Mitsubishi SRC92ZL-S Скачать руководство пользователя страница 24

-

  

-

 '12 • SRK-T-130

• Flaring work

Measurement 

B

Flarin

g

block

Copper pipe

Fini

shing work and fixing

Connection wiring,  Earth wirin

g

Outer tape

Refrigerant piping

Drain hose

Wood screw

Clamp

Cover the exterior portion with outer tape an

d

shape the

 piping so it will match the contours

of the rou

te that the piping to take

.

Also fix the wiring and pipings to the wall with

clamps

.

RKW012A400

Open/close and detachment/attachment of the air inlet panel

 To open, pull the panel at both ends of lower part 

and release latches, then pull up the panel until 

you feel resistance.

(The panel stops at approx. 60

°

 open position

)

 To close, hold the panel at both ends of lower 

part to lower downward and push it slightly until

 

the latch works.

 To remove, pull up the panel to the position 

shown in right illustration and pull it toward you

.

 To install, insert the panel arm into the slot on the 

front panel from the position shown in right 

illustration, hold the panel at both ends of lower

 

part, lower it downward slowly, then push it 

slightly until the latch works.

How to remove and install the front panel

 Uncover 

the 

wireless 

remote 

control, 

and 

mount 

the 

batteries 

[R03 

(AAA, 

Micro), 

×

pieces] 

in 

the 

body 

regularly.

(Fit 

the 

poles 

with 

the 

indication 

marks,

 

 & 

 without 

fail

)

 Conventionally, operate the wireless remote control by holding 

in your hand

.

 Avoid installing it on a clay wall etc.

Cover

CAUTION

Wood screws

ø

3.5 X 16

Wireless remote control

Battery

INSTALLATION OF WIRELESS CONTROL

Mounting method of battery

Fixing to pillar or wall

Do not use new and 

old batteries together.

2

6

5

Open the air inlet panel.

Remove the lid.

Remove the wiring clamp.

Connect the connecting wire securely to the termin

al block.

1) 

Connect the connection wire securely to the ter

minal 

block. If the wire is not affixed completely, conta

ct will be

 

poor, and it is dangerous as the terminal block 

may heat 

up and catch fire

.

2) 

Take care not to confuse the terminal numbers

 for indoor 

and outdoor connections.

Fix the connecting wire by wiring clamp.

Attach the lid.

Close the air inlet panel.

1

2

3

4

5

6

7

ELECTRICAL WIRING WORK

CAUTION

In case of faulty wiring connection, the indoor unit stops, and 

then the run lamp turns on and the timer lamp blinks.

Use cables for interconnection wiring to avoid loosening of the 

wires

.

CENELEC code for cables Required field cables

.

  H05RNR4G1.5 (example) or 245IEC5

7

    H      Harmonized cable type

   05     300/500 volts

    R      Natural-and/or synth, rubber wire insulation

    N      Polychloroprene rubber conductors insulation

    R      Stranded core 

 4or5    Number of conductors

    G      One conductor of the cable is the earth conductor

            (yellow/green

)

   1.5     Section of copper wire (mm

2

)

Preparation of indoor unit

Mounting of connecting wire

s

• Forced cooling operatio

n

Turn on a power supply again after a while after turn of

f a power supply.

Then press continually the ON/OFF button 5 seconds o

r more.

 Install the removed flared nuts to the pipes to be connected, 

then flared the pipes.

 Remove the flared nuts. (on both liquid and gas sides)

Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them

.

CONNECTION OF REFRIGERANT PIPINGS

Preparation

(Do not turn

)

Press

Remove

A

90 

±

 0.5˚

Dimension 

A

Liquid side 

ø6.35 : 

9.1 (mm

)

Gas side   

 ø

9.52 : 13.2 (mm

)

   

ø12.7 : 16.6 (mm

)

ø15.88 : 19.7 (mm

)

CAUTION

Do not apply refrigerating machine

 

oil to the flared surface.

Indoor

Copper pipe diameter

Use a flare tool designed for R410A or a conventional flare tool.

