'12 • SRK-T-122
6. RANGE OF USAGE & LIMITATIONS
Selection chart
C
oe
ff
ic
ie
nt
of
co
ol
in
g
ca
pa
ci
ty
in
re
la
tio
n
to
te
m
pe
ra
tu
re
C
oo
lin
g
op
er
at
io
n
O
ut
do
or
ai
rD
.B
.
te
m
pe
ra
tu
re
C
D
.B
.°
1.2
1.3
1.1
1.0
0.9
0.6
0.7
0.8
21
25
30
35
40
45
50
54
Indoor air W.B. temperature °C W.B.
16
18
20
22
24
Applicable range
ISO-T3
Standard Condition
ISO-T1
Standard Condition
Cooling
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following way.
Net capacity = Capacity shown on specification
×
Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
Indoor return air temperature
(Upper, lower limits)
Refrigerant line (one way) length
SRK90CL-BN
Cooling operation: Approximately 21 to 32°C
Cooling operation: Approximately 21 to 54°C
Power source voltage
Rating± 10%
Voltage at starting
Min. 85% of rating
Max. 25m
Max. 15m
Frequency of ON-OFF cycle
Max. 10 times/h
ON and OFF interval
Max. 3 minutes
Outdoor air temperature
(Upper, lower limits)
Vertical height difference between
outdoor unit and indoor unit
Item
Models