 '12 • SRK-T-130

Press         or         button.

Make sure which do you want to set, "     FUNCTION     " 
(remote control function) or "I/U FUNCTION     " (indoor unit 
function).

Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table.

Function No.
Remote controller 

function02
Remote controller 

function06
Remote controller 

function07
Remote controller 

function13

Remote controller 

function15

Default

Model

Indoor unit with only one of air flow setting
Heat pump unit

Exclusive cooling unit

"Auto-RUN" mode selectable indoor unit.
Indoor unit without "Auto-RUN" mode
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting

Item

[Flow of function setting]

Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit. 

But only master indoor unit is received the setting change of indoor unit function “05 EXTERNAL INPUT” and “06 PERMISSION /

PROHIBISHION”.

Indoor unit No. are indicated only when 
plural indoor units are connected.

01

02

Validate setting of ESP:External Static Pressure

Invalidate setting of ESP

Automatical operation is impossible

Temperature setting button is not working

02

03

03

04

04

05

05

06

06

07

07

08

09

08

10

09

11

10

12

11

13

12

13

14

14

15

16

15

17

18

19

Consult the technical data etc. for each control details

Finalize : Press “

” (SET) button.

Reset

: Press “

” (RESET) button.

Select : Press                 button.
End

: Press ON/OFF  button.

It is possible to finish above setting on the way, 
and unfinished change of setting is unavailable.

” : Initial settings

” : Automatic criterion

How to set function

2.

1.

3.

4.

5.

It is possible to finish by pressing  ON/OFF  button on the way, but unfinished change of setting is 

unavailable.
During setting, if you press              (RESET) button, you return to the previous screen.
Setting is memorized in the control and it is saved independently of power failure.

Permission/prohibition control of operation will be valid.

Record and keep the

setting

The functional setting

Stop air-conditioner and press

          (SET) +           (MODE) buttons

at the same time for over three seconds.

Function

setting

Function

setting

Mode button is not working

On/Off button is not working

Fan speed button is not working

Louver button is not working

Timer button is not working

Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro2.0˚C increase in temperature.
Remote thermistor is working, and to be set for pro1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0˚C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0˚C increase in temperature.

If you change the range of set temperature, the indication of set temperature 

will vary following the control.

If you change the range of set temperature, the indication of set temperature

will not vary following the control, and keep the set temperature.

If you change the remote controller function "14                        ", 

you must change the indoor function "04                      " accordingly. 

You can select the louver stop position in the four.

The louver can stop at any position.

In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote controller can be indicated.)

Heating preparation indication should not be indicated.

Temperature indication is by degree C
Temperature indication is by degree F

To set other indoor unit, press

AIRCON

 NO.  button, which 

allows you to go back to the indoor 
unit selection screen 
(for example: I/U 000     ).

ON/OFF  button

(finished)

The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then the indoor unit will be stopped by 
compulsion after 24 hours.
If you change the indoor function "04                           ",
you must change the remote controller function "14                         " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.

With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately. 

To be reset for pro3.0˚C increase in temperature during heating.
To be reset for pro2.0˚C increase in temperature during heating.
To be reset for pro1.0˚C increase in temperature during heating.

To be reset pro2.0˚C increase in return air temperature of indoor unit.
To be reset pro1.5˚C increase in return air temperature of indoor unit.
To be reset pro1.0˚C increase in return air temperature of indoor unit.

To be reset producing -1.0˚C increase in return air temperature of indoor unit.
To be reset producing -1.5˚C increase in return air temperature of indoor unit.
To be reset producing -2.0˚C increase in return air temperature of indoor unit.

When heating thermostat is OFF, fan speed is low speed.
When heating thermostat is OFF, fan speed is set speed.

When heating thermostat is OFF, fan speed is operated intermittently.
When heating thermostat is OFF, the fan is stopped.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set "FAN OFF" when the indoor unit's thermistor is working.

Drain pump is run during cooling and dry.
Drain pump is run during cooling, dry and heating.
Drain pump is run during cooling, dry, heating and fan.
Drain pump is run during cooling, dry and fan.

After cooling is stopped or cooling thermostat is OFF, the fan does not perform extra operation.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for half an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for six hours.

After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for six hours.

During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes 
with low fan speed after five minutes' OFF.