Please note that measurement B (protrusion from the flaring block) will vary depending on the 

type of a flare tool in use

.

If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to

 

check protrusion so that you can keep measurement B to a correct value.

Clutch type flare tool for

R410A                          

 

Conventional (R22) flare tool

ø6.35

ø9.52

ø15.8

8

0.0 - 0.5

0.0 - 0.5

0.0 - 0.5

1.0 - 1.5

1.0 - 1.5

1.0 - 1.5

1.5 - 2.

0

1.5 - 2.

0

2.0 - 2.

5

ø12.7

0.0 - 0.5

1.0 - 1.5

2.0 - 2.

5

Measurement B (mm)

Clutch type

Wing nut type

CAUTION

Do not apply excess torque to the flared nuts. 

Otherwise, the flared nuts may check depending

.

 Arrange the drain hose in a downward angle.

 Avoid the following drain piping.

 Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor

.

 When the extended drain hose is indoor, always use a shield pipe (to be arranged by the user) and ensure it is 

thermally insulated.

CAUTION

Wal

l

Gutter

Pipe accommodating sectio

n

Since this air conditioner has been designed to collect dew drops on the rear 

surface to the drain pan, do not attach the power cord above the gutter.

Drainag

e

Go through all installation steps and check if the 

drainage is all right. Otherwise water leak may occur

.

Higher than specified

The drain hose tip is in water

.

Wavy

The drain hose tip is in the gutter

.

The gap to the ground is 5 cm or less.

Odor from the gutter

Shield pipe

Drain hose

Extended drain hose

When it is exposed indoor

.

2

1

Installation Step

s

Pass the pipe through

the hole in the wall,

and hook the upper

part of the indoor unit

to the installation board

.

Gently push the lower

part to secure the unit.

• How to remove the indoor unit from the installation board

Fixing of indoor unit

Push up at the marked portion of the indoor unit base lower latch, and slightly 

pull it toward you. (both right and left hand sides) (The indoor unit base lower 

latch can be removed from the installation board)

Push up the indoor unit upward. So the indoor unit will be removed from the 

installation board.

1

2

The marked portion of the indoor unit base lower latch

.

Installation boar

d

Indoor unit base latch

W

all

CONCERNING TERMINAL CONNECTION FOR AN INTERFAC

E

Remove the air inlet panel, lid and front panel.

Remove the control cover. (Remove the screw.

)

There is a terminal (respectively marked with CNS) for the indoor control board.

In connecting an interface, connect to the respective terminal securely with the connection harness 

supplied with an optional 

“Interface connection kit SC-BIKN-E

” and fasten the connection harness

 

onto the indoor control box with the clamp supplied with the kit.

For more details, please refer to the user

’s manual of your 

“Interface connection kit SC-BIKN-E

”.

1

2

3

INSTALLATION TEST CHECK POINT

S

After installation

The power supply voltage is correct as the rating.

No gas leaks from the joints of the operation valve

.

Power cables and crossover wires are securely fixed to the terminal board

.

Operation valve is fully open.

The pipe joints for indoor and outdoor pipes have been insulated.

Air conditioning operation is normal

.

No abnormal noise

.

Water drains smoothly.

Protective functions are not working.

The remote control is normal.

Operation of the unit has been explained to the customer. 

(Three-minutes restart preventive timer

)

When the air conditioner is restarted or when changing the operation, the uni

t

will not start operating for approximately 3 minutes

.

This is to protect the unit and it is not a malfunction.

Test ru

n

Check the following points again after completion of the installation, and before turning on the power. Conduct a test run agai

n and ensure that the unit operates properly

.

At the same time, explain to the customer how to use the unit and how to take care of the unit following the user

’s manual.

 Connect the pipes on both liquid and gas sides

.

 Tighten the nuts to the following torque.

