58
-
'12 • SRK-T-130
'09•SRK-DB-087D
Outdoor fan motor error
Rotor lock
(8) Phenomenon observed after shortcircuit, wire breakage on sensor
(a) Indoor unit
Defective fan motor, connector poor
connection, defective outdoor PCB
Defective compressor, defective
outdoor PCB
Sensor
Operation
mode
Phenomenon
Shortcircuit
Disconnected wire
Room temperature
sensor
Cooling
Heating
Heat exchanger
sensor
Cooling
Heating
Humidity sensor
Cooling
Heating
■
Humidity sensor operation
Failure mode
Control input circuit resding
Air conditioning system operation
①
②
①②
①
②
See page 55.
(8) Phenomenon observed after shortcircuit, wire breakage on sensor
(a) Indoor unit
Sensor
Operation
mode
Phenomenon
Shortcircuit
Disconnected wire
Room temperature
sensor
Cooling
Heating
Heat exchanger
sensor
Cooling
Heating
Humidity sensor
Cooling
Heating
■
Humidity sensor operation
Failure mode
Control input circuit resding
Air conditioning system operation
①
②
①②
①
②
'09•SRK-DB-087D
(9) Checking the indoor electrical equipment
(a) Indoor PCB check procedure
(b) Outdoor unit
Is there voltage between terminal
blocks
①
and
②
? (AC 220/230/240
V)
Indoor electrical components
are normal.
Is the voltage between terminal
blocks
②
and
③
oscillating between
DC 0 and 20V?
Inspect power source
for outdoor unit.
Replace fuse.
Replace indoor PCB.
Is the fuse burnt out? (3.15 A)
YES
YES
YES
NO
NO
NO
(b) Indoor unit fan motor check procedure
1) Indoor PCB output check
① ④
⑤
2) Fan motor resistance check
⑥
⑤
④
③
②
①
⑥
⑤
④
③
②
①
FM
I
DC15V
Indoor PCB
DC 308~336V
DC several V
(4~6 V)
CNU
(–)
GND
Blue
Yello
w
White
Black
Red
Sensor
Operation
mode
Phenomenon
Shortcircuit
Disconnected wire
Heat exchanger
sensor
Cooling
Heating
Ourdoor air
temperature sensor
Cooling
Heating
Discharge pipe
sensor
All modes
Measuring point
Resistance when normal
① − ③
−
④ − ③
−
Measuring
point
Resistance when
normal
① − ③
④ − ③
⑤ − ③
⑥ − ③
Defrosting is performed for 10 minutes at approx. 35 minutes.
Defrosting is performed for 10 minutes at approx. 35 minutes.
k
Содержание SRC92ZL-S
Страница 2: ...TECHNICAL MANUAL...
Страница 8: ...12 SRK T 130 3 Remote control a Wireless remote control Unit mm 60 17 3 150...
Страница 55: ...53 12 SRK T 130 Service data record form 47...
Страница 75: ...73 12 SRK T 130 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control...
Страница 76: ...74 12 SRK T 130...
Страница 77: ...75 12 SRK T 130 PARTS LIST INDOOR UNIT SRK92ZL S OUTDOOR UNIT SRC92ZL S...
Страница 81: ...79 12 SRK T 130 MEMO...
Страница 84: ...82 12 SRK T 130 CRBE0347 5 14 15 13 13 15 16 2 3 4 6 12 15 9 10 7 11 15 15 8 1 2 0 55...
Страница 86: ...84 12 SRK T 130 CRBE0348 5 1 17 6 2 3 16 9 4 18 14 19 10 8 15 7 12 13 61 1 2 11 5 3 6 55...
Страница 88: ...86 12 SRK T 130 CRBE0349 23 10 5 6 6 5 11 22 21 20 14 18 17 19 16 15 2 1 3 7 8 4 7 8 9 13 12 2 11 0 1 24 5514...
Страница 90: ...88 12 SRK T 130 CRBE0350 CONTROL UNIT 18 15 3 5 6 7 20 7 19 14 13 4 10 9 12 11 1 2 17 16 8 CONTROL PARTS SET...