Function
This instruction registers a user frame.
C
ont
r
o
l Da
t
a
G(P)_PUTE
P: Executing condition
:
indicates any of the following
instructions.
G_PUTE
GP_PUTE
Input argument
EN:
Executing condition
:Bit
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
:ANY16
s1:
Variable that stores control data
:Array of ANY16 [0..3]
s2:
Start number of the device that stores read registration data
:ANY16
Output argument
ENO:
Execution result
:Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
−
−
−
−
−
Device
Item
Setting data
Setting range
Setting side
[0]
Registration/deletion specification
Specify whether to register the user frame of the
number specified by
[2].
1: Registered 3: Deleted
1, 3
User
[1]
Registration/deletion result
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
–
System
[2]
Frame No.
Specify the user frame number.
1000 to 1199
User
[3]
Number of registered bytes
1 to 80: Number of bytes of the user frame to be
registered.
* Specify any number in the range from 1 to 80 as a
dummy when '3: Deleted' is selected.
1 to 80
User
Structured ladder
ST
G_PUTE
EN
ENO
U
n
*
s
1
s
2
d
G_PUTE
(EN, U
n
*, s
1
, s
2
, d);
ENO:=
S1
S2
dd
S1
○
S1
S1
S1
S1
Содержание QCPU
Страница 1: ...Structured Programming Manual Mitsubishi Programmable Controller QCPU Special Instructions ...
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 28: ...2 10 MEMO ...
Страница 32: ...3 4 MEMO ...
Страница 38: ...4 6 MEMO ...
Страница 234: ...5 196 MEMO ...
Страница 238: ...Index 4 MEMO ...
Страница 241: ......