Liquid side 

6.35) : 14.0 - 18.0 

N

·m (1.4 - 1.8 kg

f·m)

Gas side    

9.52) : 34.0 - 42.0 

N

·m (3.4 - 4.2 kg

f·m)

    

12.7) : 49.0 - 61.0 

N

·m (4.9 - 6.1 kg

f·m)

  (

ø15.88) : 68.0 - 82.0 

N

·m (6.8 - 8.2 kg

f·m)

Connection

Insulation of the connection portion

Indoor

Liquid side Gas side

(Do not turn

)

• Cover the indoor unit s flare-connected joints, after they are checked for a gas leak, 

with an indoor unit heat insulating material and then wrap them with a tape with an 

attached insulation pad placed over the heat insulating material

’s slit area

.

Cover the coupling with insulator and then cover it with tapes.

Vinyl tape

Use an attached insulation pad for heat insulation

.

Position it so that the slit area faces upward

.

Filter 

holde

r

Air-cleanin

g

filte

r

To

 remove / 

To

 install

Installing the air-cleaning filters

1.  Open the air inlet panel and remove the air filters

.

2.  Install the filter holders, with the air-cleaning filters installed in the holders

.

In the air conditioner

.

• Each air-cleaning filter can be installed in the left or right filter holder

.

3.  Install the air filters and close the inlet panel.

Connect charge hose to check joint of outdoor unit

.

Liquid side : Close the liquid valve with hexagon wren

ch key.

Gas side : Fully open the gas valve

.

Carry out cooling operation. (If indoor temperature is 

low, operate

 

forced cooling operation.)

After low pressure gauge become 0.01MPa, stop cool

ing operation

 

and close the gas valve.

1

2

3

<How to pump down>

 In order to protect the environment, be sure to pump down (recovery of refrigerant).

 Pump down is the method of recovering refrigerant from the indoor unit to the 

outdoor unit when the pipes are removed from the unit.

HOW TO RELOCATE OR DISPOSE OF THE UNIT

Unit ON/OFF button

Indoor unit PC

B

Scre

w

C

N

S

 te

rm

inal

Control cover

Installation board

Indoor unit

Latch (2 locations

)

Removing

① 

Remove 

the 

air 

inlet 

panel.

② 

Remove 

the 

screw 

(A) 

2pcs 

/ screw 

(B) 

3pcs 

fixing 

to 

the 

front 

panel.

③ 

Remove 

the 

latches 

in 

the 

upper 

section 

of 

the 

front 

panel 

and 

then 

remove 

the 

front 

panel 

from 

the 

unit

.

Installing

① 

Remove 

the 

air 

filter.

② 

Cover 

the 

unit 

with 

the 

front 

panel.

③ 

Tighten 

the 

screw 

(A) 

2pcs 

/ screw 

(B) 

3pcs 

to 

fix 

the 

front 

panel.

④ 

Install 

the 

air 

filter.

 

⑤ 

Install 

the 

air 

inlet 

panel.

Front pane

l

Air inlet pane

l

Air filter

Latc

h

Screw (A

)

Screw (A

)

Screw (B

)

Screw (B

)

Screw (B

)

Te

rminal block

1

3

2N

Li

d

Wiring Clam

p

Approx. 80

°

Содержание SRC92ZL-S

Страница 1: ...RESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air to air heat pump type SRK92ZL S Manual No 12 SRK T 130...

Страница 2: ...TECHNICAL MANUAL...

Страница 3: ...nnual cooling function 32 4 Custom cord switching procedure 31 3 Auto restart function 2 Unit ON OFF button 31 30 8 Outline of heating operation 34 10 Outline of automatic operation 35 9 Outline of co...

Страница 4: ...r shortcircuit wire breakage on sensor 58 9 Checking the indoor electrical equipment 59 How to read the model name Example SRK 92 Z Series code Inveter type Product capacity Model name SRK Wall mounte...

Страница 5: ...hable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless Remote control Room temperature control...

Страница 6: ...5 Note 1 The model name label is attached on the underside of the panel D C B A E Wireless remote control Wired Remote control Option G F Unit mm 77 53 5 633 5 703 5 792 15 7 7 44 5 44 5 301 8 8 5 50...

