communication from

    "0" to "F" with the rotary switch SW1 on the interface PCB.

After turning the power ON, the address of indoor unit can be displayed by

    pressing  AIR CON  button on the wired remote controller.

    Make sure all indoor units connected are displayed in order by pressing

        or     button. 

Master/Slave setting wired when 2 of wired remote controller are used

Maximum two wired remote controller can be connected to one indoor unit

(or one group of indoor units)

Set the DIP switch SW1 on the wired remote controller to "Slave" for the slave

    remote controller. (Factory setting : Master)

 Caution : Remote controller sensor is invalid.

Remote controller

Adress"0"

Adress"1"

Adress"F"

Remote

controller

"Master"

Remote

controller

"Slave"

Switch

setting

contents

M

Master

remote controller

Slave

remote controller

Wired remote 

controller: SW1

S

Interface kit

6-

7-

8

2

Previous button

It is possible to quit in the middle by

pressing  ON/OFF  button, but the

change of setting is incompleted.

During setting, if pressing

(RESET) button, it returns to the

previous screen.

CHECK

TEST

AIR CON NO.

LOUVER

VENTI

FAN SPEED

SET

RESET

TIEMR

GRILL

MODE

TEMP

ON/OFF

1

3

5

6-

7-

TEMP RANGE

Temperature setting range

Mode

Heating

Other than heating

(Cooling, Fan, Dry, Auto)

Temperature setting range

16-30

18-30

Upper limit

Lower limit 

20-30

16-26

Содержание SRK90CL-BN

Страница 1: ...TECHNICAL MANUAL Manual No 12 SRK T 122 WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONERS Split system air cooled cooling only type SRK90CL BN...

Страница 2: ...ouver control 25 6 3D auto operation 26 4 Custom cord switching procedure 24 3 Auto restart function 2 Unit ON OFF button 24 23 8 Installation location setting 27 10 Outline of automatic operation 28...

Страница 3: ...8 How to read the model name Example SRK 90 C Series code Cooling only type Product capacit Model name SRK Wall mounted type SRC Outdoor unit L 1 Phase 220 240V 50Hz BN 40 11 OPTION PARTS 40 11 1 Inst...

Страница 4: ...tat Operation Display RUN Green TIMER Yellow HI POWER Green ECONO Orange Safety devices Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan...

Страница 5: ...8 Flare 65 Note 1 The model name label is attached on the underside of the panel D C B A E Wireless remote controller Wired Remote controller Option G F Unit mm 60 150 17 3 77 53 5 633 5 703 5 792 15...

Страница 6: ...perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed the unit s height 6 The model name label is attached on t...

Страница 7: ...12 SRK T 122 Unit mm 60 17 3 150 3 Remote controller a Wireless remote controller...

Страница 8: ...ct failure Length Wiring thickness 100 to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board W...

Страница 9: ...WH RD WH BK BL Y BK t TH2 TH3 LM1 LM2 SM1 FMI D S t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 TB 8 2 2 Color Marks Blue Black BK Red BL RD White WH Yellow Green Y G Yello...

Страница 10: ...ONTROL PWB FMo CNTH t t t M CNEEV U EEV CNFAN M 1 M 1 CM CC TO INDOOR UNIT POWER WIRES SIGNAL WIRE BL RD OR MARK BK BLUE ORANGE RED BLACK COLOR COLOR YELLOW GREEN YELLOW Y Y G WH MARK WHITE 52C 52C EL...

Страница 11: ...as mentined below Distance from front side 1m Mike position as below 0 8m 1m Unit Mike position Center Low points 10 20 30 40 50 60 70 Sound Pressure Level dB standard 2 10 5 P a Mid Octave Band freq...

Страница 12: ...Electronic expansion valve Liquid Strainer Capillary tube Outdoor air temp sensor Compressor Accumulator Discharge pipe temp sensor Cooling cycle Check joint Service valve TH3 Humidity sensor Th3 Gas...

Страница 13: ...ng capacity can be obtained in the following way Net capacity Capacity shown on specification Correction factors as follows 1 Coefficient of cooling capacity in relation to temperatures Indoor return...

Страница 14: ...to the one way piping length between the indoor and outdoor units 2 Correction of cooling capacity in relation to one way length of refrigerant piping Piping length m Cooling 7 1 0 10 0 99 15 0 975 20...

Страница 15: ...89 6 54 10 24 6 36 26 7 87 6 12 8 32 6 06 8 86 6 37 9 11 6 32 9 31 6 26 9 74 6 49 10 10 6 29 28 7 66 6 00 8 11 5 95 8 68 6 28 8 94 6 26 9 14 6 19 9 59 6 40 9 95 6 24 30 7 45 5 90 7 90 5 84 8 49 6 19...

Страница 16: ...g rotating equipments hot surfaces or high voltage parts can cause personal injury due to entrapment burn or electric shocks Do not perform any change of protective device itself or its setup conditio...

Страница 17: ...ed Secure a space for installation inspection and maintenance specified in the manual Insufficient space can result in accident such as personal injury due to falling from the installation place Take...

Страница 18: ...and use fire or burst e the ambient sture damage on g operation in air conditioner ain water may pressure status o the room that e In addition into negative artment etc ogen gas after t leakage in th...

Страница 19: ...room lapse into negative nd for the high rise apartment etc ressurizing with nitrogen gas after the event of refrigerant leakage in the can cause serious accidents damaged by getting wet under the or...

Страница 20: ...VOJU PS CPMU BODIPS BOE OVU BODIPS OTUBMMBUJPO CPBSE 4QBDF GPS TFSWJDF 4QBDF GPS TFSWJDF 1JQJOH IPMF 4QBDF GPS TFSWJDF 4QBDF GPS TFSWJDF 1JQJOH GPS BT 1JQJOH GPS JRVJE SBJO IPTF 1JQJOH IPMF SBJO IPTF...

Страница 21: ...JHIFS UIBO TQFDJGJFE 8BWZ 5IF ESBJO IPTF UJQ JT JO UIF HVUUFS 5IF HBQ UP UIF HSPVOE JT DN PS MFTT 0EPS GSPN UIF HVUUFS 5IF ESBJO IPTF UJQ JT JO XBUFS 6OJU NN 5IF P 1PX 5IF 0Q 5IF VMM GUF UIFO FU IF PS...

Страница 22: ...S DPNQMFUJOH WBDVVN PQFSBUJPO DMPTF UIF P IBOEMF GVMMZ BOE TUPQ PQFSBUJPO PG UIF WBDVVN QVNQ UIFO DIFDL UP TFF UIBU UIF WBDVVN HBVHF OFFEMF EPFT OPU SFUVSO FUBDI UIF DIBSHF IPTFT GSPN UIF TFSWJDF QPSU...

Страница 23: ...O 5IF QPXFS TVQQMZ WPMUBHF JT DPSSFDU BT UIF SBUJOH P HBT MFBLT GSPN UIF KPJOUT PG UIF PQFSBUJPOBM WBMWF 1PXFS DBCMFT BOE DSPTTPWFS XJSFT BSF TFDVSFMZ GJYFE UP UIF UFSNJOBM CPBSE 5IF TDSFX PG UIF MJE...

Страница 24: ...ection Unit display section 3D AUTO light green Illuminates during 3D AUTO operation HI POWER light green Illuminates during HIGH POWER operation RUN light green Illuminates during operation Blinks at...

Страница 25: ...on a b 1 2 J170 4 Custom cord switching procedure a Modifying the indoor printed circuit board b Modifying the wireless remote controller 1 2 Cut Function operation mode Indoor temperature setting Fan...

Страница 26: ...ox 45 Approx 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 45 Left Approx 45 Left Approx 20 Le...

Страница 27: ...ng Horizontal blowing Fixed Flap Louver Cooling Up down Swing Center Fixed Wide Fixed Flap Louver Cooling Horizontal blowing Fixed Operation mode Indoor temp Setting temp 2 C At cooling Air flow direc...

Страница 28: ...unit is running press the ON OFF button to stop 2 Press the AIR FLOW UP DOWN button and the AIR FLOW LEFT RIGHT button together for 5 seconds or more 3 Setting the air conditioning installation locati...

Страница 29: ...r air temperature C Outdoor air temperature C b The unit checks the temperature every 30 minutes after the start of operation and if the result of check is not same as the previ ous operation mode cha...

Страница 30: ...300 rpm or under for more than 30 seconds the unit enters first in the stop mode and then stops the entire system TIMER light illuminates simultaneously and the RUN light flashing 6 times at each 8 se...

Страница 31: ...nuously for 15 seconds or longer while operation is stopped an error indication is displayed RUN light 1 time flash TIMER light ON 3 Outdoor heat exchanger temperature sensor 25 C or lower is detected...

Страница 32: ...valve open 3 Troubleshooting procedure If the air conditioner does not run at all If the air conditioner does not run at all diagnose the trouble using the following troubleshooting procedure If the a...

Страница 33: ...32 12 SRK T 122 4 Troubleshooting procedure If the air conditioner runs NO YES 33...

Страница 34: ...onds continuously 3 times within 40 minutes after initial detection of this anomalous temperature The compressor is stopped Broken discharge pipe sensor wire poor connector connection Outdoor main PCB...

Страница 35: ...r making sure the DC fan motor and indoor PCB are normal connect the connectors and confirm that the fan motor is turning If power is turned on while one or the other is broken down it could cause the...

Страница 36: ...22 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 34 main indoor indoo...

Страница 37: ...12 SRK T 122 09 SRK DB 087D Trouble of outdoor unit Insufficient refregerant amount Faulty power transistor Broken compressor wire Service valve close Defective EEV Defective outdoor PCB 1 1 sub main...

Страница 38: ...heck procedure b Outdoor unit Is there voltage between terminal blocks and AC 220 240V Indoor electrical components are normal Is the voltage between terminal blocks and oscillating between DC 0 and 2...

Страница 39: ...er source for outdoor unit Replace fuse Replace indoor PCB Is the fuse burnt out 3 15 A YES YES YES NO NO NO b Indoor unit fan motor check procedure 1 Indoor PCB output check 2 Fan motor resistance ch...

Страница 40: ...39 12 SRK T 122 9 How to make sure of wireless remote controller Measure in this section Operation SW ON The figare below shows the SRK series...

Страница 41: ...or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote controller co terminal block Connect the terminal of remote c with...

Страница 42: ...remote controller cord to the terminal block Connect the terminal of remote controller X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram d...

Страница 43: ...seconds The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER...

Страница 44: ...cation indoor unit temperature is indicated instead of airflow Only the master remote controller can be indicated Heating preparation indication should not be indicated Temperature indication is by de...

Страница 45: ...ase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit...

Страница 46: ...ON SET will be displayed Press SET button Selecct FUNCTION remote controller function or I U FUNCTION indoor unit function Operation message Function description setting description Function No Fixing...

Страница 47: ...an electric shock fire and sersonal injury Warnings Warning Always go along these instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the...

Страница 48: ...y 1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the pu...

Страница 49: ...ection of super link E board Functions of CNT connector Switch ON the DIP switch SW2 2 Factory setting ON on the interface PCB Wiring connection between the interface and the super link E board Clamp...

Страница 50: ...hould be used for the wiring of wired remote controller C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 30...

Страница 51: ...50 12 SRK T 122 11 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control...

Страница 52: ...51 12 SRK T 122...

Страница 53: ...ing Refrigeration Systems 16 5 Konan 2 chome Minato ku Tokyo 108 8215 Japan http www mhi co jp Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the...

Отзывы: