5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
5.4.5 SEND instruction
J_SEND, G_SEND
*1 :
Data are stored only when 1 is set in bit 7 of Error completion type (
[0]).
*2 :
Logical channel setting is not available for the CC-Link IE controller network module.
[8]
Arrival monitoring time
Specify the monitoring time required for instruction completion. (Setting
is available when Execution type is set to '1: With arrival confirmation'
in [0].)
If the instruction is not completed within this time, it is resent by the
number of times specified in
[7].
0 to 32767
User
[9]
Send data length
Specify the number of send data.
1 to 960
User
[10]
(Reserved)
–
–
–
[11]
Clock set flag
*2
Valid/invalid status of the data in the area starting from
[12] is stored.
0: Invalid
1: Valid
–
System
[12]
Clock data at the time of
error completion
*2
Clock data at the time of error completion are stored in BCD format.
–
System
[16]
Error-detected network
No.
*2
Network number of the station where an error was detected is stored.
(However, when an error was detected at the host station, the network
number is not stored.)
1 to 239: Network number
–
System
[17]
Error-detected station No.
*2
Number of the station where an error was detected is stored.
(However, when an error was detected at the host station, the network
number is not stored.)
–
System
Device
Item
Setting data
Setting range
Setting side
*1
S1
○
S1
○
S1
Description
Setting value
Ethernet
0 to TCP retransmission
timer value: Monitoring is
performed by the TCP
retransmission timer value.
(TCP retransmission timer
value + 1) to 16383:
Monitoring time (unit:
second)
0 to 16383
MELSECNET/H
CC-Link IE
controller network
0: 10 seconds
1 to 32767: 1 to 32767
seconds
0 to 32767
S1
Description
Setting value
Ethernet
Writing to the QCPU
1 to 960
(word)
Writing to the QnACPU
MELSECNET/H
CC-Link IE
controller network
Writing to the QCPU
1 to 960
(word)
Writing to the QnACPU
1 to 480
(word)
S1
S1
○
S1
S1
b15
b8 b7
to
b0
to
S
1
S
1
S
1
S
1
M
onth
(
01
H
to 12
H
)
Hou
r
(
00
H
to 23
H
)
S
econ
d
(
00
H
to 59
H
)
Ye
ar
(
00
H
to 99
H
)
Fi
rs
t two
d
igit
s
Ye
ar
(
00
H
to 99
H
)
L
as
t two
d
igit
s
Da
y
(
01
H
to 31
H
)
M
inute
(
00
H
to 59
H
)
Da
y of week
(
00
H
to 06
H
)
00
H
(S
un.
)
to 06
H
(Sa
t.
)
[12 ]
[13 ]
[14 ]
[15 ]
S1
S1
Ethernet
MELSECNET/H
1 to 64
CC-Link IE controller
network
1 to 120
○
S1
Содержание QCPU
Страница 1: ...Structured Programming Manual Mitsubishi Programmable Controller QCPU Special Instructions ...
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 28: ...2 10 MEMO ...
Страница 32: ...3 4 MEMO ...
Страница 38: ...4 6 MEMO ...
Страница 234: ...5 196 MEMO ...
Страница 238: ...Index 4 MEMO ...
Страница 241: ......