Connected “OA Processing” type indoor unit, and is automatically defined.

Working only with the Single split series.
To control frost prevention, the indoor fan tap is raised. 

Change of indoor heat exchanger temperature to start frost prevention control.

How to check the current setting

When you select  from "No. and funcion" and press set button by the previous operation,  the "Setting" displayed first is the current 
setting.
(But, if you select "ALL UNIT      ", the setting of the lowest number indoor unit is displayed.)

Stop air-conditioner and press              (SET)              (MODE) 
buttons at the same time for over three seconds, and the 
"FUNCTION SET      " will be displayed.

Press              (SET) button.

Selecct "     FUNCTION      "  (remote control function) or "I/U 
FUNCTION     " (indoor unit function).

Operation message
Function description:      , 
setting description:

Function No.

Fixing button

Finishing button

7

2

1

6

Starting button

Previous screen button

Indoor unit selection button

Start

: Stop air-conditioner and press “

” (SET) and

” (MODE) buttons at the same time for over three seconds.

(Remote controller function)

(Indoor unit function)

In case of Single split series, by connecting ventilation device to CNT of the 

indoor printed circuit board (in case of VRF series, by connecting it to CND of the

indoor printed circuit board),  the operation of ventilation device is linked with the 

operation of indoor unit.

In case of Single split series, by connecting ventilation device to CNT of the indoor printed 

circuit board (in case of VRF series, by connecting it to CND of the indoor printed circuit 

board),  you can operate /stop the ventilation device independently by

    (VENT) button.

Press              (SET) button.

6.

"DATA LOADING" (Indication with blinking)

Display is changed to "01                       ".

7.

"DATA LOADING" (Blinking for 2 to 23 seconds to read the data)

(1)

(2)

(3)

Press              (SET) button.

On the occasion of remote control function selection

On the occasion of indoor unit function selection

Press         or         button.
"No. and function"are indicated by turns on the remote control 
function table, then you can select from them.
(For example)

Press         or         button.
Select the setting.

Press         or         button.

Select the setting.

The current setting of selected function is indicated.
(for example) "AUTO RUN ON"       If "02 AUTO RUN SET" is 
selected

Press              (SET) button.

Press              (SET) button.

Press         or         button.

Press         or         button.

Select the number of the indoor unit you are to set
If you select "ALL UNIT      ", you can set the same setting with 
all unites.

Press              (SET) 
"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, Set as the 
same procedure if you want to set continuously ,and if to 
finish, go to 7.

Press   ON/OFF   button.
Setting is finished.

Indication is changed to "02 FAN SPEED SET".
Go to      .

[Note]

If plural indoor units are connected to a remote control,  the 
indication is "I/U 000" (blinking)       The lowest number of the 
indoor unit connected is indicated.

"No. and function" are indicated by turns on the indoor unit function 
table, then you can select from them.
(For example)

The current setting of selected function is indicated.
(For example) "STANDARD"       If "02 FAN SPEED SET" is 
selected.

Press              (SET) button.

"SET COMPLETE" will be indicated, and the setting will be 
completed.
Then after "No. and function" indication returns, set as the same 
procedure if you want to set continuously , and if to finish, go to 7.

Setting

Function No.
Function

When plural indoor units are connected to a remote control, press 
the   AIRCON NO.  button, which allows you to go back to the 
indoor unit selection screen. (example "I/U 000     ")

The initial function setting for typical using is performed automatically by the indoor unit connected, when remote 
controller and indoor unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “

”, set your desired setting as for the selected item.

The procedure of functional setting is shown as the following diagram.

Function No.
Function

Setting

If you input signal into CNT of the indoor printed circuit board from external, the

indoor unit will be operated independently according to the input from external.

If you input into CNT of the indoor printed circuit board from external, all units which 

connect to the same remote controller are operated according to the input from external.

16

17

Airflow of fan becomes the three speed of         -        -        or         -        -        -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan becomes the two speed of         -        .

Airflow of fan is fixed at one speed.

Note2: Fan setting of "HIGH SPEED"

Initial function setting of some indoor unit is "HIGH SPEED".

UH - Hi 

UH - Me

UH - Hi - Me 

STANDARD

HIGH

SPEED1, 2

FAN

SPEED

SET

Hi - Lo

Hi - Me

-

-

-

-

-

-

-

Hi - Me - Lo

UH - UH - Hi - Me

UH - Hi - Me - Lo

Indoor unit air flow setting

Fan tap

PJA012D730

Содержание SRC92ZL-S

Страница 1: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air to air heat pump type SRK92ZL S Manual No 12 SRK T 130...

Страница 2: ...TECHNICAL MANUAL...

Страница 3: ...nnual cooling function 32 4 Custom cord switching procedure 31 3 Auto restart function 2 Unit ON OFF button 31 30 8 Outline of heating operation 34 10 Outline of automatic operation 35 9 Outline of co...

Страница 4: ...r shortcircuit wire breakage on sensor 58 9 Checking the indoor electrical equipment 59 How to read the model name Example SRK 92 Z Series code Inveter type Product capacity Model name SRK Wall mounte...

Страница 5: ...hable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless Remote control Room temperature control...

Страница 6: ...5 Note 1 The model name label is attached on the underside of the panel D C B A E Wireless remote control Wired Remote control Option G F Unit mm 77 53 5 633 5 703 5 792 15 7 7 44 5 44 5 301 8 8 5 50...

Страница 7: ...es of Dimensions installation The height of a wall is 1200mm or less Terminal block 67 9 150 70 50 195 110 50 50 27 50 1300 10 970 55 15 50 195 110 50 41 F Cable draw out hole 30 front 45 side 50 back...

Страница 8: ...12 SRK T 130 3 Remote control a Wireless remote control Unit mm 60 17 3 150...

Страница 9: ...to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cac...

Страница 10: ...BK BL Y Y G BK t Th2 1 Th2 2 Th3 LM 1 LM 2 SM 1 FM I DS t t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 Power source 220 230 240V 50Hz T 8 Color Marks Blue Black BK Red BL R...

Страница 11: ...the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please foll...

Страница 12: ...istance from front side 1m Mike position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike posi...

Страница 13: ...nce from front side 1m Mike position as below 0 8m 1m Unit Mike position Center Low points ISC12092 2 Max value in Hi MODE KF 1EVCXG CPF HTGSWGPE 0 0 0 0 0 0 5QWPF 2TGUUWTG GXGN F UVCPFCTF 2C KF 1EVCX...

Страница 14: ...e position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mik...

Страница 15: ...n as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mike positio...

Страница 16: ...e position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mik...

Страница 17: ...er sensor Electronic expansion valve Liquid Strainer Receiver Strainer Capillary tube Outdoor air temp sensor Muffler Compressor Discharge pipe temp sensor Cooling cycle Heating cycle Check joint 4way...

Страница 18: ...s as follows 0 6 0 7 0 8 0 9 1 0 1 2 1 1 1 3 0 5 10 15 24 26 20 25 30 35 40 46 10 15 20 25 27 Outdoor air W B temperature C W B 15 10 5 0 5 10 15 Cooling operation Outdoor air D B temperature C D B Co...

Страница 19: ...utdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 30 0 935 1 0 Air inlet t...

Страница 20: ...93 6 71 10 45 6 95 10 86 6 78 32 8 01 6 35 8 51 6 31 9 20 6 71 9 51 6 69 9 73 6 62 10 27 6 88 10 68 6 72 34 7 77 6 23 8 27 6 19 8 98 6 61 9 31 6 59 9 52 6 53 10 08 6 82 10 50 6 66 35 7 64 6 17 8 14 6...

Страница 21: ...ommissioning and ensure the space for inspection and maintenance Secure a space for installation inspection and maintenance specified in the manual Insufficient space can result in accident such as pe...

Страница 22: ...nstallation board Sleeve sold separately 6 5 cm minimum from the ceiling In case of rear piping draw out cut off the lower and the right side portions of the sleeve collar Drill a hole with whole core...

Страница 23: ...e arranged by the user and ensure it is thermally insulated CAUTION Wall Gutter Pipe accommodating section Since this air conditioner has been designed to collect dew drops on the rear surface to the...

Страница 24: ...n kit SC BIKN E and fasten the connection harness onto the indoor control box with the clamp supplied with the kit For more details please refer to the user s manual of your Interface connection kit S...