Страница 7: ...es of Dimensions installation The height of a wall is 1200mm or less Terminal block 67 9 150 70 50 195 110 50 50 27 50 1300 10 970 55 15 50 195 110 50 41 F Cable draw out hole 30 front 45 side 50 back...

Страница 8: ...12 SRK T 130 3 Remote control a Wireless remote control Unit mm 60 17 3 150...

Страница 9: ...to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cac...

Страница 10: ...BK BL Y Y G BK t Th2 1 Th2 2 Th3 LM 1 LM 2 SM 1 FM I DS t t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 Power source 220 230 240V 50Hz T 8 Color Marks Blue Black BK Red BL R...

Страница 11: ...the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please foll...

Страница 12: ...istance from front side 1m Mike position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike posi...

Страница 13: ...nce from front side 1m Mike position as below 0 8m 1m Unit Mike position Center Low points ISC12092 2 Max value in Hi MODE KF 1EVCXG CPF HTGSWGPE 0 0 0 0 0 0 5QWPF 2TGUUWTG GXGN F UVCPFCTF 2C KF 1EVCX...

Страница 14: ...e position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mik...

Страница 15: ...n as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mike positio...

Страница 16: ...e position as below 0 8m 1m Unit Mike position Center Low points Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position as below 0 8m 1m Unit Mik...

Страница 17: ...er sensor Electronic expansion valve Liquid Strainer Receiver Strainer Capillary tube Outdoor air temp sensor Muffler Compressor Discharge pipe temp sensor Cooling cycle Heating cycle Check joint 4way...

Страница 18: ...s as follows 0 6 0 7 0 8 0 9 1 0 1 2 1 1 1 3 0 5 10 15 24 26 20 25 30 35 40 46 10 15 20 25 27 Outdoor air W B temperature C W B 15 10 5 0 5 10 15 Cooling operation Outdoor air D B temperature C D B Co...

Страница 19: ...utdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 30 0 935 1 0 Air inlet t...

Страница 20: ...93 6 71 10 45 6 95 10 86 6 78 32 8 01 6 35 8 51 6 31 9 20 6 71 9 51 6 69 9 73 6 62 10 27 6 88 10 68 6 72 34 7 77 6 23 8 27 6 19 8 98 6 61 9 31 6 59 9 52 6 53 10 08 6 82 10 50 6 66 35 7 64 6 17 8 14 6...

Страница 21: ...ommissioning and ensure the space for inspection and maintenance Secure a space for installation inspection and maintenance specified in the manual Insufficient space can result in accident such as pe...

Страница 22: ...nstallation board Sleeve sold separately 6 5 cm minimum from the ceiling In case of rear piping draw out cut off the lower and the right side portions of the sleeve collar Drill a hole with whole core...

Страница 23: ...e arranged by the user and ensure it is thermally insulated CAUTION Wall Gutter Pipe accommodating section Since this air conditioner has been designed to collect dew drops on the rear surface to the...

Страница 24: ...n kit SC BIKN E and fasten the connection harness onto the indoor control box with the clamp supplied with the kit For more details please refer to the user s manual of your Interface connection kit S...

Страница 25: ...naked flames poisonous gas is produced Use the prescribed pipes flare nuts and tools for R410A Using existing parts for R22 or R407C can cause the unit failure and serious accidents due to burst of th...

Страница 26: ...addition just as above so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc Do not install the unit in the locations...

Страница 27: ...in the above When more than one unit are installed side by side provide a 250mm or wider interval between them as a service space In order to facilitate servicing of controllers please provide a suff...

Страница 28: ...eration valve s check joint equipped on the outdoor unit side While conducting a test keep the operation valve shut all the time a Raise the pressure to 0 5MPa and then stop Leave it for five minutes...

Страница 29: ...quired refrigerant charge volume from the following table Since R410A refrigerant must be charged in the liquid phase you should charge it keeping the container cylinder upside down or using a refrige...

Страница 30: ...for the drain elbow and the drain hose 4 ELECTRICAL WIRING WORK For details of electrical cabling refer to the indoor unit installation manual CAUTION Always use an earth leakage circuit breaker desig...

Страница 31: ...tion and then attach the cover securely Improper cover attachment can result in malfunctioning or a failure of the unit if water penetrates into the box Never use a shield cable Power cable indoor out...

Страница 32: ...the air flow left right direction CANCEL button This button cancels the ON timer OFF timer and SLEEP operation ACL switch Switch for resetting microcomputer OFF TIMER button This button selects OFF T...

Страница 33: ...b J170 4 Custom cord switching procedure a Modifying the indoor printed circuit board b Modifying the wireless remote control Cut Function operation mode Indoor temperature setting Fan speed Flap Lou...

Страница 34: ...unit PCB and the dip switch SW2 4 on the interface kit option PCB Note 1 Default states of the jumper wire J172 and the interface kit at the shipping from factory On the PCB the dip switch SW2 4 is se...

Страница 35: ...on 8 Outline of heating operation a Operation of major functional components in heating mode ON OFF ON OFF few minutes ON ON ON HOT KEEP OFF OFF OFF Thermostat ON Thermostat OFF Failure Heating Compre...

Страница 36: ...r operation 8 Outline of heating operation a Operation of major functional components in heating mode b Details of control at each operation mode pattern Fuzzy operation Hot keep operation ON OFF ON O...

Страница 37: ...6 minutes and 50 seconds Heating operation Defrast operation Depends on an operation condition the time can be longer than 7 minutes 2 7 minutes Hot keep operation 09 SRK DB 087D b 27 5 25 5 18 0 18 3...

Страница 38: ...RK92ZL S ULo Upper limit of compressor s command speed 1 Range A As per following table Range B 30 rps Indoor fan 4th speed Hi Me Lo Upper limit of compressor s command speed 1 Range A As per followin...

Страница 39: ...ve Item SRK80ZL S Outdoor air temperature Lower limit speed Model 1 2 1 2 1 2 more or 47 C or more with the compressor running the lower limit The lower limit of compressor command speed is set to 20...

Страница 40: ...F C D OFF Upper limit 50 rps Lower limit 50 rps ON ON Upper limit 52 rps Lower limit 30 rps ON Upper limit 120 rps Lower limit 20 rps Outdoor air temperature C A B 3 7 120 120 2 27 30 25 25 27 27 30 3...

Страница 41: ...peed is reduced to 0 prs a Operating conditions b Detail of operation When the outdoor air temperature TH2 is 11 C or higher continues for 30 seconds while the compressor command speed other than 0 rp...

Страница 42: ...otection Purpose Detail of operation 1 Discharge pipe temperature C 180 180 180 Example Fuzzy 95 105 115 180 180 2 j Current safe Purpose Detail of operation k Current cut Purpose Detail of operation...

Страница 43: ...ions 2 Detail of operation 3 Reset conditions Outdoor temperature 10 C 5 C Outdoor temperature 10 C Outdoor fan Outdoor temperature 5 C a b a b c 40 40 40 40 24 3 3rd 2nd FMo1 2 FMo1 2 2nd FMo1 OFF FM...

Страница 44: ...n turned OFF 2 When the conditions of i above are met the compressor stops Error stop occurs when the compressor has stopped 3 times within 60 minutes 3 When after meeting the conditions of 1 and 2 ab...

Страница 45: ...DB 087D 2 TROUBLESHOOTING PROCEDURES FOR ELECTRICAL EQUIPMENT 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooting procedure If the air conditioner does not run at all Important YES Y...

Страница 46: ...44 12 SRK T 130 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 45 46 52 46 52...

Страница 47: ...f signal transmission If the compressor motor s magnetic pole positions cannot be correctly detected when the compressor starts The air conditioner stops Defective compressor Open phase on compressor...

Страница 48: ...ndoor unit Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoo...

Страница 49: ...21 C 22 C 23 C 24 C 25 C 1 time previous previous time 2 times previous 3 times previous 4 times previous 5 times previous Only for indoor heat exchanger sensor 2 Remote control setting Indicates the...

Страница 50: ...stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by prot...

Страница 51: ...al 38 8 time flash Outdoor unit s fan motor is abnormal 48 8 time flash Current safe 58 8 time flash Connection lines between the indoor and outdoor units are faulty 61 1 time flash Serial transmissio...

Страница 52: ...top 0 1 2 4 3 AUTO DRY COOL FAN HEAT TIMER light Fan speed switching Display pattern when in service mode Fan speed switching when there is an abnormal stop 0 2 3 4 6 7 AUTO HI MED LO HI POWER ECONO R...

Страница 53: ...24 14 4 4 14 24 34 44 54 64 74 84 94 55 45 35 25 15 5 5 15 25 35 45 55 65 75 85 95 56 46 36 26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28...

Страница 54: ...86 106 126 146 48 28 8 8 28 48 68 88 108 128 148 50 30 10 10 30 50 70 90 110 130 150 52 32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 7...

Страница 55: ...53 12 SRK T 130 Service data record form 47...

Страница 56: ...0 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 Temperature C R...

Страница 57: ...lock Compressor wiring short circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload operation compressor lock...

Страница 58: ...56 12 SRK T 130 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 54...

Страница 59: ...age 55 Outdoor fan motor error Defective fan motor connector poor connection defective outdoor PCB See pages 62 for the fan motor and outdoor PCB check pro After making sure the fan motor and outdoor...

Страница 60: ...sensor Cooling Heating Humidity sensor operation Failure mode Control input circuit resding Air conditioning system operation 09 SRK DB 087D 9 Checking the indoor electrical equipment a Indoor PCB ch...

Страница 61: ...5 A YES YES YES NO NO NO b Indoor unit fan motor check procedure i Indoor PCB output check ii Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White B...

Страница 62: ...sor system burns wiring mistakes etc If no problems are found check the output of the power transistor 2 Output inspection procedure Disconnect the terminals for the compresseor If an output such as t...

Страница 63: ...Inspection power transistor Remove the fasten terminal and test output voltage Inspection of outdoor fan motor See page 62 Outdoor unit Check point of outdoor unit Color Color symbol RD Mark Orange O...

Страница 64: ...uring point Resistance when normal b Outdoor unit fan motor check procedure CNFAN1 or CNFAN2 ii Fan motor resistance check Measuring point Resistance when normal Measuring point Resistance when normal...

Страница 65: ...of remote control lower case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control cord terminal blo...

Страница 66: ...terminal block Connect the terminal of remote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direc...

Страница 67: ...The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT...

Страница 68: ...04 accordingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the ma...

Страница 69: ...C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of ind...

Страница 70: ...conditioner and press SET MODE buttons at the same time for over three seconds and the FUNCTION SET will be displayed Press SET button Selecct FUNCTION remote control function or I U FUNCTION indoor...

Страница 71: ...e instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken...

Страница 72: ...1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the pun...

Страница 73: ...external remote control unit procured locally to CNT terminal In case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB When setting operation permission prohibition mode switch...

Страница 74: ...l the wired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of w...

Страница 75: ...73 12 SRK T 130 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control...

Страница 76: ...74 12 SRK T 130...

Страница 77: ...75 12 SRK T 130 PARTS LIST INDOOR UNIT SRK92ZL S OUTDOOR UNIT SRC92ZL S...

Страница 78: ...76 12 SRK T 130 CRAE0240 1 35 41 34 14 14 14 13 18 16 19 14 5 21 20 45 45 46 42 43 32 38 10 11 23 25 12 17 15 27 22 24 26 12 10 33 36 44 39 40 37 7 31 30 28 29 6 4 46 46 4 4 3 9 8 3 2 2 0 0 55...

Страница 79: ...2 1 W K R 5 1 1 1 1 2 16 RKW129A210 BRACKET MOTOR A 1 1 1 1 2 1 K N I L 1 0 2 A 4 4 1 W K R 7 1 1 1 1 2 1 A K N A R C 2 0 2 A 4 4 1 W K R 8 1 1 1 1 2 1 B K N A R C 3 0 2 A 4 4 1 W K R 9 1 1 1 1 2 1 C...

Страница 80: ...No Part No Part Name RE Q 1 R D I L 0 0 4 A 2 3 1 W K R 0 4 1 1 2 4 1 L D I L 1 0 4 A 2 3 1 W K R 1 4 1 1 2 4 42 43 RKW132A403 LID ASSY TERMINAL 1 1 1 2 4 43 RSA011H027 LABEL NOTICE 1 44 RKW129A405 CO...

Страница 81: ...79 12 SRK T 130 MEMO...

Страница 82: ...80 12 SRK T 130 CRAE0258 26 23 28 27 31 24 29 30 12 13 2 7 6 7 7 4 5 14 20 22 21 1 3 11 9 10 8 25 25 15 19 18 17 16 6 10641...

Страница 83: ...RKW142A402 BOX CONTROL R 1 14 RKW132A404 COVER CONTROL R 1 15 RKW142A401 BOX ASSY CONTROL L 1 16 RKW129A407 HOLDER SENSOR 1 17 SSA551A223G SENSOR ASSY 1 1 1 2 4 18 SSA551B017C SENSOR HUMIDITY 1 1 1 2...

Страница 84: ...82 12 SRK T 130 CRBE0347 5 14 15 13 13 15 16 2 3 4 6 12 15 9 10 7 11 15 15 8 1 2 0 55...

Страница 85: ...SERVICE 1 1 1 5 SSA944B031A HANDLE 1 6 RCR124A102 PANEL ASSY TOP 1 7 8 RCR125A101 PANEL ASSY REAR 1 1 1 1 2 8 SSA944B031A HANDLE 1 9 10 PCA142A065F COVER FRONT 1 1 1 1 2 10 S751W25X GROMMET 1 1 1 1 2...

Страница 86: ...84 12 SRK T 130 CRBE0348 5 1 17 6 2 3 16 9 4 18 14 19 10 8 15 7 12 13 61 1 2 11 5 3 6 55...

Страница 87: ...CCUMULATOR ASSY 1 8 PCA381A062C VALVE SERVICE 5 8 1 1 1 1 2 GAS 9 SSA382C068 VALVE S 4WAY 1 20S 10 15 RCR304A109A PIPING ASSY EXPAN 1 1 1 1 2 10 SSA387F065 VALVE BODY EXP 1 1 1 1 2 EEV 11 SSA357A005 S...

Страница 88: ...86 12 SRK T 130 CRBE0349 23 10 5 6 6 5 11 22 21 20 14 18 17 19 16 15 2 1 3 7 8 4 7 8 9 13 12 2 11 0 1 24 5514...

Страница 89: ...9 S751W30X GROMMET 1 35 10 PCA141A096B PLATE BAFFLE 1 11 SSA913D020 SCREW TAP WASHER 10 1 1 1 2 M5 10 12 RCR141A104 PLATE ASSY BAFFLE 1 13 RCR141A107 PLATE ASSY BAFFLE U 1 14 AHT201C264C COMPRESSOR A...

Страница 90: ...88 12 SRK T 130 CRBE0350 CONTROL UNIT 18 15 3 5 6 7 20 7 19 14 13 4 10 9 12 11 1 2 17 16 8 CONTROL PARTS SET...

Страница 91: ...4D173 CORE FERRITE 1 9 RCR504A040 WIRING ASSY 1 PWB2 CNA TB2 1 TB2 2 TB2 3 10 RPC504A917A HARNESS ASSY 1 PWB1 CN20V PWB2 CN20V 11 RCT504A001A HARNESS ASSY 1 PWB2 CNMAIN PWB1 CNSUB 12 RCR504A036A HARNE...

Страница 92: ...VERTER RESIDENTIAL AIR CONDITIONERS Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice...

Отзывы: