'12 • SRK-T-122
Example : The net cooling capacity of the model SRK90CL-BN with the piping length of 15m, indoor wet-bulb temperature at 19.0
°C
It is necessary to correct the cooling capacity in relation to the one way piping length between the indoor and outdoor units.
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
Piping length [m]
Cooling
7
1.0
10
0.99
15
0.975
20
0.965
25
0.95
How to obtain the cooling capacity
and outdoor dry-bulb temperature 35
°C is Net cooling capacity =
8.30
×
0.975
×
1.0
=
8.10kW
SRK90CL-BN
1Phase 220V
(ISO-T1)
Length 15m
Factor by air
temperatures
.
.