Страница 25: ...naked flames poisonous gas is produced Use the prescribed pipes flare nuts and tools for R410A Using existing parts for R22 or R407C can cause the unit failure and serious accidents due to burst of th...

Страница 26: ...addition just as above so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc Do not install the unit in the locations...

Страница 27: ...in the above When more than one unit are installed side by side provide a 250mm or wider interval between them as a service space In order to facilitate servicing of controllers please provide a suff...

Страница 28: ...eration valve s check joint equipped on the outdoor unit side While conducting a test keep the operation valve shut all the time a Raise the pressure to 0 5MPa and then stop Leave it for five minutes...

Страница 29: ...quired refrigerant charge volume from the following table Since R410A refrigerant must be charged in the liquid phase you should charge it keeping the container cylinder upside down or using a refrige...

Страница 30: ...for the drain elbow and the drain hose 4 ELECTRICAL WIRING WORK For details of electrical cabling refer to the indoor unit installation manual CAUTION Always use an earth leakage circuit breaker desig...

Страница 31: ...tion and then attach the cover securely Improper cover attachment can result in malfunctioning or a failure of the unit if water penetrates into the box Never use a shield cable Power cable indoor out...

Страница 32: ...the air flow left right direction CANCEL button This button cancels the ON timer OFF timer and SLEEP operation ACL switch Switch for resetting microcomputer OFF TIMER button This button selects OFF T...

Страница 33: ...b J170 4 Custom cord switching procedure a Modifying the indoor printed circuit board b Modifying the wireless remote control Cut Function operation mode Indoor temperature setting Fan speed Flap Lou...

Страница 34: ...unit PCB and the dip switch SW2 4 on the interface kit option PCB Note 1 Default states of the jumper wire J172 and the interface kit at the shipping from factory On the PCB the dip switch SW2 4 is se...

Страница 35: ...on 8 Outline of heating operation a Operation of major functional components in heating mode ON OFF ON OFF few minutes ON ON ON HOT KEEP OFF OFF OFF Thermostat ON Thermostat OFF Failure Heating Compre...

Страница 36: ...r operation 8 Outline of heating operation a Operation of major functional components in heating mode b Details of control at each operation mode pattern Fuzzy operation Hot keep operation ON OFF ON O...

Страница 37: ...6 minutes and 50 seconds Heating operation Defrast operation Depends on an operation condition the time can be longer than 7 minutes 2 7 minutes Hot keep operation 09 SRK DB 087D b 27 5 25 5 18 0 18 3...

Страница 38: ...RK92ZL S ULo Upper limit of compressor s command speed 1 Range A As per following table Range B 30 rps Indoor fan 4th speed Hi Me Lo Upper limit of compressor s command speed 1 Range A As per followin...

Страница 39: ...ve Item SRK80ZL S Outdoor air temperature Lower limit speed Model 1 2 1 2 1 2 more or 47 C or more with the compressor running the lower limit The lower limit of compressor command speed is set to 20...

Страница 40: ...F C D OFF Upper limit 50 rps Lower limit 50 rps ON ON Upper limit 52 rps Lower limit 30 rps ON Upper limit 120 rps Lower limit 20 rps Outdoor air temperature C A B 3 7 120 120 2 27 30 25 25 27 27 30 3...

Страница 41: ...peed is reduced to 0 prs a Operating conditions b Detail of operation When the outdoor air temperature TH2 is 11 C or higher continues for 30 seconds while the compressor command speed other than 0 rp...

Страница 42: ...otection Purpose Detail of operation 1 Discharge pipe temperature C 180 180 180 Example Fuzzy 95 105 115 180 180 2 j Current safe Purpose Detail of operation k Current cut Purpose Detail of operation...

Страница 43: ...ions 2 Detail of operation 3 Reset conditions Outdoor temperature 10 C 5 C Outdoor temperature 10 C Outdoor fan Outdoor temperature 5 C a b a b c 40 40 40 40 24 3 3rd 2nd FMo1 2 FMo1 2 2nd FMo1 OFF FM...

Страница 44: ...n turned OFF 2 When the conditions of i above are met the compressor stops Error stop occurs when the compressor has stopped 3 times within 60 minutes 3 When after meeting the conditions of 1 and 2 ab...

Страница 45: ...DB 087D 2 TROUBLESHOOTING PROCEDURES FOR ELECTRICAL EQUIPMENT 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooting procedure If the air conditioner does not run at all Important YES Y...

Страница 46: ...44 12 SRK T 130 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 45 46 52 46 52...

Страница 47: ...f signal transmission If the compressor motor s magnetic pole positions cannot be correctly detected when the compressor starts The air conditioner stops Defective compressor Open phase on compressor...

Страница 48: ...ndoor unit Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoo...

Страница 49: ...21 C 22 C 23 C 24 C 25 C 1 time previous previous time 2 times previous 3 times previous 4 times previous 5 times previous Only for indoor heat exchanger sensor 2 Remote control setting Indicates the...

Страница 50: ...stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by prot...

Страница 51: ...al 38 8 time flash Outdoor unit s fan motor is abnormal 48 8 time flash Current safe 58 8 time flash Connection lines between the indoor and outdoor units are faulty 61 1 time flash Serial transmissio...

Страница 52: ...top 0 1 2 4 3 AUTO DRY COOL FAN HEAT TIMER light Fan speed switching Display pattern when in service mode Fan speed switching when there is an abnormal stop 0 2 3 4 6 7 AUTO HI MED LO HI POWER ECONO R...

Страница 53: ...24 14 4 4 14 24 34 44 54 64 74 84 94 55 45 35 25 15 5 5 15 25 35 45 55 65 75 85 95 56 46 36 26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28...

Страница 54: ...86 106 126 146 48 28 8 8 28 48 68 88 108 128 148 50 30 10 10 30 50 70 90 110 130 150 52 32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 7...

Страница 55: ...53 12 SRK T 130 Service data record form 47...

Страница 56: ...0 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 Temperature C R...

Страница 57: ...lock Compressor wiring short circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload operation compressor lock...

Страница 58: ...56 12 SRK T 130 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 54...

Страница 59: ...age 55 Outdoor fan motor error Defective fan motor connector poor connection defective outdoor PCB See pages 62 for the fan motor and outdoor PCB check pro After making sure the fan motor and outdoor...

Страница 60: ...sensor Cooling Heating Humidity sensor operation Failure mode Control input circuit resding Air conditioning system operation 09 SRK DB 087D 9 Checking the indoor electrical equipment a Indoor PCB ch...

Страница 61: ...5 A YES YES YES NO NO NO b Indoor unit fan motor check procedure i Indoor PCB output check ii Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White B...

Страница 62: ...sor system burns wiring mistakes etc If no problems are found check the output of the power transistor 2 Output inspection procedure Disconnect the terminals for the compresseor If an output such as t...

Страница 63: ...Inspection power transistor Remove the fasten terminal and test output voltage Inspection of outdoor fan motor See page 62 Outdoor unit Check point of outdoor unit Color Color symbol RD Mark Orange O...

Страница 64: ...uring point Resistance when normal b Outdoor unit fan motor check procedure CNFAN1 or CNFAN2 ii Fan motor resistance check Measuring point Resistance when normal Measuring point Resistance when normal...

Страница 65: ...of remote control lower case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control cord terminal blo...

Страница 66: ...terminal block Connect the terminal of remote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direc...

Страница 67: ...The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT...

Страница 68: ...04 accordingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the ma...

Страница 69: ...C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of ind...

Страница 70: ...conditioner and press SET MODE buttons at the same time for over three seconds and the FUNCTION SET will be displayed Press SET button Selecct FUNCTION remote control function or I U FUNCTION indoor...

Страница 71: ...e instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken...

Страница 72: ...1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the pun...

Страница 73: ...external remote control unit procured locally to CNT terminal In case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB When setting operation permission prohibition mode switch...

Страница 74: ...l the wired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of w...

Страница 75: ...73 12 SRK T 130 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control...

Страница 76: ...74 12 SRK T 130...

Страница 77: ...75 12 SRK T 130 PARTS LIST INDOOR UNIT SRK92ZL S OUTDOOR UNIT SRC92ZL S...

Страница 78: ...76 12 SRK T 130 CRAE0240 1 35 41 34 14 14 14 13 18 16 19 14 5 21 20 45 45 46 42 43 32 38 10 11 23 25 12 17 15 27 22 24 26 12 10 33 36 44 39 40 37 7 31 30 28 29 6 4 46 46 4 4 3 9 8 3 2 2 0 0 55...

Страница 79: ...2 1 W K R 5 1 1 1 1 2 16 RKW129A210 BRACKET MOTOR A 1 1 1 1 2 1 K N I L 1 0 2 A 4 4 1 W K R 7 1 1 1 1 2 1 A K N A R C 2 0 2 A 4 4 1 W K R 8 1 1 1 1 2 1 B K N A R C 3 0 2 A 4 4 1 W K R 9 1 1 1 1 2 1 C...

Страница 80: ...No Part No Part Name RE Q 1 R D I L 0 0 4 A 2 3 1 W K R 0 4 1 1 2 4 1 L D I L 1 0 4 A 2 3 1 W K R 1 4 1 1 2 4 42 43 RKW132A403 LID ASSY TERMINAL 1 1 1 2 4 43 RSA011H027 LABEL NOTICE 1 44 RKW129A405 CO...

Страница 81: ...79 12 SRK T 130 MEMO...

Страница 82: ...80 12 SRK T 130 CRAE0258 26 23 28 27 31 24 29 30 12 13 2 7 6 7 7 4 5 14 20 22 21 1 3 11 9 10 8 25 25 15 19 18 17 16 6 10641...

Страница 83: ...RKW142A402 BOX CONTROL R 1 14 RKW132A404 COVER CONTROL R 1 15 RKW142A401 BOX ASSY CONTROL L 1 16 RKW129A407 HOLDER SENSOR 1 17 SSA551A223G SENSOR ASSY 1 1 1 2 4 18 SSA551B017C SENSOR HUMIDITY 1 1 1 2...

Страница 84: ...82 12 SRK T 130 CRBE0347 5 14 15 13 13 15 16 2 3 4 6 12 15 9 10 7 11 15 15 8 1 2 0 55...

Страница 85: ...SERVICE 1 1 1 5 SSA944B031A HANDLE 1 6 RCR124A102 PANEL ASSY TOP 1 7 8 RCR125A101 PANEL ASSY REAR 1 1 1 1 2 8 SSA944B031A HANDLE 1 9 10 PCA142A065F COVER FRONT 1 1 1 1 2 10 S751W25X GROMMET 1 1 1 1 2...

Страница 86: ...84 12 SRK T 130 CRBE0348 5 1 17 6 2 3 16 9 4 18 14 19 10 8 15 7 12 13 61 1 2 11 5 3 6 55...

Страница 87: ...CCUMULATOR ASSY 1 8 PCA381A062C VALVE SERVICE 5 8 1 1 1 1 2 GAS 9 SSA382C068 VALVE S 4WAY 1 20S 10 15 RCR304A109A PIPING ASSY EXPAN 1 1 1 1 2 10 SSA387F065 VALVE BODY EXP 1 1 1 1 2 EEV 11 SSA357A005 S...

Страница 88: ...86 12 SRK T 130 CRBE0349 23 10 5 6 6 5 11 22 21 20 14 18 17 19 16 15 2 1 3 7 8 4 7 8 9 13 12 2 11 0 1 24 5514...

Страница 89: ...9 S751W30X GROMMET 1 35 10 PCA141A096B PLATE BAFFLE 1 11 SSA913D020 SCREW TAP WASHER 10 1 1 1 2 M5 10 12 RCR141A104 PLATE ASSY BAFFLE 1 13 RCR141A107 PLATE ASSY BAFFLE U 1 14 AHT201C264C COMPRESSOR A...

Страница 90: ...88 12 SRK T 130 CRBE0350 CONTROL UNIT 18 15 3 5 6 7 20 7 19 14 13 4 10 9 12 11 1 2 17 16 8 CONTROL PARTS SET...

Страница 91: ...4D173 CORE FERRITE 1 9 RCR504A040 WIRING ASSY 1 PWB2 CNA TB2 1 TB2 2 TB2 3 10 RPC504A917A HARNESS ASSY 1 PWB1 CN20V PWB2 CN20V 11 RCT504A001A HARNESS ASSY 1 PWB2 CNMAIN PWB1 CNSUB 12 RCR504A036A HARNE...

Страница 92: ...VERTER RESIDENTIAL AIR CONDITIONERS Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice...

Отзывы: