5-122
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
5.4.8 REQ instruction
J_REQ, G_REQ
(1) Remote RUN/STOP
Request data (all set by the user)
Response data (all set by the system)
Device
Item
Description
Remote
RUN
Remote
STOP
[0]
Request type
0010
H
: When station number is specified in
[5]
0030
H
: When all stations a group is specified in
[5]
[1]
Sub-request type
0001
H
: Remote RUN
0002
H
: Remote STOP
[2]
Mode
Specify whether to forcibly execute remote RUN/STOP.
0001
H
: No forced execution
0003
H
: Forced execution (This setting can be specified for
remote RUN.)
(The forced execution is used when the station stopped by
remote STOP failed to start in remote RUN to forcibly start it by
remote RUN from another station.)
[3]
Clear mode
Specify the CPU device memory status only for remote RUN.
0000
H
: Not cleared (Note that the local devices are cleared.)
0001
H
: Cleared (excluding the latch range and settings in
remote RUN)
0002
H
: Cleared (including the latch range and settings in remote
RUN)
Device
Item
Description
Remote
RUN
Remote
STOP
[0]
Request type
0090
H
: When station number is specified in
[5]
00B0
H
: When all stations or a group is specified in
[5]
[1]
Sub-request type
0001
H
: Remote RUN
0002
H
: Remote STOP
S2
○
S1
○
S1
S2
S2
S2
d1
○
S1
○
S1
d1
Содержание QCPU
Страница 1: ...Structured Programming Manual Mitsubishi Programmable Controller QCPU Special Instructions ...
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 28: ...2 10 MEMO ...
Страница 32: ...3 4 MEMO ...
Страница 38: ...4 6 MEMO ...
Страница 234: ...5 196 MEMO ...
Страница 238: ...Index 4 MEMO ...
Страница 241: ......